HomeMy WebLinkAboutRIDGEWOOD HILLS FOURTH FILING - Filed FDT-FIELD DENSITY TEST - 2020-01-29 (4)FIELD DENSITY TEST REPORT
Report Number:
Service Date:
Report Date:
Task:
20191099.0035
11/18/19
11/20/19
Site Work / Utilities / CIty ROW
1901 Sharp Point Dr, Ste C
Fort Collins, CO 80525-4429
970-484-0359
Client
M Timm Development
Attn: Bill Timm
233 E Carrillo St Ste D
Santa Barbara, CA 93101
Ridgewood Hills Apartments
7363 Avondale Road
Fort Collins, CO 80525
Project
Project Number: 20191099
Lab Test Data
(%)
Compaction
Project Requirements
(%)
Content
Water
No.
Mat.
Material Information
Density
Max. Lab
(%)
Content
Water
Optimum
Ref. No.
Proctor Laboratory
Classification and Description Test Method (pcf)
1 20191099.0007 Sandy Lean Clay ASTM D698 16.2 108.4 15.2-19.2 Min 95
Field Test Data
No. Test Location Elev. No.
Test Lift / Mat. Depth Density
Probe Wet
Content
Water
(%)
Content
Water
Density
Dry
(%)
Percent
Compaction
(in) (pcf) (pcf) (pcf)
Storm line B backfill - Avondale
1 At Inlet N of Bld 1 (west inlet) -1' 1 8 123.7 17.6 16.6 106.1 98
2 0' 1 8 122.2 17.9 17.2 104.3 96
3 30' East of west inlet -1' 1 8 121.9 17.3 16.5 104.6 96
4 0' 1 8 125.3 17.5 16.2 107.8 99
5 70' East of west inlet -1' 1 8 122.3 17.3 16.5 105.0 97
6 0' 1 8 120.0 15.9 15.3 104.1 96
7 50' West of East inlet (NE of Bld
5)
-1' 1 8 122.3 17.1 16.3 105.2 97
8 0' 1 8 120.7 16.4 15.7 104.3 96
9 10' West of East inlet -1' 1 8 120.3 16.2 15.6 104.1 96
10 0' 1 8 122.8 16.7 15.7 106.1 98
Comments:
Datum: 0= Finish sewer backfill elevation Std. Cnt. M: 542 Std. Cnt. D: 1756
Test and/or retest results on this report meet project requirements as noted above.
S/N: 17271 Make: Troxler Model: 3440 Last Cal. Date: 01/16/2019
Services:
Reported To:
Contractor:
Kim w/ CoFC
M. Timm
Eric Buol
Project Manager
Report Distribution:
(1) M Timm Development, Bill Timm (1) City Of Fort Collins CO, Kim Keiswetter
(1) Dirt One Excavating, Tom Thompson (1) M Timm Development, Kevin Egan
(1) M Timm Development, Larry McGee (1) Terracon Consultants, Inc., Eric Bernhardt
Reviewed By:
Terracon Rep.: Christopher Rivera
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11-16-12, Rev.7 Page 1 of 1