The plans and specifications resubmitted for the construction
of Trunk's Bar & Grill, 450 North Linden Circle, Fort Collins,
Colorado, have been reviewed by this department. The following
items were not clearly specified in the plans or were not in
compliance with the Rules and Regulations Governing the Sanitation
of Food Service Establishments in the State of Colorado. These
items must be clearly specified in writing or be modified�t:o be in
compliance with the above regulations prior to approval of the
submitted plans. The plans are not approved at this. time. .All
plans must,.be approved prior to commencement of.conistruction.
1) All food service- equipment must be....NSF...:(National'.Sanitation
Foundation) approved or its equivalent. 7.The following
equipment and their specific model numbers were not found in
the most current NSF or equivalent commercial listing or were
visually inspected and not approved for use: Perlick blender
stand TS60 (8B), ice machine (no plan number), and Amana
microwaves RFS9B (no plan number). Provide additional
information on the blender stand and microwaves units
verifying that they meet current NSF standards. Provide a new
ice bin for the ice machine or an alternate commercial unit of
comparable size.
The following equipment was visually inspected. and found to be
acceptable only with modifications as noted during the
December 23, 1997 inspection: Dalton walk-in freezer (10),
vegetable prep sink (15), kitchen exhaust hood (4), wait area
table (14), Wolf flat grill (10), bar spacers (7), and Perlick
keg dispenser (C-5122A). Please make the required
modifications to this equipment so they can be approved for
use.
The following equipment is not approved at this time due to
lack of information. Submit make and model numbers, and
specification sheets on the following equipment: dish machine
(11) , fryer (8) , Silver King freezer, and bottle coolers (4B) .
It is understood that the charbroiler (7) has been eliminated
from the plans.
Trunk's Bar & Grill
December 29, 1997
Page 2
Be advised, custom made equipment and used equipment cannot be
approved until it is visually inspected.
2) The proposed menu has been reviewed. Work top refrigeration
in the kitchen is limited to one cold table. There does not
appear to be sufficient conveniently located work top
refrigeration to store the appetizers, salad fixings, sandwich
items, burger, items, and pizza toppings listed on the menu.
5U�:1Clent CO11Vei7icii-1 1GCatcd refrigeration facilities must
be provided to assure the maintenance of potentially hazardous
food at the required temperatures during storage and
preparation. Please provide additional work top refrigeration
in the kitchen.
3) Acknowledged.
4) Acknowledged.
5) Be advised that no appurtenances, such as syrup lines,
carbonators, drop -in cold plates, drain lines or bottle
holders are permitted in potable ice bins or ice machines or
any unit used to store potable ice.
6) Be advised, make-up air must be filtered, tempered during
winter months (when exhaust exceeds 2500 CFM), and
mechanically introduced into the establishment at a volume
equal to or greater than what is being exhausted; must be
dis-ributed through several registers to establish necessary
air patterns so as not to short circuit exhaust systems; the
kitchen should be under a slightly negative pressure so that
make up air. can be exhausted through the kitchen exhaust
sys-em after it moves from the dining area into the kitchen.
The kitchen exhaust hood switch must be interlocked with the
make up air system.
The plans for the establishment's exhaust/ventilation system
have been reviewed and are not approved at this time.. Please
submit the following information:
a) A complete, updated, ventilation schedule for the entire
building. Include proposed air flows (return air, supply
air, outside air) in CFM, the locations of all return and
supply air registers with their CFM ratings,. air flows
inside the kitchen hood, and make/model numbers and
specifications of all air handling units (HVAC & exhaust)
to be utilized.
Trunk's Bar & Grill
December 29, 1997
Page 3
b)
Approved
during
December 23, 1997 inspection.
c)
The CFM
ratings
of the restroom exhaust fans.
A charbroiler is specified on the kitchen grill line but the
kitchen exhaust hood is a compensating unit. Charbroilers are
not approved beneath compensating hoods. During the December
23, 1997 inspection Mrs. Patricia Smith indicated that the
charbroiler was eliminated from the plans.
All above information must be provided in written form with or
as part of the shop drawings of the hood and ventilation
system.
All hoods, approved or not, must be visually inspected and
approved in writing by this department prior to installation.
8) Information in the resubmitted plans indicated that a spray
hose would be connected to the mop sink for cleaning purposes.
The addition of the spray hose will cause the establishments
planned hot. water requirements to exceed what can be provided
by the existing water heating units (Rheem 360,000 BTU and
A.O. Smith 40,000 BTU).
A commercial water heater that can achieve a minimum recovery
rate .of 400 gallons/hour at 100OF rise if gas, or 333
gallons/hour at 100°F rise if' electric, or has a 443,822 BTU
rating or has a 98 KW (kilowatt) rating is required.
Submit make, model -number and recovery rate: of a proposed
commerci-EAl water heater that meets the above specifications.
Without the spray hose the Rheem 360,000 BTU and A.O. Smith
40,000 BTU water heaters, installed on the second floor are
adequate to meet the establishments hot water requirements.
However, these units must be connected so they work together
as one unit for approval. Please provide information
verifying that the water heaters are connected in such a way.
10) Drainboards of the kitchen 3-compartment sink were found
shorter than 36" inches in length. Additional commercial wire
racking will be required over the sink to at least make up the
difference. Submit information on what will be provided. '
11) Submit information on the make and model number of the
chemical dispensing unit to be provided for the dish. machine.
Trunk's Bar & Grill
December 29, 1997
Page 4
12) Acknowledged. Be advised, chemical dispensing systems when
used with mop sinks require separate water lines or vented
dual check backflow prevention devices (designed for in -line.
continuous pressure applications). Provide information on
what will be provided.
13) Approved. During the December 23, 1997 equipment inspection
you indicated that an additional hand sink would be provided
on the kitchen wall northeast of the cold. unit (19). Revised
plans showing new locations for the main bar handsinks were
also provided. The revised locations of the bar handsinks and
the location of the additional kitchen handsink were approved.
14) Be advised that all handsinks must be provided with hot and
cold running water under pressure through a mixing valve,
single service hand towels from a dispenser, and soap.
15) As discussed during the December 23, 1997 ' equipment
inspection:. the vegetable sink (15) and beverage station (14)
require indirect drainage to sewer; the beer tap stations in
the main bar will be drained indirectly to floor sinks in the
ice machine room and utility room; and the walk-in cooler (1)
and walk-in freezer (10) will drain indirect to floor drains
outside the boxes. Submit information on the drainage of the
dishmachine (11), and 3-compartment sink (12).
16) Be advised, floor drains provided inside walk-in refrigerators
must drain through an air gapped drain .line and to a floor
drain/sink outside the cooler box. Floor drains that directly
drain to sewer inside walk-in refrigeration units are not
approved and require modification or removal. Provide
information on.which walk-in cooler(s) (kitchen and/or bar)
have floor drains inside of them and whether these drains are
air -gapped or not.
17) Acknowledged. Be advised, floor sinks must not be installed
under equipment or cabinetry where they cannot be cleaned.
23) Flcors, walls, ceilings, counter tops, storage shelves,
cabinets and all work surfaces located within the kitchen,
storage rooms, janitor's closet, restrooms, waitress station,
serving area, bar, dishwashing areas, walk-ins, and all food
prep areas must be of an approved material that is smooth,
durable, easily cleanable, and nonabsorbent.
Trunk's Bar & Grill
December 29, 1997
Page 5
a) Submit information on the floor, wall, and ceiling
materials and finishes to be used: in the 2nd floor
.liquor storage area.
c) All floor/wall junctures and stationary equipment floor
junctures in the kitchen, storage rooms, janitor's
closet, restroom, waitress station, serving area, bar,
dishwashing areas, walk -iris, and all food prep areas must
be provided with approved concave coving. Be acvised,
coving adhesive is not approved by itself, 4" inch rubber
cove base sealed on its top and bottom edges is the
minimum requirement.
d) In the dishwashing area portions of the floor tiling are
cracked around the sunken areas below the general floor
grade. The current finishes of these areas are
unacceptable. These areas must be finished to be smooth,
durable, easily cleanable, and nonabsorbent. Submit
information on what will be done in these areas.
25) Solid metal shelving in the walk-in cooler and freezer is not
approved, unless NSF approved for use in walk-ins. Wooden
shelves, pallets, or any wooden interior finishes are not
permitted in walk-in coolers or freezers. Metal shelves in
the walk-in cooler and freezer must be of an approved metal
wire construction. Submit information/specification sheets on
all storage shelving to be provided in kitchen areas, storage
rooms, and the walk-in cooler/freezers.
26) Acknowledged.
27) Approved.
28) Acknowledged.
The plans are not approved at this time. Once items # 1, 2,
6, 8, 10, 11, 12, 15, 16, 23(a',d), and 25 have been submitted in
writing, the plans will be reviewed for final approval. After the
last item is resubmitted, the department will review the plans and
resubmittals within 10 days.
Be advised that Colorado Revised Statutes (1989) 12-44-206
require plans and specifications be submitted to the local health
department and approved prior to beginning construction.
Trunk's Bar & Grill
December 29, 1997
Page 6
Please feel free to contact this department if questions
arise, or if I can be of further service at 498-6775.
Sincerely,
g�W
seoh Comello, R.E.H.S.
vironmentalHealth Specialist