HomeMy WebLinkAboutWILLOW BROOK SECOND - Filed CS-COMMENT SHEETS - 2005-09-01Project Comments Sheet
(��' Selected Departments
City of Fort Collins
Department: Engineering
Date: July 16, 2002
Project:
WILLOW BROOK, 2ND FILING, PDP/FINAL COMPLIANCE #8-99/8-99F
All comments must be received by TED SHEPARD in Current Planning no later than
the staff review meeting:
July 10, 2002
Note - Please identify your redlines for future reference
Issue Contact: Marc Virata
Topic: General
62
Remove all the listed revisions in the revision block on all documents with mylar
submittals.
Topic: Plat
55
Please see the redlined sheets of the plat for changes to the Notice of Other Documents
as well as further clarification on the plat notes.
7/10
Please correct the revisions as redlined.
Topic: Street Design
24
Provide spot elevations and show the transition points for where the unnamed public
street intersects both Southern Cross Lane and the looped portion of the unnamed
public street.
5/22
This was not provided in accordance with LCUASS Details 7-32A & B. The transition
point to remove the crown is required for Sky Gazer Lane approaching Southern Cross
Lane. It is optional for Sky Gazer Lane approaching the looped street.
7 c2
Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _ Site Drainage Report Other_
✓ Utility _Redline Utility Landscape
Page I
REVISION
COMMENT SHEET
DATE: May 1, 2002 TO: Technical Services
PROJECT: #8-99E Willowbrook, 2nd Filing — Type I (LUC)
All comments must be received by Ted Shepard no later than the
staff review meeting:
May 22, 2002 r J
ElNo Comment
T, Problems or Concerns (see below or attached)
**PLEASE IDENTIFY YOUR REDLINES FOR FUTURE
REFERENCE**
fj ccii�J �r}c�� <
,- -rA K c z C �
L�;—
(. So)'"er acts G 11 we
�eaur allow c(eQ
Date: _Signature:_
CHECK HERE IF YOU WISH TO RECEIVE, COPIES OF REVISIONS
Plat Site Drainage Report Other
Utility __ Redline Utility ___ Landscape
Project Comments Sheet
Selected Departments
CitVof Fort Collins
Department: Engineering
Date: March 20, 2002
Project: WILLOWBROOK, 2ND FILING, PDP
All comments must be received by TED SHEPARD in Current Planning no later than
the staff review meeting:
March 13, 2002
Note - Please identify your redlines for future reference
Issue Contact: Marc Virata
Topic: Drainage
42
Comment #36 from Stormwater no longer applies as Engineering will not be requiring
the use of sidewalk chases for the drainage between the buildings that are within
landscaped swales.
43
There appear to be multiple instances where drainage swales between buildings are in
the same area as pedestrian connections.
Topic: General
14
An update to the subdrain report originally submitted by Anderson Consulting Engineers
for the first filing should be submitted addressing the subdrain issues and design
pertaining to this project.
18
Replace any and all indications of "alley" or "private alley' with "private drive".
35
It was previously discussed by the City's Transportation Services group prior to this
formal submittal that there was a viewed benefit in having at least 4 of the private drives
connect to the perimeter of the existing public streets surrounding this project from the
1 st filing. Only one connection is being shown. It should perhaps be discussed further
by the applicant on the merits of only one connection.
45
Signatart, Datt,
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _ Site Drainage Report Other ter,
Utility _ Redline Utility Landscape
Paae I
Provide the correct approval blocks on the documents. Approval blocks for Type II
projects were used on the planning documents and the plat, it is my understanding and
assumption that this is a Type I project.
Topic: Plat
32
Add the attached private drive note on the plat.
33
The plat should show existing easements and a note indicating said easements are to
be vacated (if appropriate.)
34
The plat indicates a drainage easement along the south boundary. The recorded plat
document at the City indicates this as a utility easement. Will this easement need to be
vacated on the plat?
44
It was discussed that Note #4 may result in the interpretation that the entire
development is a blanket easement and that this would result in not being able to build
anything within this easement. Perhaps it would be beneficial if this note was removed
from the plat.
Topic: Street Design
22
Provide directional ramps for new construction instead of access ramps that lead to a
corner an intersection.
23
The internal (currently unnamed) public street is required to have flowline elevations on
both sides of the street, a centerline profile was only provided for the non -looped
portion.
24
Provide spot elevations and show the transition points for where the unnamed public
street intersects both Southern Cross Lane and the looped portion of the unnamed
public street.
25
The loop street is required to be widened where turns are greater than 60 degrees per
LCUASS Detail 7-26.
26
The loop street is required to be a crowned section and not a sloped to one side street
section as shown on Sheet 15. Sheet 5 and other sheets appears to show by grading
that this is a crowned section - please clarify this roadway section. Assuming a centered
crowned road section for the loop street. cross -sections appear to work, though the
additional spot elevations would help in further evaluating this.
Paae 2
27
Please provide spot elevations within the loop street at flowline and centerline locations
perpendicular to the direction of travel in order to easier verify cross slopes as redlined
on the plan set.
28
Please provide spot elevations where the private drives meet the two public streets
(Sheets 9 and/or 14.)
29
Please use different gridlines on the profile views (.25 instead of .3) in order to allow
easier measuring with a 30 scale.
30
The private drive profiles (Sheets 10-13) should not have Notes 1-4 on these sheets
31
Please use LCUASS Detail 7-29A for the private drive detail on sheet 15. Include the
additional detail of 7-31 for the culvert/channel design.
Topic: Utility Plan
15
Provide two benchmarks on the utility plan set.
16
Add an additional general note to the cover sheet that all recommendations of the
subdrain report by (the subsurface engineer) shall be complied with.
17
Ensure that a copy of the plat is also included in the utility plan set.
19
On the overall utility plan sheet (Sheet 6) revise Note 8 to also include the City of Fort
Collins not having responsibilities or liability for the design, installation, operation or
maintenance of the subdrain system.
20
Add an additional note on Sheet 6 indicating that the City of Fort Collins is not
responsible or liable for the design, installation, operation or maintenance of any grinder
pumps in the Development.
21
The sanitary sewer plan and profile doesn't show a design of the subdrain system. This
design is required and should be in accordance with an approved subdrain report
pertaining to the 2nd filing.
Page 3
PROJECT
COMMENT SHEET
City of Fort Collins
Current Planning
DATE: February 12, 2002 TO: Engineering Pavement
PROJECT: #8-99E Willowbrook, Filing 2, PDP - Type I (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting:
March 13, 2002
Note - Please identify your redlines for future reference
l r cc 1'k /1-Y eM4
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat _Site _Drainage Report _Other
_Utility _Redline Utilitv _Landscape
6 1 / larqml
�;A":M
City of Fort Collins
PROJECT
COMMENT SHEET
City of Fort Collins
Current Planning
DATE: February 12, 2002 TO: Technical Services
PROJECT: #8-99E Willowbrook, Filing 2, PDP - Type I (LUC)
All comments must be received by Ted Shepard no later than the staff
review meeting: Pi
March 13, 2002 "��"' z3:
Note - Please identify your redlines for future reference
5
k-c-� be-r LI �N �7 � �, G, �'l.s L-e � 4 (
3' F)aT �teCdS ck liaYe UctGa .q EXiS�. cI�SPPti l�
Fc �eQ'G4�in9 cts o, t-45
L'
Sewrc kxX 2 11tie we i 903
at H i
Gt I DW Y-e— f'rC, (AU-C+t
ot.t curve 4 �.
'C'°r al( Gurv� S���vte pis
Name (please print)
CI IECK HERE IF YCl_' WISH TO RECEIVE COPIES OF REVISIONS
Plat _.Bile Drmmi,-,e Report _Other
ttiht% RcclimeUtilin Lmcisc.ipc
(mimmm
Gtv of Fort Collins
7/10
The spot elevations provided at these two points should further specify if they are
transition points to remove the crown or are strictly just "spot elevations."
28
Please provide spot elevations where the private drives meet the two public streets
(Sheets 9 and/or 14.)
5/22
The spot elevations for the private drive out to Northern Lights Drive exceeds the grade
specified in 7-29A.
7/10
This still appears to be the case.
61
Specify whether driveover curb and gutter is used throughout, including the Tract A
median.
Topic: Utility Plan
21
The sanitary sewer plan and profile doesn't show a design of the subdrain system. This
design is required and should be in accordance with an approved subdrain report
pertaining to the 2nd filing.
5/22
See redlines for additional clarification/changes still required regarding this. (Specify
SDR 35)
7/10
Please specify SDR 35 for the subdrain.
Page 2
Project Comments Sheet
41Mzhmd" Selected Departments
Cityof Dort Collins
Department: Engineering
Date: July 9, 2002
Project:
WILLOW BROOK, 2ND FILING, PDP/FINAL COMPLIANCE #8-99/8-99F
All comments must be received by TED SHEPARD in Current Planning no later than
the staff review meeting:
July 10, 2002
Note - Please identify your redlines for future reference
Issue Contact: Marc Virata
Topic- General
8
Reptace any and all indications of "alley" or "private alley' with "private drive".
5/22
This correction still needs to be done on the landscape plan.
5
Provide the correct approval blocks on the documents. Approval blocks for Type II
projects were used on the planning documents and the plat, it is my understanding and
assumption that this is a Type I project.
5/22
This was not provided on the site plan.
Topic: Plat
55
Please see the redlined sheets of the plat for changes to the Notice of Other Documents
as well as further clarification on the plat notes.
jr. - -
Topic: Street Design
24
Signature Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat Site Drainage Report Other
Utility Redline Utility Landscape
Page 1
Provide spot elevations and show the transition points for where the unnamed public
street intersects both Southern Cross Lane and the looped portion of the unnamed
public street.
5/22
This was not provided in accordance with LCUASS Details 7-32A & B. The transition
point to remove the crown is required for Sky Gazer Lane approaching Southern Cross
Lane. It is optional for Sky Gazer Lane approaching the looped street.
Thle loop street is required to be widened where turns are greater than 60 degrees per
LCUASS Detail 7-26.
5/22
This was not provided on one street turn as redlined on the plan set.
he loop street is required to be a crowned section and not a sloped to one side street
section as shown on Sheet 15. Sheet 5 and other sheets appears to show by grading
that this is a crowned section - please clarify this roadway section. Assuming a centered
crowned road section for the loop street, cross -sections appear to work, though the
additional spot elevations would help in further evaluating this.
5/22
The revised loop street with additional elevations indicates a few sections where cross
slopes are not to standard. Please rectify.
28
Please provide spot elevations where the private drives meet the two public streets
(Sheets 9 and/or 14.)
5/22
The spot elevations for the private drive out to Northern Lights Drive exceeds the grade
specified in 7-29A.
50
The outside flowine of the looped street is of issue with the short reverse curves
proposed on the design.
Thc� two inlets on the loop street are proposed on a curve. Please provide a detail to
show this can be built and function. These inlets may have to be relocated outside of a
curve.
52
Page 2
The widened street turns (on the two that were provided, though three are needed) are
not symmetrical and it would appear to be beneficial if the turning movements were the
same between these two curves.
53
For the vertical design, the flowline of the inner loop is substandard with the lengths of
vertical curves provided. Please revise.
Tropic: Utility Plan
Provide two benchmarks on the utility plan set.
5/22
Provide missing information for the second benchmark provided. It does not appear to
be part of the City's Vertical Control.
21
The sanitary sewer plan and profile doesn't show a design of the subdrain system. This
design is required and should be in accordance with an approved subdrain report
pertaining to the 2nd filing.
5/22
See redlines for additional clarification/changes still required regarding this. (Specify
SDR 35)
54
Revisions were received from the design engineer for Willow Brook in order to have
underground services pertinent with this project installed with the 1st filing. Please see
redlines for comments. Note that these revision need to clearly distinguish between
existing, proposed with the revisions, and proposed with the 2nd filing. The utility plans
for this project will now need to distinguish portions of the project having already been
approved with the pertinent revision(s) to the 1st filing.
Page 3
i..� FINAL, COMPLIANCE,
City of Fort Collins COMMENT SHEET
Current Plannine
DATE: June 25, 2002 TO: Mapping/Drafting
PROJECT: #8-99F Willowbrook, 2nd Filing — Final Compliance
All comments must be received by Ted Shepard no later than the staff
review meeting:
July 10, 2002
Note - Please identify your redlines for future reference
�, Bounrf�Rf� it s Cco.SE ,
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _Site _Drainage Report _Other
_Utility _Redline Utility _Landscape
City of Fort Collins
Project Comments Sheet
tort CILVEM)m Selected Departments
ofollins
Department: Engineering
Date: May 29, 2002
Project: WILLOWBROOK, 2ND FILING, PDP
All comments must be received by TED SHEPARD in Current Planning no later than
the staff review meeting:
May 22, 2002
Note - Please identify your redlines for future reference
Issue Contact: Marc Virata
Topic: General
18
Replace any and all indications of "alley" or "private alley' with "private drive".
5/22
This correction still needs to be done on the landscape plan.
45
Provide the correct approval blocks on the documents. Approval blocks for Type II
projects were used on the planning documents and the plat, it is my understanding and
assumption that this is a Type I project.
5/22
This was not provided on the site plan.
Topic: Plat
55
Please see the redlined sheets of the plat for changes to the Notice of Other Documents
as well as further clarification on the plat notes.
Topic: Street Design
24
Provide spot elevations and show the transition points for where the unnamed public
street intersects both Southern Cross Lane and the looped portion of the unnamed
public street.
Signature - T Date
HECK HER IF YOU WISH TO RECEIVE COPIES OF REVISIONS
flat Site Drainage Report Other_
Utility _ Redline Utility Landscape
Pale I
5/22
This was not provided in accordance with LCUASS Details 7-32A & B. The transition
point to remove the crown is required for Sky Gazer Lane approaching Southern Cross
Lane. It is optional for Sky Gazer Lane approaching the looped street.
25
The loop street is required to be widened where turns are greater than 60 degrees per
LCUASS Detail 7-26.
5/22
This was not provided on one street turn as redlined on the plan set.
26
The loop street is required to be a crowned section and not a sloped to one side street
section as shown on Sheet 15. Sheet 5 and other sheets appears to show by grading
that this is a crowned section - please clarify this roadway section. Assuming a centered
crowned road section for the loop street, cross -sections appear to work, though the
additional spot elevations would help in further evaluating this.
5122
The revised loop street with additional elevations indicates a few sections where cross
slopes are not to standard. Please rectify.
28
Please provide spot elevations where the private drives meet the two public streets
(Sheets 9 and/or 14.)
5/22
The spot elevations for the private drive out to Northern Lights Drive exceeds the grade
specified in 7-29A.
50
The outside flowine of the looped street is of issue with the short reverse curves
proposed on the design.
51
The two inlets on the loop street are proposed on a curve. Please provide a detail to
show this can be built and function. These inlets may have to be relocated outside of a
curve.
52
The widened street turns (on the two that were provided, though three are needed) are
not symmetrical and it would appear to be beneficial if the turning movements were the
same between these two curves.
Page 2
53
For the vertical design, the flowline of the inner loop is substandard with the lengths of
vertical curves provided. Please revise.
Topic: Utility Plan
15
Provide two benchmarks on the utility plan set.
5/22
Provide missing information for the second benchmark provided. It does not appear to
be part of the City's Vertical Control.
21
The sanitary sewer plan and profile doesn't show a design of the subdrain system. This
design is required and should be in accordance with an approved subdrain report
pertaining to the 2nd filing.
5/22
See redlines for additional clarification/changes still required regarding this. (Specify
SDR 35)
54
Revisions were received from the design engineer for Willow Brook in order to have
underground services pertinent with this project installed with the 1st filing. Please see
redlines for comments. Note that these revision need to clearly distinguish between
existing, proposed with the revisions, and proposed with the 2nd filing. The utility plans
for this project will now need to distinguish portions of the project having already been
approved with the pertinent revision(s) to the 1 st filing.
Page 3