Re: Construction Observation and Materials Testing Report – Submittal No. 4
Elizabeth Street Farms – Infrastructure Development
Fort Collins, Colorado
EEC Project No. 1184108
Mr. Donkle:
As requested, during the period of July 15 through July 27, 2019, Earth Engineering Consultants,
LLC (EEC) personnel provided construction observation and testing services for the referenced
project in Fort Collins, Colorado. The services provided during the referenced period were on a
part-time/on-call basis and included observations and field density testing of curb and gutter,
roadway, and sidewalk subgrade materials, roadway aggregate base course (ABC) and hot mix
asphalt (HMA) pavement materials and testing of cast-in-place concrete as described herein for
the referenced project. The results of the observation and testing services completed by EEC
personnel during the referenced period are included with this report.
Observations and Field Density Testing Services
On July 24, 2019, a proof roll observation was conducted on the prepared pavement subgrades
for the interior roadways and along the widening portion of West Elizabeth Street. The proof
roll consisted of visual observations of the effects with a loaded dual axle water truck
maneuvering along the roadway alignments. At the time of observation, the subgrades appeared
to be stable/suitable for placement of the pavement section.
During the referenced period, EEC personnel performed field density tests on prepared subgrade
materials within curb, gutter and sidewalk alignments as well as of ABC pavement materials as
presented herein, that had been placed and compacted prior to and/or during our various site
visits. The field density tests were completed at random locations within the areas tested and
were performed in general accordance with ASTM Specification D6938. Results of the field
density tests completed during the referenced period are shown on the attached summary sheet
Earth Engineering Consultants, LLC
EEC Project No. 1184108
August 20, 2019
Page 2
and approximate locations are “plotted” on the attached site diagram included with this report.
The field density test results met the compaction requirement of at least 95% of standard Proctor
maximum dry density and were within ±2% and/or ±3% of the material’s optimum moisture
content, where applicable.
Laboratory and Field Density Testing of HMA Pavement Material
During the referenced period, EEC personnel observed paving operations and obtained a sample
of the Grading S(75) HMA pavement materials, (Kehn Construction – Mix ID 638119) from the
site during paving operations along West Elizabeth Street as identified herein. Laboratory
testing for the collected HMA sample included determination of the binder content (by means of
ASTM D6307) and washed sieve analysis of the extracted aggregates (ASTM Specifications
C117 and C136). The percent asphaltic cement (AC) content and extracted aggregate gradations,
as presented herein, were performed without an ignition oven calibration of the aggregate and
AC materials used to produce the Grading S HMA materials. The uncorrected HMA laboratory
test results were within the acceptable oil content range for the approved mixes (i.e., within +/-
0.3% of optimum AC content). For the extracted aggregate portion, the results were, generally,
within the approved job mix formula tolerances for the Grading S mix. The results of the
laboratory tests completed by EEC personnel are indicated on the attached summary sheets.
After compaction of the HMA pavement materials, EEC personnel performed density tests on
the in-place pavement using a nuclear moisture-density gauge. The density tests were completed
at random locations as shown on the enclosed summary sheets within the pavement improvement
areas, and were performed in general accordance with ASTM Specification D2950. Results of
the field density tests completed during the referenced period are indicated on the attached
summary sheet. Those test results were within the project compaction requirements of 92% to
96% of the material’s maximum theoretical specific gravity (Rice Value) as indicated on the mix
design as provided to us by Kehn Construction.
Testing of Cast-in-Place Concrete
During the referenced period, EEC personnel observed, and tested Portland cement concrete
delivered to the site for placement as indicated on the enclosed daily reports for the referenced
project, (please refer to Set Nos.2 through 4). Field testing performed on the plastic concrete
Proctor Designation A Class 6
Maximum Dry Density (pcf) 109.5 137.2
Optimum Moisture Content (%) 16.5% 6.0%
Required Moisture Variance OMC +/-2% N/A
Required Percent Compaction 95% 95%
Laboratory Method ASTM D-698 ASTM D-698
Compliance with
Project Specs
Elev. / Lift
No.
Material
(Proctor)
Percent
Moisture
Dry
Density
Moisture
(Pass /
Fail)
%Comp.
(Pass /
Fail)
70 7/17 1 Curb & Gutter Subgrade - See Diagram FSG Class 6 5.8% 131.5 -0.2% 96% N/A Pass
71 7/17 2 Curb & Gutter Subgrade - See Diagram FSG Class 6 7.1% 130.8 1.1% 95% N/A Pass
72 7/17 3 Curb & Gutter Subgrade - See Diagram FSG Class 6 5.3% 133.0 -0.7% 97% N/A Pass
73 7/24 1 Base - See Diagram FG Class 6 4.7% 131.6 -1.3% 96% N/A Pass
74 7/24 2 Base - See Diagram FG Class 6 4.5% 130.9 -1.5% 95% N/A Pass
75 7/24 3 Base - See Diagram FG Class 6 4.6% 131.2 -1.4% 96% N/A Pass
76 7/24 4 Base - See Diagram FG Class 6 4.5% 131.1 -1.5% 96% N/A Pass
77 7/25 1 Base - See Diagram -0.5 Class 6 3.9% 134.2 -2.1% 98% N/A Pass
78 7/25 2 Base - See Diagram -0.5 Class 6 4.0% 136.1 -2.0% 99% N/A Pass
79 8/1 1 Sidewalk Subgrade - See Diagram FSG A 14.8% 108.5 -1.7% 99% Pass Pass
EARTH ENGINEERING CONSULTANTS, LLC
Approximate Test Location / Notes
Daily Test
Number
Date
Consecutive
Test Number
Moisture
Variance
Percent
Compaction
Field Test Results
Project Name:
SUMMARY OF FIELD DENSITY TESTS
Location:
Project No:
Date:
1184108
August 2019
Elizabeth Street Farms - Infrastructure Development
Fort Collins, Colorado
6/26-6
6/26-2
6/26-5
6/26-4
6/26-3
6/26-1
7/12-3 7/12-2
7/12-1
7/1-3
7/1-4
7/1-2
7/1-1
7/24-4
8/1-1
7/24-3
7/24-2
7/24-1
7/17-3
7/17-2
7/17-1
7/25-1
7/25-2
Field Density Test Location Diagram
Elizabeth Street Farms - Fort Collins, Colorado
EEC Project #: 1184108
Fill, Subgrade, & Aggregate Base
EARTH ENGINEERING CONSULTANTS, LLC
Elizabeth Street Farms - Infrastructure Development
Location:
EEC Project No.:
Fort Collins, Colorado
1184108.1
No. 16
7.5%
Project:
39%
No. 200
16%
4.7%
--
8.7%
26%
1"
No. 30
3/4"
1/2"
3/8"
No. 4
No. 8
EARTH ENGINEERING CONSULTANTS, LLC
SUMMARY OF ASPHALT EXTRACTION/GRADATION TEST RESULTS
GRADATION OF EXTRACTED AGGREGATE (ASTM C 136 & C 117)
SIEVE SIZE PERCENT PASSING SPECIFICATION
638119
Sample Information
Date Sampled:
Sample Location:
Ticket No.
S
Don Kehn
Bottom
Supplier
Sample Time: 11:00 AM
29%
11%
100%
100%
100%
93%
84%
67%
100%
100%
93%
84%
67%
53%
72%
21%
Mix Information
July 25, 2019
Lift:
50' from W End of Rd on Elizabeth
6430-2
57%
43%
0.3%
Project Name:
Location:
S
152.8
Measured Gauge Required Pass or
Lift No. Density Correction % Comp. Fail
17/251 Bottom S 144.3 0.0 144.3 94% 92-96% Pass
27/252 Bottom S 141.4 0.0 141.4 93% 92-96% Pass
37/253 Bottom S 141.7 0.0 141.7 93% 92-96% Pass
47/254 Bottom S 145.3 0.0 145.3 95% 92-96% Pass
Daily Test
Number
Project Specifications
See Diagram
See Diagram
Material
Compliance With
See Diagram
EARTH ENGINEERING CONSULTANTS, LLC
Field Test Results
Approximate Test Location/Notes
Percent
Compaction
SUMMARY OF ASPHALT DENSITY TESTS
Corrected
Density
Consecutive
Test Number
Date
See Diagram
1184108
Date: August 2019
Elizabeth Street Farms - Infrastructure Development Project No:
Fort Collins, Colorado
Material Designation
Rice Value
7/25-4
7/25-3
7/25-2
7/25-1
Field Density Test Location Diagram
Elizabeth Street Farms - Fort Collins, Colorado
EEC Project #: 1184108
Asphalt Surfacing
EARTH ENGINEERING CONSULTANTS, LLC
Placement Date:
Placement Location:
Concrete Supplier:
Water Added on Site:
of
Required 28 Day Compressive Strength (psi):
B
D
D1
D2
Project Number:
Martin Marietta
1184108 Report Distribution:
Gerrard Excavating - Tom Donkle (tdonkle@gerrardinc.com)
Project: Elizabeth Street Farms – Infrastructure Development
5110
2 08/15/19 28 62440
2 08/15/19 28 64230 8 4 12.57 Shear
8 4 12.57 Shear 5160
8 4 12.57 Shear 4970 5080
2 08/15/19 28 64900
2 07/25/19 7 50740 8 4 12.57 Shear 4040 4040
Failure Strength Strength
Number Tested (days) (lbs) (in) (in) (in2) Type (psi) (psi)
Specimen Date Age Applied Load Height Diameter Area
Average
Maximum Cylinder Cylinder Compressive Compressive
----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Slump (in) ASTM C143 4"
Air Content (%) ASTM C231 5%
Unit Weight (pcf) ASTM C138 146.2 ----
Concrete Temperature (deg F) ASTM C1064 90 90° Max
Air Temperature at Placement (deg F) 78
FIELD TEST DATA
TEST RESULTS SPECIFICATIONS
Comments:
Yards: 10 10
4000 EEC Technician: TA
Batch Time: 7:17 AM Sample Time: 9:00 AM
Mix Code: A4780 None
Curb & Gutter - Along Elizabeth Street
Martin Marietta Type of Placement: Chute
7/18/2019 Test No.: 2
Ticket Number: 49160800 Truck Number:
GENERAL INFORMATION
1918
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
Placement Date:
Placement Location:
Concrete Supplier:
Water Added on Site:
of
Required 28 Day Compressive Strength (psi):
Project Number:
NO CYLINDERS MADE
Martin Marietta
1184108 Report Distribution:
Gerrard Excavating - Tom Donkle (tdonkle@gerrardinc.com)
Project: Elizabeth Street Farms – Infrastructure Development
(in) (in2) Type (psi) (psi)
Failure Strength Strength
Number Tested (days) (lbs) (in)
Specimen Date Age Applied Load Height Diameter Area
Average
Maximum Cylinder Cylinder Compressive Compressive
----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Slump (in) ASTM C143 3.5"
Air Content (%) ASTM C231 6.1%
Unit Weight (pcf) ASTM C138 144.6 ----
Concrete Temperature (deg F) ASTM C1064 80 90° Max
Air Temperature at Placement (deg F) 82
FIELD TEST DATA
TEST RESULTS SPECIFICATIONS
Comments:
Yards: 11 11
4000 EEC Technician: RD
Batch Time: 8:27 AM Sample Time: 9:05 AM
Mix Code: A4780 None
Sidewalk Across Road at NW Corner of Site
Martin Marietta Type of Placement: Chute
7/19/2019 Test No.: 2A
Ticket Number: 49160889 Truck Number:
GENERAL INFORMATION
628
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
Placement Date:
Placement Location:
Concrete Supplier:
Water Added on Site:
of
Required 28 Day Compressive Strength (psi):
B
Project Number:
Martin Marietta
1184108 Report Distribution:
Gerrard Excavating - Tom Donkle (tdonkle@gerrardinc.com)
Project: Elizabeth Street Farms – Infrastructure Development
3 07/29/19 7 49870 8 4 12.57 Shear 3970 3970
Failure Strength Strength
Number Tested (days) (lbs) (in) (in) (in2) Type (psi) (psi)
Specimen Date Age Applied Load Height Diameter Area
Average
Maximum Cylinder Cylinder Compressive Compressive
----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Slump (in) ASTM C143 4.75"
Air Content (%) ASTM C231 6%
Unit Weight (pcf) ASTM C138 146.3 ----
Concrete Temperature (deg F) ASTM C1064 94 90° Max
Air Temperature at Placement (deg F) 77
FIELD TEST DATA
TEST RESULTS SPECIFICATIONS
Comments:
Yards: 4.5 4.5
4000 EEC Technician: TA
Batch Time: 2:29 PM Sample Time: 3:20 PM
Mix Code: HE4348 None
Curb & Gutter / Sidewalk
Martin Marietta Type of Placement: Chute
7/22/2019 Test No.: 3
Ticket Number: 49161038 Truck Number:
GENERAL INFORMATION
225
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
Placement Date:
Placement Location:
Concrete Supplier:
Water Added on Site:
of
Required 28 Day Compressive Strength (psi):
B
Project Number:
Martin Marietta
1184108 Report Distribution:
Gerrard Excavating - Tom Donkle (tdonkle@gerrardinc.com)
Project: Elizabeth Street Farms – Infrastructure Development
4 07/30/19 7 49300 8 4 12.57 Shear 3920 3920
Failure Strength Strength
Number Tested (days) (lbs) (in) (in) (in2) Type (psi) (psi)
Specimen Date Age Applied Load Height Diameter Area
Average
Maximum Cylinder Cylinder Compressive Compressive
----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Slump (in) ASTM C143 4"
Air Content (%) ASTM C231 5.8%
Unit Weight (pcf) ASTM C138 ----
Concrete Temperature (deg F) ASTM C1064 86 90° Max
Air Temperature at Placement (deg F) 86
FIELD TEST DATA
TEST RESULTS SPECIFICATIONS
Comments:
Yards: 10 10
4000 EEC Technician: ZG
Batch Time: 5:02 PM Sample Time: 6:00 PM
Mix Code: A4780 None
Sidewalk - N Side of W Elizabeth St, S of Brick Building
Martin Marietta Type of Placement: Chute
7/23/2019 Test No.: 4
Ticket Number: 49161127 Truck Number:
GENERAL INFORMATION
1735
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
--
SPECIFICATION
5.4% +/-
--
--
--
--
100%
53%
90%
81%
ASPHALT BINDER CONTENT BY IGNITION METHOD (ASTM D 6307)
No. 50
--
No. 100
75
ASPHALTIC CEMENT CONTENT (%)
5.6%
1 1/2"
Mix ID No.:
Grading:
Truck No.: 71