PARCEL A OUTFALL SEWER - PLAN REVIEW OCTOBER 7, 1996
• THE FOLLOWING NEEDS TO BE ADDED TO NOTE I : ANY CONSTRUCTION OCCURRING
THREE YEARS AFTER THE DATE OF PLAN APPROVAL SHALL REQUIRE RE-EXAMINATION OF
THE PLANS BY THE DIRECTOR OF ENGINEERING, WHO MAY REQUIRE THAT THEY BE MADE
TO CONFORM TO STANDARDS AND SPECIFICATIONS CURRENT AT THAT TIME.
SHEET 3
• WHAT DOES THE IRRIGATION LINE CONNECT TO ON BOTH ENDS?
• WHAT TYPE OF PIPE IS THE IRRIGATION LINE?
• NEED TO MAKE SURE THAT THE SEWER LINE IS OUT BEYOND THE WING WALLS OF THE
LEMAY BRIDGE ACROSS FOSSIL CREEK. IT LOOKS LIKE YOU ARE, BUT THE WING WALLS
EXTEND OUT BEYOND THE RIGHT-OF-WAY.
• NEED TO REPLACE AND/OR REPAIR ALL DISTURBED RIP -RAP WHERE THE SEWER LINE IS
TAKEN UNDER FOSSIL CREEK ADJACENT TO THE BRIDGE.
• SET THE RIM ELEVATIONS OF MANHOLES MH-HH-S9 AND MH-H 11 H-S j O TO THE N5W
E V`TION OF LEMAY.
�aTe_ lol Signature -
CHECK IF YOU WISH TO RECEIVE ❑ PLAT'
COPIES OF REVISIONS: ❑ SITE
❑ LANDSCAPE
❑ UTILITY
DEVELOPMENT SERVICES 281 NORTH COLLEGE P.O.BOX 580 FORT COLLINS, COLORADO 80522-0580
PLANNING DEPARTMENT (303)221-6750
City of Fort Collins
Planning
DATE: 2-1.0 - 96
PROJECT
COMMENTSHEET
DEPARTMENT: E'\vve r-) 5
PROJECT: Faecc 1 "A'' -Sa..; �5;'M er
PLANNER: S �er i L-Ja- -, h0 -(-F
All comments must be received by: 1-21 Ili(,?
❑ No Problems
121"Problems or Concerns (see below)
PARCEL 'A' SANITARY SEWER - REVIEW COMMENTS MARCH IS, 1996
• ADD THE FOLLOWING TO GENERAL NOTE I ANY CONSTRUCTION OCCURRING THREE
YEARS AFTER PLAN APPROVAL SHALL REQUIRE RE-EXAMINATION OF THE PLANS BY THE
DIRECTOR CF ENGINEERING, WHO MAY REQUIRE THAT THEY BE MADE TO CONFORM TO
STANDARDS AND SPECIFICATIONS CURRENT AT THAT TIME.
• MODIFY GENERAL. NOTE 1 2 TO READ AS FOLLOWS: THE CITY SHALL NOT BE HELD
RESPONSIBLE FOR DAMAGES OR INJURIES SUSTAINED IN THIS DEVELOPMENT AS A
RESULT OF GROUNDWATER SEEPAGE, WHETHER RESULTING FROM GROUNDWATER
FLOODING, STRUCTURAL DAMAGE OR OTHER DAMAGE UNLESS SUCH DAMAGE OR
INJURIES ARE SUSTAINED AS A RESULT OF THE CITY'S FAILURE TO PROPERLY MAINTAIN
ITS WATER, WASTEWATER AND/OR STORM DRAINAGE FACILITIES IN THE DEVELOPMENT.
(CONTINUED ON NEXT PAGE)
Date_.3���9�4 _ Signature
CHECK IF YOU WISH TO RECEIVE ❑ PLAT
COPIES OF REVISIONS: ❑ SITE
❑ LANDSCAPE
❑ UTILITY
DEVELOPMENT SERVICES 281 NORTH COLLEGE P.O.BOX 580 FORT COLLINS, COLORADO 80522-0580
PLANNING DEPARTMENT (303)221 -6750
PARCEL 'A' SANITARY SEWER - REVIEW COMMENTS MARCH 1 6, 1 996
(PAGE 2 OF 2)
SANITARY SEWER - PLAN AND PROFILE
• A DISTANCE OF I .75 FEET IS SHOWN BETWEEN THE SANITARY SEWER LINE AND THE
STORMDRAIN WILL THE SUBDRAIN FIT THROUGH HERE, IF YOU IGNORE THE PIPE
THICKNESS THERE IS ONLY I INCH OF CLEARANCE.
• A HYDROLOGIC STUDY IS NEEDED FOR THE UNDERDRAIN. A SEPARATE SYSTEM IS
PROBABLY NEEDED. THE EXISTING SYSTEM SOUNDS LIKE IT IS CURRENTLY UNDERSIZED.
YOU WILL NEED TO PROVE THE EXISTING SYSTEM HAS CAPACITY FOR THE ADDITIONAL
FLOWS IF WANT TO USE THE EXISTING SYSTEM.