HomeMy WebLinkAboutK MART PLAZA - Filed CS-COMMENT SHEETS - 2004-08-11PROJECT COMMENT SHEET City of Fort Collins Current DATE: January 28, 1998 DEPT: Engineering PROJECT: # 38-97 KMart Plaza Type I (LUC) PDP/FC PLANNER: Ted Shepard ENGINEER: Michael K. Dean All comments must be received by: 1/28/98 Please provide greater detail on the utility plans, as is they are difficult to review due to the lack of information and over crouding of the relevant information. Make corrections to the General Notes as shown on the engineering redlines. Cover sheet layout needs additional information as shown on the redlines. A Title Block located along the far right of the sheet including Engineers Name, Project Name, Project Number, a 3.5" high by 4.5" wide Signature Blo:.. is needed in the lower right comer of each sheet. It is unnecessary to sign and stamp the Utility Plans until after the City of Fort Collins Engineering Department requests Mylar originals for this project. After the original Mylars have been approved by the City of Fort Collins Engineering Department. I will return them to you and request a copy of the original Mylars and 4 signed and stamped bluelines. To have signed and stamped preliminary utility plans circulating prior to the final approved plan could place you in a precarious situation. Provide more distinct differentiation between existing conditions and proposed construction. Include a sheet similar to the Horizontal Control Plan with the Utility Plans. Clarify Legend to include what is revelant to this project this should be included on all relevant sheets. Provide elevations alone, the proposed curb and gutter at spots necessary to conclude if ponding will occur. Label curb and gutter, I believe you intend to use out fall curb and gutter if so also provide a detail. **See redlines for additional comments Date:�t9g Signature:! CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS ,/Plat /Site _DrainageReport Other D A. roFo ,/Utility ✓Redline Utility Landseape This completes the review comments at this time. Additional comments may be forthcoming as the various departments and reviewing agencies continue to review this request. Please provide a written response to each of the above stated comments with the submittal of plan revisions. Please contact me at 221-6750 if you have any questions or concerns that are related to the comments. If you would like to schedule a meeting, please call me as soon as possible. Revisions may be submitted at any time. With the submittal of revisions, please include the enclosed redlined plans. The number of revisions required is attached. Best regards, eanne A. Harter, AICP City Planner xc: Mark McCullum File/Project Planner REVISION COMMENT SHEET wv DATE: 26, September 1998 DEPT: Engineering PROJECT: #38-97 Fuller's Texaco, (LUC) Type I PDP PLANNER: Leanne Harter ENGINEER: Mark McCallum All comments must be received by: 09/02/98 General Comments: More detailed comments will be mentioned below. Utility Plan Comments: Cover Sheet; Sheet I of 5: d--- See redlined comments 2,-There is a new vertical control listing for the City of Fort Collins which does not include fire hydrant benchmark descriptors as being accurate. Therefore, the benchmark descriptors for this project should come from the new vertical control listing. It has been discussed tp allow a tire_ hydrant benchmark descriptor if it id referenced from the new vertical control list. J,A i ,,- - A = E.M. G -4v; ,: -794- Utility Plan; Sheet 2 of 5: 3. An offsite utility easement should be dedicated for the sanitary sewer service. See rcdllnedcomments. Royi�Btif�, yJp� ¢��",4 4-a no'f A- -e e-,'e"Oro S owi'�wea+ !°:-7�/e��, e,{ Own; dti '%fie �o.o�1 Leis✓. 4. See redlined comments. Detail Sheet; 4 of 5: 5. See redlined comments. Plat: 6. An offsite utility easement should be dedicated for the sanitary sewer service. See redlined comments. S e z i�- 3 4 P.D.P. Plan: Site and Landscape Plan Comments: 7. See comments made for the utility plans. 8. See redlined comments that do not match the utility plans. Date: i Signature: Please send copies of marked revisions Plat Site Utility _Landscape City of Fort Collins REVISION COMMENT SHEET DATE: ember 28, 1998 DEPT: Engineering PROJECT: #38-97 Fuller's Texaco, (LUC) Type I PDP/rC_ P-LANNE1 t - ENGINEER: Mark McCallum All comments must be received no later than the staff review meeting: Utility Plan Comments: 1Y The cross -pan should be shown on the utility plan. sheet 2 of 5. f pled F41 i Date: ��� Signature:", /C � Please send copies of marked revisions flat Site ifJtility andscape rr City of Fort Collins PROJECT COMMENT SHEET City of Fort Collins Current Planning DATE: February 27, 1998 DEPT: Engineering PROJECT:#38-97 Kmart Plaza, Fuller's Texaco - Type II - PDP PLANNER: Leanne. Harter ENGINEER: Michael K. Dean, P.E. All comments must be received by: March 25, 1998 O Add additional notes as shown on the redlines to the General Notes. 0 Include a Plat of the site proposed for this development in the Utility Plans. ( even if it's for reference only ) 0 Provide an additional reference elevation in the project benchmark in accordance with the Black Bolt Survey. 0 Provide a Legend in the Utility Plans to identify line types and symbols. 0 The access to West Drake Road will be limited to Right In/ Right Out in the near future in order to accommodate; stacking needs for the East Bound Left Turn Lane from Drake Road to College Ave.. 0 The site boundary shown in the TIS does not match the Site Plan. Date: 3/24 Aqg Signature: CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS ,/Plat , lSite _Drainage Report Other &a,ifp T1S xf6liliry ✓kedline Utility iandseape Commun. Planning and Environmental S. ;ices Current Planning m t k!p City of Fort Collins April 3, 1998 Carr Beiker 117 E. Mountain Avenue Fort Collins, Colorado 80524 Dear Carr: City staff has reviewed the Kmart Plaza, Fuller's Texaco Project Development Plan, #38-97, and offers the following comments: 1. The Zoning Department offered the following: a) Pleas show the handicapped ramps at parking spaces and the sidewalks. b) A trash enclosure shall be provided for the Texaco lot. c) As the project is not located within the Neighborhood Sign District, and therefore, you are not required to show the wall sign elevations. 2. Comments from Building Inspections are attached. 3. Comments from the Poudre Fire Authority are attached. 4. Comments from Water Conservation Specialist are attached. 5. Comments from the Engineering Department are attached. 6. Comments for the Stormwater Utility are attached. 7. Comments from the Water/Wastewater Utility are attached. 8. Comments from the Transportation Planning Department are attached. 9. Comments from Traffic Operations are attached. 10. The Current Planning Department offered the following comments: �81 Forth College :Ac(,nue • P.O. Box 980 • Fort Collins, CO 80522-0580 • (070) 221-o750 • FAX (970) 416-2020 a) Please add a general note on details of the lighting. The photometric plan submitted shows that the lighting exceeds the levels detailed in Section 3.2.4(D) of the Land Use Code. Standards in that section state that "Maximum on -site lighting levels shall not exceed ten (10) foot-candles, except for loading and unloading platforms where the maximum lighting level shall be twenty (20) foot-candles" and "light levels measured twenty (20) feet beyond the property line of the development site (adjacent to residential uses or public rights -of -way) shall not exceed one -tenth (0.1) foot-candle as a direct result of the on -site lighting." Therefore, in order to comply with the requirements of the Land Use Code, it is necessary to do one or all of the following: reduce the wattage, provide high-pressure sodium light sources, or further direct the lighting downwards. This section does have the alternative compliance option that may be submitted by the applicant. Please reference Section 3.2.4(E) of the Land Use Code for details on the section. b) Please provide a detail of the light poles to be used, including wattage, type of light source, type of cover, and height. c) Please show the lights on the site/landscape plan. d) Foundation plantings are required along the south elevation and east elevation according to the requirements of Section 3.2.1(E)(a)(d) of the Land Use Code. e) The proposed removal of the junipers along Drake Avenue does not comply with the screening requirements of Section 3.2.1(E)(4)(a-b) Parking Lot Perimeter Landscaping, and would need to be replaced with other plantings in order to comply with the requirements of this section. The requirements of Section 3.2.1(E)(4)(b) state: Screening. Parking lots with six (6) or more spaces shall be screened from adjacent uses and from the street. Screening from residential uses shall consists of a fence of a wall six (6) feet in height in combination with plant material and of sufficient opacity to block at least seventy-five (75) percent of light from vehicle headlights. Screening from the street and all nonresidential uses shall consist of a wall, fence planter, earthen berm, plant material or a combination of such elements, each of which shall have a minimum height of thirty (30) inches. Such screening shall extend a minimum of seventy (70) percent of the length of the street frontage of the parking lot and also seventy (70) percent of the length of any boundary of the parking lots that abuts any nonresidential use. Openings in the required screening shall be knitted for such features as access ways or drainage ways. Where screening from the street is required, plans submitted for review shall include a graphic depiction of the parking lot screening as seen from the street. Plant material used for the required screening shall achieve required opacitV in its winter seasonal condition within three (3) years of construction of the vehicular use area to be screened. f) There is some confusion as to whether the existing Jiffy Lube site is or is not included within the boundaries of the project development plan. Please clarify this issue. If the Jiffy Lube site is included, additional issues will need to be addressed, including requirements for landscaping and the building and project compatibility standards. g) Please label the landscape plan as the landscape plan and number all the sheets. h) The pedestrian crossings at both access points will be required to be defined according to the requirements of the Land Use Code as outlined in Section 3.2.2(C)(5)(b). i) At this stage, staff would not support the request for alternative compliance to increase the proposed number of parking spaces. The purpose of the section of the Land Use Code must be addressed and additional rationale behind the request for more parking must be provided. j) Please provide a direct pedestrian connection from Drake Road through the two sites (shown on the redlined plans). The area wherein is crossing any drive aisles must be defined according to the requirements of the Land Use Code. k) Please show all bicycle parking 1) Staff strongly encourages the applicant to pursue the reverse layout mode and essentially redesign the site so that it complies with the requirements of the Land Use Code, Section 3.5.3. It may be possible that the building could be rotated 90 degrees and would accomplish the purposes of the standard without necessitating a request for modification. There appears to be potential conflict between the entrance off of Drake and the first access point into the site. The redesign could accommodate the entrance further to the north, and allow for the building to meet the build -to standard, as well as better accommodate pedestrian circulation from Drake Road, and provide space for water quality treatment (which is required by Stormwater Utility). If the applicant decides that redesign in not an option, please be aware that it is likely that staff will not recommend approval of the modification request to the Planning and Zoning Board as the request does not demonstrate that the plan as submitted accomplishes the purposes of the Land Use Code equally well or better than a plan designed according to the requirements of the Code. The request for modification needs to address the criteria outlined in Section 2.7.1 of the Land Use Code. m) Please demonstrate how the pedestrian/automobile interface works at the exit of the car wash. n) Please provide a pedestrian connection to the retail uses to the north of the existing Jiffy Lube. o) Please contact Tim Buchanan, City Forester, regarding the removal of existing trees on site and any tree replacement/mitigation that will follow. p) Please show the square footage of each building. q) Please add the zoning to the vicinity map. r) There should be additional notes regarding bicycle parking, changes to the site necessitating a minor amendment approval, and other standard general notes. s) Please remove the signature block for the Administrative Hearing Officer. However, if the applicant does decide to pursue the reverse mode layout, a modification request is not necessary and the project remains an administrative review rather than review by the Planning and Zoning Board. t) According the Section 3.2.1(D)(1)(c ),"Canopy shade trees shall constitute at least fifty (50) percent of all tree plantings." Therefore, you are required to place more canopy shade trees on the site and reduce the number of ornamental trees. Alternative compliance is available for Section 3.2.1, and any request for such must comply with Section 3.2.1(N). u) The trash collection area shall be screened according to the requirements of the Land Use Code. Please provide shrubbery to provide additional screening. v) Please provide a detail of the trash enclosure and fence. w) What does a "subtle combo" of beige and tan mean? Please provide color samples. x) Please specify the materials to be used for the canopy. y) Please see the attached red -lines for additional comments. 11. The Advance Planning Department offered the following comments: a) The site plan needs to be rearranged to better meet the purposes of (1) Building Standards regarding WHAT the building faces onto and what the street front consists of; and (2) Site Planning standards for pedestrian circulation and access. b) The building as shown is completely surrounded by parking lots and driveways. The canopy along the public street would add to an already overwhelming image of auto -related commercial uses. The plaza is emphasized in the letter but it appears to be a leftover strip isolated from streets and buildings by parking lots and driveways for the gas pumps and car wash. See the enclosed sketch diagram of an alternative approach which makes progress toward meeting the Code requirements and purposes. It looks like it might be helpful to meet with the applicant to discuss the many competing objectives and the need for a fundamentally different layout than the one submitted. This completes the review comments at this time. Additional comments may be forthcoming as the various departments and reviewing agencies continue to review this request. Please provide a. written response to each of the above stated comments with the submittal of plan revisions. Please contact me at 221-6750 if you have any questions or concerns that are related to the comments. If you would like to schedule a meeting, please call me as soon as possible. Revisions may be submitted at any time. With the submittal of revisions, please include the enclosed redlined plans. The number of revisions required is attached. }Best regards, , Leanne A. Harter, AICP City Planner xc: Mike Dean File/Project Planner REVISION COMMENT SHEET City of Fort Collins Current Planning DATE: June 15, 1998 DEPT: Engineering PROJECT:438-97 Kmart Plaza, Fuller's Texaco - Type II - PDP PLANNER: Leanne Harter ENGINEER: Michael K. Dean, P.E. All comnients must be received by: July 8, 1998 Provide signed Easement Dedication documents with exhibits, when you have them available, to be checked and approved by the City. ? 4 4�4 [4r6.. f d-^ /'�•� � eyh"I.h i++-46$.A. ti,Ne t. T!w aw-6+ 44r ♦,j,eA v1ec--•-1 ✓Provide a note on the site and Utility Plans stating, the access to West Drake Road will be limited to Right Ini Right Out in the near future. S a t d'.l -o4 e. The site boundary shown in the T.I.S. does not match the Site Plan, revise the T.I.S.- Plot the tumin;_ radii and provide a scetch of how the tanker truck will access the site. *** See redlines for additional comments.*** Date: Taw 9, 1776 Signature:' CIfECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS ,/Plat _✓Site _Drainage Report Other T�,��Rnon / of TAA)KEA TkoUl .,�t/tility ,/kerlline Utility YLanrlscape Cornmu a Planning and Environmental Current Planning Citv of Fort Collins September 8, 1998 Carr Beiker 117 E. Mountain Avenue Fort Collins, Colorado 80524 Dear Carr: •vices City staff has reviewed the revisions submitted for the Kmart Plaza, Fuller's Texaco Project Development Plan, #38-97, and offers the following comments: 1. The Zoning Department offered the following: a) Please remove the topo lines from the final site plan. b) I don't see any building lighting on the main building or the gas island canopy. Will there be any? Please show on the elevations. 2. Comments from Stormwater Utility are attached. 3. Comments ffrom the Engineering Department are attached. 4. Comments Ifor the Stormwater Utility are attached. 5. Comments from the Water/Wastewater Utility are attached. 6. Comments from the Transportation Planning Department are attached. (For your records, this Division provided copies of previous comments as well.) 7. The Current Planning Department offered the following comments: a) Please add additional language under General Note #1 that the lighting under the canopy will be recessed, and that the average maximum of the lighting on the site does not exceed 10 foot-candles in accordance with the requirements of the Land Use Code. b) Please label the materials proposed to be used on the canopy (i.e., brick columns.) c) Please show all lighting on the elevations. 281 :Cnrth College A%enuc • PO. Box 580 • Fort Collins, CO 8052_'-0580 • (970) 221-6750 • FAX (970) 416-2020