RE: Elderhaus Adult Daycare Major Amendment, MJA140004, Round Number 3
Please see the following summary of comments from City staff and outside reviewing
agencies for your submittal of the above referenced project. If you have questions about
any comments, you may contact the individual commenter or direct your questions through
the Project Planner, Rebecca Everette, at 970.416-2625 or reverettei@fcgov.com.
Comment Summary:
Department: Engineering Development Review
Contact: Tyler Siegmund, 970-416.2772, tsieomund(a)_fcgov.com
Topic: General
Comment Number: 1
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
kgov. corn1developmentreview
Comment Originated: 10/14/2014
01/09/2015The non-exclusive access easement on the property to the east
appears to be a private access and private utility easement and was not
dedicated to the City or for public access or public utility installation. Further
discussion with PFA and the utility providers is needed to determine if an
emergency access easement and public utility easement are needed on this
property to serve the Elderhaus site.
Response: The easement on the property to the east has been re -written to the requirements of
PFA and the city and a new easement agreement is being submitted for recordation as part of this
package.
10/14/2014: Is the non-exclusive easement that is referenced on the plat
existing or proposed? If this easement exists please include the reference
number that was assigned when it was recorded. If proposed, it appears that it
falls outside of the property that is to be platted as part of this project (6815 S
College Ave). This easement will need to be dedicated by separate document
by the property owner. There is a separate process and fee to dedicate
easements by separate document. You can contact me for additional
information on the process to dedicate easements by separate document or
Comment Number: 1
Comment Originated: 10/10/2014
10/10/2014:
Building Permit Pre -Submittal Meeting
Pre -Submittal meetings are offered to assist the designer/builder by assuring, early on in the design,
that the new commercial or multi -family projects are on track to complying with all of the adopted City
codes and Standards listed below. The proposed project should be in the early to mid -design stage
for this meeting to be effective and is typically scheduled after the Current Planning conceptual review
meeting. Applicants of new commercial or multi -family projects are advised to call 416-2341 to
schedule a pre -submittal meeting. Applicants should be prepared to present site plans, floor plans,
and elevations and be able to discuss code issues of occupancy, square footage and type of
construction being proposed.
Construction shall comply with the following adopted codes as amended:
2012 International Building Code (IBC)
2012 International Residential Code (IRC)
2012 International Energy Conservation Code (IECC)
2012 International Mechanical Code (IMC)
2012 International Fuel Gas Code (IFGC)
2012 International Plumbing Code (IPC) as amended by the State of Colorado
2014 National Electrical Code (NEC) as amended by the State of Colorado
Accessibility: State Law CRS 9-5 & ICC/ANSI Al 17.1-2009.
Snow Load Live Load: 30 PSF / Ground Snow Load 30 PSF.
Frost Depth: 30 inches.
Wind Load: 100- MPH 3 Second Gust Exposure B.
Seismic Design: Category B.
Climate Zone: Zone 5
Energy Code Use
1. Single Family; Duplex; Townhomes: 2012 IRC Chapter 11 or 2012 IECC.
2. Multi -family and Condominiums 3 stories max: 2012 IECC residential chapter.
3. Commercial and Multi -family 4 stories and taller: 2012 IECC commercial chapter.
Fort Collins Green Code Amendments effective starting 1-1-2012. A copy of these requirements can
be obtained at the Building Office or contact the above phone number.
Elderhaus — project specific concerns:
1. Fire -sprinkler systems are required if adult day-care is provided on any building level except the
1st floor.
2. This must go through a change of occupancy process.
City of Fort Collins
Building Services
Plan Review
416-2341
Contact: Todd Reidenbach, ,
Topic: General
Comment Number: 2 Comment Originated: 10/15/2014
10/15/2014: No additional comments from GIS for this project.
Page 4 of 8
Department: Outside Agencies
Contact: Terry W. Farrill, P.E., ,
Topic: General
Comment Number: 1 Comment Originated: 10/14/2014
Fort Collins -Loveland Water District 1 South Fort Collins Sanitation District:
10/14/2014: The District requires a Reduced Pressure Principle Back -Flow -Prevention -Device (RP
Device) on the fire line and the domestic water service. The RP devices are to be located near the
porperty line along U.S. Highway 287. The existing double check valve and vault are to be removed.
Comment Number: 2 Comment Originated: 10/14/2014
Fort Collins -Loveland Water District / South Fort Collins Sanitation District:
10/14/2014: The District will require a grease trap/interceptor on the sanitary sewer service.
Comment Number: 3 Comment Originated: 10/14/2014
Fort Collins -Loveland Water District / South Fort Collins Sanitation District:
10114/2014: The District's Industrial Pretreatment Business Questionnaire needs to be completed and
submitted to the district. The Questionnaire can be obtained by email by contacting Terry Farrill, District
Engineer, at tfarrill@aol.com. Please do not hesitate to contact me at 226-3104, ext.104 if you have
any questions or require additional information.
Department: PFA
Contact: Jim Lynxwiler, 970.416.2869, jlynxwile[ftudre-fire.oro
Topic: General
Comment Number: 1
Comment Originated: 10/13/2014
10/13/2014: Major Amendment comments are consistent with prior Conceptual Review comments
dated 3110/2014.
Comment Number: 2 Comment Originated: 10/13/2014
10113/2014: FIRE LANE SPECIFICATIONS
The submitted material does not clearly delineate the limits of the fire lane nor does available
information appear to meet minimum requirements. A fire lane plan shall be submitted for approval
prior to installation. In addition to the design criteria already contained in relevant standards and
policies, any new fire lane must meet the following general requirements:
> Shall be dedicated and noted on the plat as an Emergency Access Easement (EAE) with
boundaries and limits of the easement clearly labeled.
> Minimum width of EAE to be 20 foot throughout and maintained unobstructed at all times with 14 foot
minimum overhead clearance.
> Be designed as a flat, hard, all-weather driving surface
> Fire lane must be capable of supporting 40 tons (80,000 lb). The 53,000 lb rating of the metal culvert
would not meet minimum requirements.
> Dead-end fire access roads in excess of 150 feet in length shall be provided with an approved area
for turning around fire apparatus.
> The required turning radii of a fire apparatus access road shall be a minimum of 25 feet inside and 50
feet outside (20' wide). Turning radii shall be detailed on submitted plans.
> Be visible by painting and/or signage, and maintained unobstructed at all times.
International Fire Code 503.2.3, 503.2.4, 503.2.5, 503.3, 503.4 and Appendix D; FCLUC 3.6.2(B)2006
and Local Amendments.
Page 5 of 8
Comment Number: 3
10/13/2014: WATER SUPPLY
Comment Originated: 10/13/2014
The submitted plans reference a "yard hydrant" approximately 350' from the building. More information
is required. Fire hydrants must be the type approved by the water district having jurisdiction and the
Fire Department. Hydrant spacing and flow must meet minimum requirements based on type of
occupancy.
IFC 508.1 and Appendix B: COMMERCIAL REQUIREMENTS: Hydrants to provide 1,500 gpm at 20 psi
residual pressure, spaced not further than 300 feet to the building, on 600-foot centers thereafter.
Comment Number: 4 Comment Originated: 10/13/2014
10/13/2014: PREMISE IDENTIFICATION
2012 IFC 505.1: New and existing buildings shall have approved address numbers, building numbers
or approved building identification placed in a position that is plainly legible, visible from the street or
road fronting the property, and posted with a minimum of six-inch numerals on a contrasting
background. Where access is by means of a private road and the building cannot be viewed from the
public way, a monument, pole or other sign or means shall be used to identify the structure. Details of
the monument sign shall be submitted for review and approval.
Comment Number: 5
10/13/2014: FIRE SPRINKLER SYSTEM
Comment Originated: 10/13/2014
A review of the existing sprinkler plan may be required. System alterations and upgrades require a
separate permit. Please contact Assistant Fire Marshal, Joe Jaramillo at 970416-2868 to discuss your
needs or determine need for a system evaluation.
Comment Number: 6 Comment Originated: 10/13/2014
10/13/2014: PUBLIC -SAFETY RADIO AMPLIFICATION SYSTEM
New and existing buildings require a fire department, emergency communication system evaluation.
For the purposes of this section, fire walls shall not be used to define separate buildings. Where
adequate radio coverage cannot be established within a building, public -safety radio amplification
systems shall be designed and installed in accordance with criteria established by the Poudre Fire
Authority. 2012 IFC 1103.2; Poudre Fire Authority Bureau Admin Policy #07-01
Comment Number: 7 Comment Originated: 10/13/2014
10113/2014: GROUP 14 OCCUPANCIES REQUIREMENTS
> IFC 907.2.6: MANUAL FIRE ALARM. A manual fie alarm systems that activates the occupant
notification system in accordance with Section 907.5 shall be installed in Group I occupancies. An
automatic smoke detection system that activated the occupant notification system in accordance with
Section 907.5 shall be provided in accordance with Sections 907.2.6.1, 907.2.6.2 and 907.2.6.3.3.
> IFC 1103.4.1: VERTICAL OPENINGS. In Group I occupancies, interior vertical openings connecting
two or more stories shall be protected with 1-hour fire resistance -rated construction.
> IFC404 & 405: FIRE SAFETY & EVACUATION DRILLS. An approved fire safety and evacuation plan
shall be prepared and maintained for Group I occupancies and be practiced per Table 405.2.
> Tenant finish plans to be submitted for 14 exiting compliance and further comment.
Comment Number: 8 Comment Originated: 10/13/2014
10/13/2014: KEY BOXES REQUIRED
Update Knox Box keys as needed.
Department: Stormwater Engineering
Contact: Wes Lamarque, 970.416.2418, wfamaraue0fcgov.com
Page 6 of 8
1b
Topic: General
Comment Number: 1 Comment Originated: 10/15/2014
10/15/2014: If no site work is required, than no Stormwater requirements apply.
Comment Number: 2 Comment Originated: 10/15/2014
10/15/2014: If site work is performed, the City requires the site to provide water quality mitigation to the
extent reasonably feasible.
Department: Technical Services
Contact: Jeff County, 970-221.6588, lcounty0kgov.com
Topic: Plat
Comment Number: 1 Comment Originated: 10/01/2014
10/01/2014: The legal description does not match the plat. See redlines.
Comment Number: 2 Comment Originated: 10/01/2014
10/01/2014: A full review will take place when the Plat is submitted following the City's submittal
requirements. Please make changes as marked. If changes are not made or you disagree with
comments, please provide written response of why corrections were not made.
Topic: Site Plan
Comment Number: 3 Comment Originated: 10/01/2014
10/01/2014: There are line over text issues. See redlines.
Department: Traffic Operation
Contact: Martina Wilkinson, 970-221.6887, mwilkinson0fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 10/14/2014
10/14/2014: We'll need to estimate both previous traffic at the property and proposed traffic at the
property - both daily traffic and peak hour traffic. Then we'll need to coordinate with CDOT to see if a
change in use permit for the access to US287 is needed. We can help facilitate that coordination once
we have some traffic numbers from the applicant.
Topic: Site Plan
Comment Number: 2 Comment Originated: 10/14/2014
10/14/2014: Does the access meet sight distance requirements?
Department: Zoning
Contact: GaryLopez, 970-416.2338, 910nez@ caov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 10/02/2014
10/02/2014: Landscaping seems sparse along the west property line. Depending on whether
screening type plants or taller trees are preferred please check with Lindsey Ex on native species.
This would be infill between tree 3 and tree 6 and around tree 8.
Comment Number: 2 Comment Originated: 10/02/2014
10/02/2014: The parking along the west property is long and should be broken up with a landscape
island. Consider the parking space in front of tree 5 as the island blending in with the crabapple.
Page 7 of 8
Comment Number: 3 Comment Originated: 10/02/2014
10/02/2014: Similar to the first comment the north property around the "existing structure" should also
be landscaped with a minimum of three acceptable trees. Again consider native trees if for screening
purposes. This applicable to the s-e comer of the property also.
Comment Number: 4 Comment Originated: 10/02/2014
10/02/2014: What is the ground cover in these areas referred to above? Please label.
Topic: Site Plan
Comment Number: 5 Comment Originated: 10/02/2014
10/02/2014: How will trash be enclosed/stored? No trash enclosures are shown. Trash enclosures
should meet LUC 3.2.5.
Page 8 of 8
visit http://www.fcgov.com/engineedng/devrev.php
Comment Number: 2 Comment Originated: 10/14/2014
01/09/2015: The access easement limits depicted on the site plan does not
match what is being dedicated on the plat. Additional easement width is
needed in areas. See plat redlines.
Response. Please refer to submitted plat and site plan. The easement limits and the plat have
been coordinated to ensure conformity and that they meet requirements.
10/14/2014: An access easement will need to be dedicated on the property (lot
1) to comply with the South College Avenue Access Control Plan. This
easement is needed along northern and western boundary of the property for
future cross connectivity to adjacent parcels. It may make sense to dedicate the
access easement in relation to the drive lanes that exist through the parking lot.
Please see site plan redlines for an access easement that would meet the intent
of the South College Ave Access Control Plan.
Comment Number: 4 Comment Originated: 01/09/2015
01/09/2015: Please label the access easement on the plat as Emergency
Access and Access Easement.
Response: Corrected on submitted plat
Comment Number: 5 Comment Originated: 01/09/2015
01/09/2015: Please extend the emergency access/access easement to the
north property line for future connectivity. See plat redlines.
Response: Corrected on submitted plat
Comment Number: 6 Comment Originated: 01/09/2015
01/0912015: The trash enclosure will need to be relocated outside of the limits
of the access easement.
Response: Corrected on submitted site plan.
Comment Number: 7
Comment Originated: 01/09/2015
01/09/2015: Comcast cable has requested that a 5ft utility easement be
provided around the perimeter of the property. See plat redlines.
Response: Corrected on submitted plat Note that the trash enclosure encroaches on this easement
On the south property line, but Eldedous prefers to have an exception to this udifty easement and
will deal with requests to accommodate ff and when they occur.
Department: Internal Services
Contact: Russell Hovland, 970.416-2341, rhoviand()-fcoov.com
Topic: Building Insp Plan Review
Comment Number: 1 Comment Originated: 10/10/2014
10/10/2014:
Building Permit Pre -Submittal Meeting
Pre -Submittal meetings are offered to assist the designer/builder by assuring,
early on in the design, that the new commercial or multifamily projects are on
track to complying with all of the adopted City codes and Standards listed
below. The proposed project should be in the early to mid -design stage for this
meeting to be effective and is typically scheduled after the Current Planning
conceptual review meeting. Applicants of new commercial or multi -family
projects are advised to call 416-2341 to schedule a pre -submittal meeting.
Applicants should be prepared to present site plans, floor plans, and elevations
and be able to discuss code issues of occupancy, square footage and type of
construction being proposed.
Construction shall comply with the following adopted codes as amended:
2012 International Building Code (IBC)
2012 international Residential Code (IRC)
2012 Intemational Energy Conservation Code (IECC)
2012 International Mechanical Code (IMC)
2012 International Fuel Gas Code (IFGC)
2012 International Plumbing Code (IPC) as amended by the State of Colorado
2014 National Electrical Code (NEC) as amended by the State of Colorado
Accessibility: State Law CRS 9-5 & ICC/ANSI Al17.1-2009.
Snow Load Live Load: 30 PSF / Ground Snow Load 30 PSF.
Frost Depth: 30 inches.
Wind Load:100- MPH 3 Second Gust Exposure B.
Seismic Design: Category B.
Climate Zone: Zone 5
Energy Code Use
1. Single Family; Duplex; Townhomes: 2012 IRC Chapter 11 or 2012 IECC.
2. Multi -family and Condominiums 3 stories max: 2012 IECC residential
chapter.
3. Commercial and Multi -family 4 stories and taller. 2012 IECC commercial
chapter.
Fort Collins Green Code Amendments effective starting 1-1-2012. A copy of
these requirements can be obtained at the Building Office or contact the above
phone number.
Elderhaus — project specific concerns:
1. Fire -sprinkler systems are required if adult day-care is provided on any
building level except the 1st floor.
2. This must go through a change of occupancy process.
City of Fort Collins
Building Services
Plan Review
416-2341
Response: Building permit submitted and approved. In process of gaining all city inspections
at this time.
Department: Outside Agencies
Contact: Rebecca Everette, 970-416.2625, reveretteDfcgov.com
Topic: Plat
Comment Number: 4 Comment Originated: 12129/2014
Comcast
12/29/2014: Comcast cable would like to see a public utilities easement around
the perimeter of the site.
Response: Corrected on submitted plat Note that the bash enclosure encroaches on this easement
On the south property line, but Elderhaus prefers to have an exception to this utility easement and
will deal with requests to accommodate if and when they occur.
Contact: Terry W. Farrill, P.E.,
Topic: General
Comment Number: 1
Comment Originated: 10/14/2014
Fort Collins -Loveland Water District / South Fort Collins Sanitation District:
10/14/2014: The District requires a Reduced Pressure Principle
Back -Flow -Prevention -Device (RP Device) on the fire line and the domestic
water service. The RP devices are to be located near the property line along
U.S. Highway 287. The existing double check valve and vault are to be
removed.
Response: A agreeable solution was negotiated with FCLWD to provide the RP Device in a newly
constructed room on the main floor of the main facility. This has been built as approved by
FCLWD.
Comment Number: 2
Comment Originated: 10/14/2014
Fort Collins -Loveland Water District / South Fort Collins Sanitation District:
10/14/2014: The District will require a grease traptinterceptor on the sanitary
sewer service.
Response: A grease interceptor has been added to Me development and building permit
Department: PFA
Contact: Jim Lynxwiler, 970.416.2869, jlynxwile .poudre-fire.oro
Topic: General
Comment Number. 2 Comment Originated: 10/13/2014
01/06/2015: FIRE LANE SPECIFICATIONS
A number of fire lane issues still need to be cleared up.
1) The culvert needs to be shown as supporting 40 Tons.
2) The fire lane shall be labeled as an Emergency Access Easement on the
plat.
3) The dimensions of the fire lane shown on the site plan to do not match the
limits of the access easement shown on the plat.
4) The EAE shall connect to the public way and it is unclear if this condition is
being met.
See 10/13/2014 comments for further details.
Response: See submitted site plan and plat for emergency access easements. Engineering letter
resubmitted as part of this package certifying 40 tons. PFA has inspected and approved fire lane
designations and markings.
10/13/2014: FIRE LANE SPECIFICATIONS
The submitted material does not clearly delineate the limits of the fire lane nor
does available information appear to meet minimum requirements. A fire lane
plan shall be submitted for approval prior to installation. In addition to the design
criteria already contained in relevant standards and policies, any new fire lane
must meet the following general requirements:
> Shall be dedicated and noted on the plat as an Emergency Access Easement
(EAE) with boundaries and limits of the easement clearly labeled.
> Minimum width of EAE to be 20 foot throughout and maintained unobstructed
at all times with 14 foot minimum overhead clearance.
> Be designed as a flat, hand, all-weather driving surface
> Fire lanes must be capable of supporting 40 tons (80,000 lb) throughout. The
54,000 lb rating of the metal culvert would not meet minimum requirements. The
engineer's stamped letter of approval may be revised and resubmitted if the
culvert can be reassessed to carry 40 tons.
> Dead-end fire access roads in excess of 150 feet in length shall be provided
with an approved area for turning around fire apparatus.
> The required turning radii of a fire apparatus access road shall be a minimum
of 25 feet inside and 50 feet outside (29 wide). Turning radii shall be detailed
on submitted plans.
> Be visible by painting and/or signage, and maintained unobstructed at all
times.
International Fire Code 503.2.3, 503.2.4, 503.2.5, 503.3, 503.4 and Appendix
D; FCLUC 3.6.2(B)2006 and Local Amendments.
Response: See submitted she plan and plat for emergency access easements. Engineering letter
resubmitted as part of this package certifying 40 tons. PFA has inspected and approved fire lane
designations and markings.
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, jschlam@fcgov.com
Topic: Erosion Control
Comment Number: 3 Comment Originated: 01/02/2015
01/02/2015: No Comment from Erosion Control. This site; disturbs less than
10,000 sq-ft, is not in a sensitive area, and is not in a larger development under
construction. Therefore, no submittal of erosion control material is needed.
However, the site still must be swept and maintained to prevent dirt, saw
cuttings, concrete wash, and other pollutants from entering the storm sewer at all
times or BMPs will be required of the site. If you need clarification concerning
this, or if there are any questions please contact Jesse Schiam 970-218-2932
or email @ jschlam@fcgov.com
Response: Owner will maintain site to prevent pollutants from entering storm sewer.
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcounty@fcoov.com
Topic: Plat
Comment Number: 4
Comment Originated: 01/07/2015
02/12/2015: There are still some to be added. See redlines.
01/07/2015: Please add bearings & distances as marked. See redlines.
Response: Plat as submitted addresses all redlined bearings and distances marked.
Department: Traffic Operation
Contact: Martina Wilkinson, 970.221.6887, mwilkinsonCc0fcaov.com
Topic: General
Comment Number: 1
Comment Originated: 10/14/2014
01/06/2015: Thank you for submitting the anticipated traffic usage. I'll write up
a summary, and help you fill out the change in use permit form that needs to go
to CDOT.
10/14/2014: We'll need to estimate both previous traffic at the property and
proposed traffic at the property - both daily traffic and peak hour traffic. Then
we'll need to coordinate with CDOT to see if a change in use permit for the
access to US287 is needed. We can help facilitate that coordination once we
have some traffic numbers from the applicant.
Response: CDOT permit granted. Copies attached in this package.
Topic: Site Plan
Comment Number. 2
Comment Originated: 10/14/2014
01/0612015: CDOT said they would do the sketch for you that is submitted with
the change in use form.
10/14/2014: Does the access meet sight distance requirements?
Response: CDOT permit granted. Copies attached in this package.
Cltyof
F6rt Collins
October 15, 2014
Jim Brannan
SPC, INC
1209 ST. CROIX PLACE
Fort Collins, CO 80525
RE: Elderhaus Adult Day Program Major Amendment, MJA140004, Round Number 1
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov. com/developmentreview
Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of
the above referenced project. If you have questions about any comments, you may contact the individual
commenter or direct your questions through the Project Planner, Rebecca Everette, at 970416-2625 or
reverette@fcgov.com.
Comment Summary
Department: Planning Services
Contact: Rebecca Everette, 970.416.2625, reverette(&fcgov.com
Topic: Landscape Plans
Comment Number: 2 Comment Originated: 10/14/2014
10/14/2014: Please show any trees to be added for mitigation of those to be removed. Keep in mind
the minimum species diversity requirements in LUC 3.2.1(D)(3) when selecting species for mitigation
trees.
Comment Number: 3 Comment Originated: 10/14/2014
10/14/2014: Mitigation trees and additional landscaping should be located in high visibility areas, along
property lines to provide screening from adjacent uses (e.g., along the west property line), or to break
up long stretches of parking (e.g., western side of parking lot).
Comment Number: 4 Comment Originated: 10/14/2014
10/14/2014: Please identify lawns, native grasses, or other planted and/or non -impervious areas on the
landscape plan (see redlines).
Comment Number: 5 Comment Originated: 10/14/2014
10/14/2014: Six percent of the interior space of the parking lot should be landscaped area, per LUC
3.2.1(E)(5). Please show calculations for landscaping within the parking area to confirm that this
standard is met. Provide additional landscaping to meet the requirement, if needed.
Comment Number: 6 Comment Originated: 10/14/2014
10/14/2014: Please show the existing trees along the driveway, even though they are off -site.
Topic: Lighting Plan
Page 1 of 8
Comment Number: 10
Comment Originated: 10/14/2014
10/14/2014: Please provide photos of the existing outdoor lighting fixtures on the site to ensure they
meet the requirements of LUC 3.2.4(D). Light sources should be fully shielded and down -directional to
minimize light spillage.
Topic: Planning Objectives
Comment Number: 1 Comment Originated: 10/14/2014
10/14/2014: The adult day/respite care center will be considered a secondary use in the MMN zone
district. Per LUC section 4.6(D)(2), we need a description of how this proposal contributes to the
overall mix of land uses within the surrounding area.
Topic: Site Plan
Comment Number: 7
Comment Originated: 10/14/2014
10/14/2014: It appears that 6 bicycle parking spaces are provided on -site. Please include this in the
Land Use Data section of the site plan.
Comment Number: 8 Comment Originated: 10/14/2014
10/14/2014: The vehicle parking provided on -site exceeds the maximum allowed for similar uses. We
can look at options for meeting the requirement or consider alternative compliance (See LUC 3.2.2(I)
(3))•
Comment Number: 9 Comment Originated: 10/14/2014
10/14/2014: See redlines for text edits in the notes and land use data.
Department: Engineering Development Review
Contact: Tyler Siegmund, 970.221.6501, tiegmund cgov.com
Topic: General
rr ' Comment Number: 1 Comment Originated: 10/14/2014
l S - 10/14/2014: Is the non-exclusive easement that is referenced on the plat existing or proposed? If this
easement exists please include the reference number that was assigned when it was recorded. If
proposed, it appears that it falls outside of the property that is to be platted as part of this project (6815
S College Ave). This easement will need to be dedicated by separate document by the property
owner. There is a separate process and fee to dedicate easements by separate document. You can
contact me for additional information on the process to dedicate easements by separate document or
visit http:/twww.fcgov.com/engineering/devrev.php
Comment Number: 2 Comment Originated: 10/14/2014
10/14/2014: An access easement will need to be dedicated on the property (lot 1) to comply with the
South College Avenue Access Control Plan. This easement is needed along northern and western
boundary of the property for future cross connectivity to adjacent parcels. It may make sense to
dedicate the access easement in relation to the drive lanes that exist through the parking lot. Please
see site plan redlines for an access easement that would met the intent of the South College Ave
Access Control Plan.
Comment Number:
Comment Originated: 10/14/2014
10/14/2014: See redlines on the plat for additional comments. A few of the notes need to be revised
or removed. Please contact me if you have any questions after reviewing my redline comments on
the plat.
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lex@fcgov.com
Page 2 of 8
Topic: General
Comment Number: 1 Comment Originated: 10/15/2014
10/15/2014: The Loudon ditch runs underground through this property and is therefore not serving as a
wildlife corridor in this area. Thus, no comments from Environmental Planning on this proposal.
Department: Forestry
Contact: Tim Buchanan, 970-221.6361, tbuchananD-fcaov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 10/14/2014
10/14/2014:
Please add these two notes to the tree inventory landscape plan:
1. Future pruning of existing trees shall be by a business that holds a current City of Fort Collins
Arborist License where required by City code.
2. All existing trees not shown to be removed shall be retained and protected.
Comment Number: 2 Comment Originated: 10/14/2014
10/14/2014:
Tree number 46 should have its mitigation changed to 0 due to the impact that this tree could cause to
the building and foundation.
Department: Internal Services
Contact: Russell Hovland, 970.416.2341, rhovlandMcgov.com
Topic: Building Insp Plan Review
Page 3 of 8