FTENJI: 146-79G RAINTREE PUD, Phase 2, Final
CITY OF FRT COLLINS
COMMUNITY DEVELOPMENT DEPARTMENT, PLANNING DIVISION
April 15, 1985
Frank Vaught
ZVFK Architects/Planners
11 Old Town Square, Suite 200
Fort Collins, CO 80524
Dear Frank:
Staff has reviewed the application for final PUD and subdivision plat approval
for Raintree Commercial PUD Tract F, Phase 2 and offers the following
comments:
1. The sidewalk along Raintree Drive and Shields Street should be detached
from the curb. Please revise.
2. Note #14 should read that type of stamped concrete to be used must be
approved by the City Engineer prior to construction.
3. Shields Street and Raintree Drive will need to be fully improved with this
phase of development. Please indicate an accurate representation of the
improvements to be installed on the site plan.
4. The location of the "potential future curb cut" on Shields Street will
conflict with the operation of the deceleration lane. Staff would like to
discuss the location and need for this curb cut at this time. Also, the
note on the site plan should refer to note #17 rather than note #16.
5. The loading zone located north of the 17,200 square :foot retail building
may create problems for large truck access. Raintree Drive should not be
used for "backing" of large vehicles. Please provide evidence to justify
the plan design.
6. The design of the deceleration lane needs further work. The deceleration
lane should begin approximately fifty feet past the intersection rather
than at the intersection. Please revise.
7. The location of the sign at the Raintree entrance will present sight
distance problems. Please relocate.
y.
r4lY
OFFICE OF COMMUNITYV
DEVELOPMENT, PLANNING DIVISION
iv',n•v'Yna J .wY�r � .,
'; i r �, ..mA'Y :. i � •: 1 L 1 uy "} pie y f
it
300 LaPorte Ave. • P.O. Box 580 • Fort Collins, Colorado 80522 • (303)221-6750
Frank Vaught
From: Joe Frank
Re: Raintree
April 16, 1985
Page 2
8. Please show any hydrants that could serve Phase 2 which are planned for
Phase 1.
9. The 19,000 square foot retail building does not meet the 150 foot fire
access requirement and will require sprinkling. Please indicate
sprinkling of this building on the site plan.
10. Improvement of Shields Streeet should include the installation of the
inlets at Raintree Drive and the 15" RCP outfall from the inlets. Details
for constrolling subbasin releases must be provided by the applicants.
The Final drainage report indicates either the applicants will need to
construct the approved storm sewer system in the Raintee residential
portion to drain this PUD or another means of outfall will need to be
designed. If the latter is chosen, the design must be submitted and
approved prior to final approval by the City. Before approval of this
site, the mylars for Raintree residential portion that show changes made
to accomodate this development must be submitted for revision approval.
11. The amount of information and detail shown on the combined landscape plan
and site plan makes the plan very difficult to read and understand. Staff
recommends the landscape plan be on a separate sheet from the site plan.
12. All sidewalks should be dimensioned. Please revise.
13. The setback of the building footprints from the ROW and street pavement
should be indicated on the site plan.
14. The location of the evergreens at the entrances to parking lots and at the
corner of Shields Street and Raintree Drive appear to present sight
distance problems. Please revise.
15. A pedestrian connection between the sidewalk and Raintree Drive to the
west should be provided for at this time. How will snow and ice build up
be prevented in the narrow corridors between retail buildings?
16. Indoor theatres should be eliminated from list of potential uses in note
#13. Please revise.
17. The limits of Tract F are not clearly indicated on the site plan. Please
revise.
18. Berming should be at least 3 feet in height rather than 2 feet as
indicated. Berming should be provided along Shields Street. The parking
islands along the west side of the 19,000 square foot retail building
should include low lying shrubs in addition to trees. Additional comments
regarding the landscape plan will be available at our meeting on this
project.
19. The building elevations are unclear as to which buildings in Phase 2 that
they apply to. Please clarify. A note should be added that all rooftop
mechanical equipment will be screened from view by a solid masonry wall.
Frank Vaught
From: Joe Frank
Re: Rai ntr-,:i
April 16, 1985
Page 3
M
20. The note regarding the residential density to the north appears to be
incorrect. Also, "decleration lane" is misspelled.
21. Owners certification block is needed. Also, is it necessary to include a
developers certification block if transfer of ownership to developer has
already occurred?
22. Planning and Zoning Board block should be for 1985 rather than 1983.
Please revise.
23. Staff has considered your request to include the parking lots on the
remaining tracts and feels they should not be approved separately from the
buildings on those tracts. If it is the applicants desire to build those
parking lots at the same time as the other lots, a separate PUD will need
to be submitted and approved which indicates building pads and elevations,
final landscape and.utility plans, etc. and other necessary information as
required for final PUD approval. The final PUD for these tracts will need
to be submitted on the fifth of the month and follow the necessary process
for PUD approval.
I recommend we meet as soon as possible to discuss the above comments.
Revisions (three copies) to the plans reflecting the above comments should be
delivered to this office no later than Wednesday, May 1, 1985. On Friday, May
10, 1985, 8 1/2 x 11" PMT reductions of all plans and plats and colored
renderings of the site plan and building elevations should be submitted.
Also, on Monday, May 13, 1985, ten full size copies of the site plan and
building elevations should be delivered to me. Final signed mylars of the
site plan, landscape plan, building elevations and subdivision plat including
a signed "Site and Landscape Covenants" document should be submitted no later
than noon on Thursday, May 16, 1985.
It is extremely important that the above deadline
to be heard at the May meeting of the Planning and
any questions, please feel free to call me.
attention to this matter.
�r
cc: Sam Mutch, Planning Director
Bonnie Tripoli, Development Coordinator
s
be followed if the item is
Zoning Board. If you have
Thank you for your prompt
D A T Em" DEPARTuI,'7ENi
ITE2M: �!Aioj-e-ee-- �>ut3 dmm� .(�evts1c)VJ
st soe z,
COMMENTS vA%O-,4v#%A
ITEM : Q.�t� � �� �� w i�ae,� � -
No Problems
, Problems or Concerns (see below)
Date Signature
DeveloL_,entl Services
Planning Department
City of Fort Collins
August 18, 1988
John Barnett
C/o ZVFK Architects
# 11 Old Town Square
Fort Collins, CO 80524
Dear John:
r
Staff has reviewed the Raintree Commercial PUD, Tract H Preliminary and
Final and has the following comments:
I. In addition to the existing 8" gas line in Shields Street shown on the plans,
there is an existing 4" gas line in a utility easement at 14' west of the
west right-of-way line of Shields Street. Trees to be planted on the west
side of Shields must remain a minimum of 6' from this existing gas line
(as measured from the center of the gas line to the nearest portion of tree
trunk).
2. There are 2 existing taps for water in Raintree Drive. One of these is a
4" fire line stub, which will not be used by this development. This stub
must be abandoned at the main. The second tap may be used for the gas
station if it is sized correctly. A water main is existing south of the fast
food restaurant and may be tapped for the restaurant's service. A sewer
main is existing west of Tract H and sewer services for both buildings
should be tapped into that main.
3. Raintree Drive and Shields Street need to be labelled on the site plan. The
15' easement shown along Shields should be labelled as a utility and access
easement.
4. Access into the site from Raintree Drive needs to be more clearly defined.
5. The grading and drainage plan needs to be signed and stamped by a PE
licensed in Colorado. The on -site detention is to include the area to the
center line of adjacent streets. It does not appear that the street runoff
was included.
6. Is sub -basin I-5 shown on Phase II included in the drainage area for Tract
H? The sub -basins do not appear to match the proposed grading contours.
300 LaPorte Avenue • P.O. Box 580 • Fort Collins, CO 80522-0580 • (303) 221-6750
Page 3
By noon on Wednesday, September 7, 1988 three copies of the revised site
and landscape plans addressing these comments must be submitted to this
office. Items that cannot be provided graphically should be addressed in
written form. By Monday. September 19, 1988 ten (10) folded sets of all
plans, a colored rendering (unfolded) and an 8-1/2"x 11" PMT reduction (or
other similar quality, xerox copies unacceptable) must be submitted.
If you have any questions or would like to meet with me to discuss these
comments, please do not hesitate to contact me.