HomeMy WebLinkAboutMATADOR APARTMENTS PHASE IV - Filed CS-COMMENT SHEETS - 2004-08-16PROJECT
COMMENT SHEET
Ciry of Fort Collins
Current Planning
DATE: July 1, 2003 TO: Engineering Pavement
PROJECT: #23-03 RAMS CROSSING PDP —TYPE I (LUC)
RE 3 '93,i11L
All comments must be received by Bob Barkeen no later than the staff
review meeting:
July 30, 2003
Note --PLEASE identify your redlines for future reference
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat Site Drainage Report Other
Utility Redlinc Utility Landscape
'9)
Project Comments Sheet
6186m*0 Selected Departments
( ilti o1 l2ort ("fl1 ra.ti
Department: Engineering
Date: July 30, 2003
Project: RAM'S CROSSING PDP - TYPE I (LUC) #22-03
All comments must be received by Bob Barkeen in Current Planning, no later than
the staff review meeting:
No Review Date
Note - Please identify your redlines for future reference
Issue Contact: Dave Stringer
Topic: General
Number: 17 Created: 7/30/2003
No comments, everything is on site, need to show manhole and underwalk details
Signature
Dttte d U'3
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat Site Drainage Report Other_
Utility _ Redline Utility Landscape
Page I
"z = project Comments Sheet
Selected Departments
l :not Fort Collins ` $
Department: Engineering
Date: December 8, 2003
Project: RAM'S CROSSING PDP - TYPE I (LUC) AND FINAL PLAN
All comments must be received by Bob Barkeen in Current Planning, no later than
the staff review meeting:
December 10, 2003
Note - Please identify your redlines for future reference
Issue Contact: Dave Stringer
Topic: Engineering
Number: 32
[12/8/03] No Problems
Created: 12/8/2003
Hare,
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat _ Site Drainage Report Other
Utility _ Redline Utility Landscape
Page l
6mR.
sr.
: F �
" RESPONSES FOR CITY COMMENTS
By TAS and S&A
THE ARCHITECTS" STUDIO 1211512003 Date: 1211112003
CARR BIEKER
151 W. MOUNTAIN AVE.
FT. COLLINS, CO 80524
The Architect's Studio and Stewart & Assoc. have resonded to City Comments as follows:
Staff has reviewed your submittal for RAM'S CROSSING POP - TYPE 1 allCJ AND FINAL PLAN,
and we offer the fallowing comments:
ISSUES:
Department: Engineering
Topic: Engineering
Number: 32
[12181031 No Problems
S&A: Acknowledged
Department: Stormwater Utility
Topic: Drainage
Number: 19
Issue Contact: Dave Stringer
Created: 121812003
Issue Contact: Wes Lamarque
Created: 713112003
112/9/031
REPEAT COMMENT- There still needs to be a detail regarding the orifice plate and dimensions, as well as how it
is to be attached to the inlet.
Please provide details for the water quality outlet structures on the plans. An outlet structure similar to the City's
standard would be preferred. They can be a smaller version and would provide a better design regarding
aesthetics and spare usage. An area inlet in the middle of the pond sticking out of the ground may be less
appealing visually.
S&A: Details for orifice plate added to Sheet No. 6.
Number: 33 Created.- 121912003
There is a tree still being proposed on top of an area inlet as per previous comment. Please
relocate tree.
S&A: Tree has been relocated.
Topic: Erosion/Sediment Control
Number. 34 Created. 121912003
1. The plan has the wrong erosion control notes. Please use the "new" Loveland/Ft. Collins/Larimer County
notes for sediment and erosion control. Please add to these any notes specific to the construction of this
project.
S&A: Notes have been revised. See Sheet 6.
2. There is no erosion control plan that indicates the BMP's to be used and their location.
S&A: There are now. See Sheet 4.
3. There are no PS or EFF calculations.
S&A: Added PS & EFF to Storm Drainage Report.
Topic: Floodplain
Number: 35 Created. 121912003
1) Sheet 2 of 6- Reference Map. Please change the note to add the word floodplain after Canal Importation Basin.
S&A: Added floodplain to Sheet 2 of 6.
Pagc I
2) Drainage Report
a) Please state the building foundation is slab -on -grade. This is noted on the plans, but not in the report.
S&A: First paragraph under Developed Site section.
h) On Page 1, please state this site is in the Canal Importation floodplain, not just the Canal Importation basin.
S&A: Added to page 1.
c) Please attach the Anderson report. It's referenced, but not attached.
S&A: Attached Anderson report.
Department: Traffic Operations
Topic: Traffic
Number: 31
1111201031 No problems
S&A: Acknowledged.
Department: Water Wastewater
Topic: General
Number: 16
112/10/031
Issue Contact: Eric Bracke
Created. 1112012003
Issue Contact: Jeff Hill
Created: 712812003
Additional fees may be assessed on this additional usage. Contact Mary Young for additional fee information
221-6700.
S&A: Acknowledged.
Number: 36 Created: 1211012003
1121101031 Provide profiles of alf proposed storm sewers.
S&A: See Sheets 5 & 6.
Number: 37 Created: 1211012003
1121101031 Provide complete details for the adjustment of the existing sanitary sewer manhole
(see detail attached to plans).
S&A: See Sheet 6.
Redline drawings are available at the Current Planning front desk. Be sure and return a# of your
redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
Please feel free to call me at (970) 221-6750.
Yours Truly
Bob Barkeen
City Planner
Page 2
Project Comments Sheet
Selected Departments
C itvof 1�oit Collins
,..MMM��
Department: Engineering
Date: January 12, 2004
Project: RAM'S CROSSING PDP -TYPE I (LUC) AND FINAL PLAN
All comments must be received by Bob Barkeen in Current Planning, no later than
the staff review meeting:
January 21, 2004
Note - Please identify your redlines for future reference
Issue Contact: Dave Stringer
Topic: General
Number: 38 Created: 1/12/2004
[1/12/04] Engineering has no further comments on this project.
Engineering okay for mylars, need approval of other reviewing departments
Dave Stringer
Signature
1 /12/04
Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat Site Drainage Report Other_
Utility Redline Utility Landscape
Page l
RAMS CROSSING PDP
STEWART & ASSOCIATES RESPONSES TO STAFF PROJECT REVIEW
DATED 1/26/04
DEPARTMENT: ENGINEERING
No. 38 - Acknowledged ready for mylars
DEPARTMENT: STORMWATER UTILITY:
No. 39 -
Revised Sheets No. 4 and 6 of Utility Plans and Sheets 13, 19 and 25 of the Drainage Report to
revised extended detention opening holes in the restriction plate from 2 1/4" holes to 1-3/9" hole
No. 40 -
I. Relabeled title block on Sheet 4
2. Adding Legend to Sheet 4.
3. The silt fence is shown around the construction site but will now be extended to be placed
where other fences are existing.
4. Please see notes No. 4 thru 7 on Sheet 4. Detention ponds are grassed areas.
5_ Added note to Sheet 4 to see detail Sheets 5 and 6.
RAMS XLuf i rc.pebtf Rrojmv d—
RAMS CROSSING PDP
STEWART & ASSOCIATES RESPONSES TO STAFF PROJECT REVIEW
DATED 1/26/04
DEPARTMENT: ENGINEERING
No. 38 - Acknowledged ready for mylars
DEPARTMENT: STORMWATER UTILITY:
No 39 -
Revised Sheets No. 4 and 6 of Utility Plans and Sheets 13, 19 and 25 of the Drainage Report to
revised extended detention opening holes in the restriction plate from 2 1/4" holes to 1-3/9" hole
No. 40 -
I . Relabeled title block on Sheet 4
2. Adding Legend to Sheet 4.
3_ The silt fence is shown around the construction site but will now be extended to be placed
where other fences are existing.
4. Please see notes No. 4 thru 7 on Sheet 4. Detention ponds are grassed areas.
5. Added note to Sheet 4 to see detail Sheets 5 and 6.
RANVs VINO rup.IIrtm..im. dov