HomeMy WebLinkAboutCOUNCIL - AGENDA ITEM - 03/01/2011 - ITEMS RELATING TO THE GREEN BUILDING PROGRAM DATE: March 1, 2011
STAFF: Brian Janonis, John Phelan _
Felix Lee, Mike Gebc • • •
Items Relating to the Green Building Program.
A. First Reading of Ordinance No. 030, 2011,Amending Chapter 5,Article 11, Division 2,of the City Code for the
Purpose of Amending the 2009 International Building Code as adopted.
B. First Reading of Ordinance No. 031,2011,Amending Chapter 5,Article II, Division 2, of the City Code for the
Purpose of Amending the 2009 International Energy Conservation Code as Adopted.
C. First Reading of Ordinance No. 032, 2011,Amending Chapter 5,Article 11, Division 2,of the City Code for the
Purpose of Amending the 2009 International Residential Code as Adopted.
D. First Reading of Ordinance No. 033, 2011, Amending Chapter 5, Article IV, of the City Code for the Purpose
of Amending the 2009 International Mechanical Code as Adopted.
E. First Reading of Ordinance No. 034, 2011, Amending Chapter 5,Article IV, of the City Code for the Purpose
of Amending the 2009 International Fuel Gas Code as Adopted.
F. First Reading of Ordinance No. 035; 2011, Amending Chapter 5, Article V of the City Code for the,Purpose
of Repealing the Uniform Plumbing Code and Adopting a Local Amendment to the Colorado Plumbing Code
to Establish Water Flow Rate Restrictions on Certain Fixtures.
EXECUTIVE SUMMARY
Implementation of the Fort Collins Green Building Program has the primary goal of better aligning the built environment
with community goals of reduced carbon emissions, reduced energy use and reduced water use. The Green Building
Program framework is designed to support market transformation through a combination of regulatory and voluntary
elements. Green Building Program work over the past year has focused on developing a package of "green
amendments"for incorporation into the Fort Collins Building Code. This process has been led by staff,working closely
with stakeholders. The proposed amendments address opportunities with regard to resource efficiency, energy
efficiency,water efficiency, indoor and outdoor environmental quality,and buildings operation and maintenance. The
benefit cost analysis shows an overall net positive benefit compared with buildings constructed to current Code
requirements. The changes in Code requirements are projected to increase initial design and construction costs by
1% to 2% for residential buildings and 1% to 4% for commercial buildings. Among other benefits, the proposed
changes will provide energy, water and carbon savings compared with buildings constructed to current Code
requirements. Staff recommends the green amendments become effective January 1, 2012, with the exception of
the amendments establishing more stringent requirements for electrically heated buildings, to be effective upon
adoption.
BACKGROUND / DISCUSSION
Implementation of a Green Building Program was identified as a City Council priority during the 2010—2011 budget
process,with a primary goal of better aligning Fort Collins'built environment with community goals of reduced carbon
emissions, reduced energy use and reduced water use. Green building has a strong policy basis with the 2008
Climate Action Plan, 2009 Energy Policy and 2009 Water Conservation Plan.
The Utilities department is leading the effort of developing the Green Building Program in close collaboration with
Community Development and Neighborhood Services (CDNS).
March 1, 2011 -2- ITEM 28
The Green Building Program framework is designed to support market transformation through a combination of
regulatory and voluntary, market-driven elements. Green Building Program work to date has focused on developing
a package of"green amendments" for incorporation into the Fort Collins Building Code.
Green Amendment Development Process
After review of national model green building codes and standards, staff recommended to City Council at the July 13,
2010 Work Session that the project focus on developing a strategic selection of effective amendments to further
..green"the existing Building Codes. A majority of Council members supported the recommendation. Developing a
green amendment proposal was the focus of the project from July through November 2010. (The 2009 International
Codes(I-Codes) package, adopted by Council in September 2010, is the baseline for these amendments.)
The green amendment development process closely involved two Technical Review Advisory Committees, one
focused on the residential sector, the other on the commercial sector. Members were invited to participate based on
their technical and market expertise. Each committee typically met twice a month from May through November 2010.
Attachment 5 lists committee members. Attachment 12 lists comments from committee members on the green
amendment proposal. '
At the December 14, 2010 Work Session, staff presented a draft of the proposed green building practices under
consideration as amendments, along with four additional `options," a proposed implementation schedule and a
preliminary benefit cost summary. A majority of Council supported the direction and directed staff to finalize the
proposal and develop ordinances for adoption in March 2011 (Attachment 4).
Since the December Work Session, staff has refined details of the proposal, developed ordinances to amend the
Building Code, finalized the benefit cost analysis and reviewed the,proposal with boards and commissions.
Community Outreach
In addition to the community involvement via the technical review advisory committees,other community engagement
activities have included:
Web site. Information and opportunities to provide input have been available via the project web pages at
fcgov.com/gbp.
Public meetings. All advisory committee meetings have been open to the public. Meetings have been listed
on the project web pages and City web calendar.
Board,commission and other stakeholder meetings. Staff has presented multiple updates to City boards
and commissions and the Green Building Program Advisory Committee(Attachment 5), as well as to several
other stakeholder groups by request. Board and commission recommendations regarding adoption of the
green amendment ordinances are itemized below.
Public Open House. A public open house was held on November 17, 2010. The associated summary of
feedback was included in the December Work Session Agenda Item Summary.
Attachment 10 is a log of community engagement activities.
Green Amendments Proposal
The green amendments proposal has changed little from the draft package presented to City Council at the December
14,2010 Work Session."Amend ment-proposals-at-a-glance"—listing the proposed green building practices with brief
descriptions, for the residential and commercial sectors—are included as Attachments 1 and 2. Additional details
about each practice are available at the Green Building Program web pages, www.fcgov.com/gbp.
Proposal refinements made since the December Work Session are as follows:
Occupancy sensor controls of lighting in defined spaces. This measure was added to the commercial
amendment proposal, applicable to commercial and multi-family residential buildings. The proposed
amendment would require automatic reduction of connected lighting power by at least 50% in corridors,
enclosed stairwells, parking garages and other intermittently used spaces, when these spaces are
unoccupied. This measure was added as a low-cost practice for reducing electric energy use and carbon
emissions.
March 1, 2011 -3- ITEM 28
Certified wood. A requirement for sustainable forestry certification of wood products used in construction
was in the"option"category at the December 14, 2010 Work Session. A subset of this has been developed
as a proposed amendment. Tropical hardwoods, used in both residential and commercial projects,would be
required to have Forest Stewardship Council certification. Staff recommends this as an appropriate step for
regulation that will help to stimulate more attention and thought toward the"upstream impacts"of extracting
and processing building materials. Since tropical hardwoods are rarely used in entry-level projects,this does
not represent an added expense to the most cost-sensitive portion of the market.
Building envelope requirements for electrically heated residential buildings. The December 2010 draft
package included more stringent thermal requirements for attics,frame walls,windows,crawl spaces and air
leakage of electrically heated buildings, reflecting the significantly higher cost to heat with electricity versus
natural gas. The refinements increase stringency for basement walls, slab-on-grade foundations and mass
walls as well, to more comprehensively address electrically heated buildings.
Effective date for electric heat buildings amendments. Based on Council direction at the December 14,
2010 Work Session, the amended envelope requirements for electrically heated buildings are proposed to
become effective upon adoption of the amendment ordinances. The proposed effective date for the balance
of the amendments is proposed as January 1, 2012.
Other"options" discussed with Council at the December 14, 2010 Work Session, not included in the final proposal,
are:
Envelope requirements for gas-heated homes. Staff recommends that thermal requirements for gas-
heated residential buildings not be increased beyond those in the recently adopted 2009 I-Code package. In
staffs experience, the more important next step in achieving thermal envelope efficiency is increased focus
on the details necessary to install components so they deliver rated performance. This is what drives the
amendments regarding insulation installation standards and installation procedures forwindows,skylights and
doors, as well as plans for training and developing field guides that clearly illustrate important thermal
envelope details. Staff expects to recommend that the next steps in thermal envelope requirements be taken
with the 2012 I-Codes package, currently planned for adoption in 2013.
Renewable energy. Staff recommends that renewable energy requirements remain in the voluntary,market-
driven realm at this time, because they represent a much larger increase in first cost than anything else
included in the proposal. For example, the installed cost of a typical solar electric system for residential use,
three kilowatt peak capacity, is on the order of$18,000. This would add about 7%to the cost of the residential
prototype house used for the benefit cost analysis, far greater than the total estimated cost increase
associated with the green amendment proposal as a whole (see "Financial/Economic Impacts" below). It
would produce about half of the electrical energy used by a typical customer. The average cost of the
electricity produced by the photovoltaic system (over a 20-year life, with a 7%discount rate), would be about
$0.40 per kilowatt-hour, compared to the current Fort Collins Utilities' residential rate of about$0.08/kWh.
The same-sized system on the commercial prototype would add about 1% to the cost of the building, while
meeting only about 3% of annual electrical needs. The $18,000 cost assumes no tax incentives or utility
rebates.
Higher performance requirements for larger homes. Staff recommends that variable green requirements,
based on house size, not be incorporated as part of the Building Code. Though a case can be made that
larger homes built to the same standards as smaller homes have a larger environmental footprint,preliminary
discussion at stakeholder meetings suggested that mandating stricter standards would be very controversial.
This approach is incorporated in the national,voluntary green building rating systems as well as the updated
ENERGY STAR® Homes standard that will be effective in January 2012. As other portions of the Green
Building Program develop,the City may offer increasing levels of recognition and/or incentives based on some
of these programs. Staff recommends gaining more experience through the voluntary approaches before
addressing this through a Code requirement. Attachment 7 provides data on the sizes of single-family homes
built in Fort Collins from 2005 through 2010.
Proposed ordinances have been developed to incorporate the green practices as amendments to the existing Fort
Collins Building Codes. T able 1 itemizes the specific Codes that will be amended and how they apply to different
building types.
March 1, 2011 -4- ITEM 28
Table 1: Building Code and Green Amendment Applicability, by Building Type
Building Type
Building Code Residential:
Single-Family Detached Residential: All Commercial
Duplexes Multi-family 1-Story Mulltifamily 4-Story
Townhouses to 3-Story and Higher
International Building Code Applies Applies
International Residential Code Applies
International Energy Applies (Chapter 4) Applies (Chapter 4) Applies (Chapter 5)
Conservation Code
International Mechanical Code Applies Applies
Colorado Plumbing Code Applies Applies
International Fuel Gas Code Applies Applies
Green Building Practices Not Included in Proposed Amendments
Green building practices that were considered in the development process but not included in the proposed
amendment package are listed in Attachment 6. Many of these practices are already addressed to some extent by
current Fort Collins Codes or will be promoted through voluntary Green Building Program elements (education,
training, recognition, incentives). Some will likely be reviewed in the future for inclusion in other parts of the City Code
or the Land Use Code.
Implementation Planning
Staff recommends a high level of support be provided for a smooth transition to the new Code requirements. A
proposed effective date of January 1, 2012 for all but the electric heat amendments was supported by Council at the
December 14, 2010 Work Session. The period between adoption and implementation provides time to detail
certification requirements and testing protocols, develop new submittal forms and templates associated with the
amendments, develop field guides illustrating acceptable techniques for compliance, and provide training for
contractors and enforcement staff.
Utilities and CDNS will closely work together in support of a successful transition. Table 2 outlines general City
responsibilities, by department:
Table 2: Implementation Roles and Responsibilities
Description Community Development Utilities
and Neighborhood Services Energy Services
Development of verification procedures Primary Secondary
Development of support materials Secondary Primary
Training and education (contractors, inspectors, public) Secondary Primary
Day-to-day implementation (plan review, field inspections, Primary Secondary
administration) (technical support)
Monitoring and evaluation of the implementation process Secondary Primary
and results
March 1, 2011 -5- ITEM 28
FINANCIAL / ECONOMIC IMPACTS
Benefit Cost Analysis
A benefit cost analysis of the proposed green amendments considers benefits and costs related to owners/occupants,
the building sector and the community/ecosystem. The report, Attachment 3, describes the methodologies and
assumptions used in the analysis.
Results show:
• The proposed green amendments align with Fort Collins community goals embodied in the Energy Policy
(2009), Water Conservation Plan (2009) and the Climate Action Plan (2008), while providing a variety of
benefits for building owners and occupants.
• Costs incurred at the individual, building sector or community/ecosystem levels can produce benefits at
multiple levels.
• Near-term cost increases, associated with the design and construction of a building project, are balanced by
recurring benefits delivered over the life of the building. Other community-level benefits improve the economic
picture.
• Initial cost increases projected for building projects are not insignificant, but represent relatively small
percentage increases(1%to 4%); these are within typical variance ranges for construction. It is anticipated
that increased design and construction costs incorporated in this analysis will decrease as contractors gain
experience and infrastructure matures. There are exemplary green,h ig h-performance buildings in Fort Collins
that deliver a strong array of benefits with little or no cost increase compared with conventional construction.
• Reductions of energy,water and carbon are projected on the order of 5%to 10%for residential projects and
20% to 30%for commercial projects.
• The proposed green amendments do not provide a quick"payback"for building owners,based on a traditional
view of utility savings compared with increased design and construction costs.
• Increases in Code enforcement time are estimated on the order of 45%for residential projects and 25% for
commercial projects, requiring additional staffing.
Using generally conservative assumptions and the elements quantified to date,total benefits are projected to exceed
total costs, with a benefit-to-cost ratio of 1.3.
There are direct costs to the City in two areas:
• Development of support materials and training. These pre-implementation phase costs, estimated at
$100,000, will primarily be incurred in 2011. They are one-time costs. The planned materials and training,
discussed above under "Implementation Planning," will support a smooth transition to the new Code
requirements. Funds covering these needs have been appropriated in the Utilities 2011-2012 budget.
• Enforcement. The amendments will represent increased enforcement staff time. This cost has been
accounted for in the benefit cost analysis. Council recently allocated funding from Amendment 2B revenues
to cover increased enforcement staffing, for 2011 and 2012. This means that, in this time frame, building
permit fees will not increase as a result of the green amendments.
Appraisal/valuation
The benefit cost analysis documents ranges of increased initial design and construction costs associated with the
proposed green amendments for prototypical buildings. Staff is aware of potential appraisal and underwriting
challenges related to these cost increases. Residential appraisal procedures have become much more tightly
regulated since the recent mortgage foreclosure crisis, leaving appraisers little latitude in recognizing non-standard
features. These challenges can be real for any building containing features which have not yet been widely
implemented in the market. The challenges are not specific to Fort Collins or green building;they are national in scope
and part of the challenges buyers face when trying to secure financing for a home they wish to build or buy.
Efforts are underway at the state and national level to modify regulations to make it possible to more readily recognize
the benefits of green features in the appraisal process. "Green fields" were recently added to the Multiple Listing
Service database serving Northern Colorado. Education and public awareness building in Fort Collins will also help
to increase market recognition of these benefits.
March 1, 2011 -6- ITEM 28
The proposed green amendments are not unlike other Code updates that have occurred on a regular basis for many
years. Typically, Code updates include increased requirements related to health, safety and energy, many of which
are not immediately recognized by the marketplace. The most recent Fort Collins Code update went into effect in
October 2010 with, for example, increased prescriptive insulation requirements for single-family homes. Appraisal
and valuation issues have not generally been an issue for previous Code updates in Fort Collins.
Development trends
Some stakeholders have expressed concern that adding new regulations to construction in Fort Collins may drive
development to nearby communities with less stringent building codes. This, in turn,could potentially undermine the
green intent of the proposed amendments by increasing vehicle miles traveled and associated environmental effects.
These stakeholders have pointed out that construction activity is currently very low in Fort Collins and that the
proposed amendments may cause a further decline.
Council members asked staff to provide information on development trends in Fort Collins, regionally and nationally
to help better understand these dynamics. Relevant data is summarized in Attachment 8. Construction activity in Fort
Collins,while currently low, is not as low as comparable Northern Colorado communities; it has actually outperformed
the comparables in 2008 to 2010.
As indicated in the benefit cost analysis, concerns about higher initial costs associated with increased Code
requirements are balanced by a variety of other factors. A higher profile for green building can increase a community's
competitive advantage, attracting development and business. The U.S. Green Building Council outlines a business
case for green building for commercial building owners(Attachment 9). This information suggests that green building
is a competitive differentiator, mitigates risk, attracts tenants, is cost-effective and increases rental rates. All of these
factors bolster the City's economic health.
ENVIRONMENTAL IMPACTS
The proposed amendments provide a variety of environmental benefits. Though construction will continue to have
environmental impacts, buildings meeting the proposed amendments will have less impact than buildings built to the
current code.
• Energy savings.These are projected at 5%to 10%of annual use for residential construction and 24%to 36%
for commercial construction.
• Water savings. These are projected at 5%to 10% of total annual use for residential construction and about
20% of indoor water use for commercial construction. Less water use translates to reduced wastewater
treatment needs.
Carbon reduction.These are projected at 5%to 10%of annual emissions for residential construction and 17%
to 26% for commercial construction.
• Landfill diversion. The construction waste recycling amendment will divert materials from the landfill.
Enhanced durability anticipated to result from several amendments will reduce maintenance requirements and
associated waste disposal. These benefits have not been quantified.
• Sustainable forests. The certified wood amendment will require tropical hardwoods used in construction
projects to be obtained from sustainably managed forests. Benefits will be"upstream,"in the areas from which
the lumber is harvested, rather than in Fort Collins. Impacts have not been quantified.
More information is provided in the benefit cost analysis report(Attachment 3).
r
STAFF RECOMMENDATION
Staff recommends adoption of the Ordinances on First Reading.
March 1, 2011 -7- ITEM 28
BOARD / COMMISSION RECOMMENDATION
The Green Building Team gave presentations to boards and commissions regarding the green amendments proposal
during February 2011. Excerpts of minutes reflecting each boards'discussion on this topic are included in Attachment
11.(Recommendations from boards and commissions,that are received after this Agenda Item Summary is submitted
will be included in the Council meeting "read before" packet on March 1)
The recommendations from boards and commissions to which presentations were made prior to submission of this
Agenda Item Summary are as follows:
• Electric Board (February 2) recommended adoption (5-1)
• Affordable Housing Board(February 3)recommended against adoption(5-1). Additional recommendations:
• Ask that City Council consider making these proposed changes to the Code voluntary (rather than
mandatory code) with a reward of reduced fees or approval delays if the project meets stringent green
building Code guidelines.
o If Council declines to make these Codes voluntary, and instead adopts them as part of Code, ask that
Council consider waiving these requirements for projects that qualify as Affordable Housing.
o Alternatively, ask that Council consider funding the Affordable Housing Fund an additional amount
($50,000) that would be set aside just for"green" projects, so that qualified "green" Affordable Housing
projects could apply for and use these funds to offset the increased costs in the new Code.
• Landmark Preservation Commission (February 9) recommended adoption (6-0)
Presentations are scheduled to the following boards and commissions prior to the March 1, 2011 Council meeting;
their recommendations will be forwarded to Council in the "read-before" packet:
• Economic Advisory Commission (February 16)
• Natural Resources Advisory Board (February 16)
• Water Board (February 17)
• Building Review Board (February 24)
• Air Quality Advisory Board (February 28)
ATTACHMENTS
1. Residential Building Code Green Amendments Proposal at a Glance
2. Commercial Building Code Green Amendments Proposal at a Glance
3 Benefit Cost Analysis
4 City Council Work Session Summary—December 14, 2010 re: Green Building Program Update
5 Membership of Stakeholder Advisory Committees
6 Green Building Practices Not Included in Green Amendments Proposal
7 Fort Collins New Home Size, 2005 to 2010
8. Development Trends
9. Business Case for Green Building
10. Community Engagement Log
11. Boards and Commission Minutes
12. Advisory Committee Member Comments
13. Powerpoin presentation
ATTACHMENT
Proposed Residential Code Green Building Amendments ( Prescriptive)
These amendments apply to single-family detached housing , duplexes, townhomes and low-rise (one- to three-story) multifamily housing .
City of
2/9/2011 F6rt Collins
# GB Practice Description * Intent Applicability Type**
RESOURCE EFFICIENCY
Construction waste • Submit recycling plan (who, what, where, how) before project begins Divert construction waste New: Yes
1 recycling • Implement recycling (non-landfill ) for wood, metal , concrete and from landfill Addition: Yes New
cardboard Alteration : No
Support sustainable New: Yes
2 Certified wood Sustainable forestry certification required for all tropical hardwoods forestry practices Addition: Yes New
Alteration : Yes
Windows , skylights, New: Yes
Increased detailing regarding integration of fenestration with exterior Reduce potential for
3 doors : drainage plane exterior moisture damage Addition : Part Refine
installation Alteration : No
ENERGY EFFICIENCY
Building envelope: More rigorous insulation and air sealing specifications for electric-heat Save energy and reduce New: Yes Reinstate
4 thermal specifications Addition: Part
for electric-heat homes homes (beyond 2009 International Residential Code requirements) peak electrical demand Alteration : No + Refine
Set stage for energy- New: Yes
5 Basement windows : Basement windows with comparable performance to windows on main efficient, comfortable living Addition: Part Refine
thermal specifications living levels space when basement is Alteration : No
finished
• Whole-building air leakage: 4.0 ACH50 maximum energy,Capture
p gy, comfort, New: Yes
Air sealing : • Increased focus on effective sealing between house and attached Reinstate
6 tight construction garage durability and health Addition: Part + Refine
• Performance testing required benefits Alteration : Part
Insulation installed to the Residential Energy Services Network
Insulation :
(RESNET) Grade I standard Install insulation so it New: Yes
7 delivers rated energy Addition: Part Refine
installation Exceptions for which RESNET Grade II is acceptable: performance Alteration : Part
• Rim joists
• Exterior walls with continuous rigid insulating sheathing, R-5 minimum .
Added requirements for permit application : Design heating and
• Heating + cooling design load calculations include room-by-room cooling systems that
Heating + cooling New: Yes
loads satisfy comfort needs and
a systems : Addition : Part Refine
design • Air-Conditioning, Heating , and Refrigeration Institute (AHRI) matched perform in accordance Alteration : Part
evaporators, condensing units and furnaces (AHRI certificate required) with manufacturer
• Document key design parameters specifications
Heating , ventilation, air Performance testing of heating , cooling and ventilation systems, aligned
New: Yes
conditioning ( HVAC) with Air Conditioning Contractors of America (ACCA) 5 "Quality Verify that HVAC systems Addition: Part Refine
9 systems : Installation" procedures. Systems operating out of tolerance compared perform as designed + New
commissioning with design specifications will be adjusted and re-tested until they pass. Alteration : Part
WATER EFFICIENCY
Toilets, showerheads and lavatory faucets must meet Environmental New: Yes
10 Water-efficient fixtures Save water and energy Addition : Part New
Protection Agency (EPA) WaterSense® standards.
Alteration : Part
Page 1 of 2
ATTACHMENT
INDOOR ENVIRONMENTAL QUALITY (IEQ)
Atmospherically vented combustion appliances (furnaces, boilers, water Eliminate potential health
Safer combustion heaters, fireplaces) must be placed outside the pressure boundary of and safety hazard of New: Yes
11 appliances : new the house and pass combustion safety test. Addition : Part New
construction (This requirement may also be met with safer combustion appliances: combustion products Alteration : No
power-vented , sealed-combustion or direct-vent.) spilling into house
Safer combustion Atmospherically vented combustion appliances must pass combustion Reduce potential health New: No
12 appliances : existing safety test under "natural conditions." (Applies when combustion and safety hazard of Addition : Part New
buildings appliances are replaced and when other changes are made to house combustion products Alteration : Yes
that may affect pressure balance in combustion appliance zone. ) spilling into house
Interior materials meet maximum VOC emissions standards:
• Sealants + adhesives
Low-Volatile Organic • Resilient flooring Improve indoor air quality New: Yes
13 Compound (VOC) • Carpeting for construction workers Addition : Part New
materials • Paints, stains, varnishes and other site-applied finishes and occupants Alteration : Part
• Structural wood panels, hardwood veneer plywood , particle board , and
fiber board
• Insulation
Provide whole-house, controlled, mechanical ventilation system ,
designed to meet ASHRAE 62.2 requirements. New: Yes
1a Whole-house ventilation Improve indoor air quality Addition : No New
Air handlers used to move ventilation air must be equipped with efficient Alteration : No
blower motors.
OUTDOOR ENVIRONMENTAL QUALITY (OEQ)
Exterior lighting: Increase security New: Yes
15 fixture design Install "dark-sky friendly" exterior lighting fixtures Reduce light pollution and Addition : No New
light trespass Alteration : No
OPERATIONS + MAINTENANCE + EDUCATION
Educate owners about New: Yes
Building owner their home and other
16 education "green" choices they can Provide operations and maintenance manual for building owner Addition: Part New
make Alteration : Part
* Visit the City of Fort Collins Green Building Program web site (www.fcgov.com/qbp) for more information:
• Fort Collins Building Code Green Amendments - context for this evolving proposal
• Expanded descriptions of each proposed green building practice
• Benefits and Costs of Proposed Building Code Green Amendments
** Classifies how the proposed amendment relates to the existing building code:
New: not previously addressed in Fort Collins code
Refine: already addressed in Fort Collins code; the amendment provides more detail or takes it further
Reinstate: similar provision existed in the Fort Collins code prior to fall 2010 update.
Page 2 of 2
ATTACHMENT
Proposed Commercial Code Green Building Amendments ( Prescriptive)
City 0f
These amendments apply to commercial buildings and high-rise (four-story and more) multi-family housing . Fit Collins2/11 /2011 `ram
# I GB Practice Description* I Intent jApplicability
RESOURCE EFFICIENCY
Construction waste ' Submit recycling plan (who, what, where, how) Divert waste from landfill . New: Yes
1 • Implement recycling (non-landfill ) for wood , metal , concrete and Potential disposal cost Addition : Yes
recycling cardboard savings Alteration : No
Support sustainable New: Yes
2 Certified wood Sustainable forestry certification required for all tropical hardwoods forestry practices Addition : Yes
Alteration : Yes
ENERGY EFFICIENCY + CONSERVATION
Energy distribution Each electrical panel supplies only one of the following electricity use measurement and Provides means for New: Yes
s types - Heating, Ventilation , and Air Conditioning (HVAC), Lighting, Addition : Part
design miscellaneous loads, plug loads , & process loads. verification leading to Alteration: No
potential enery savings
Saves energy, improves
Building envelope: air Require continuous air and thermal barrier per The American Society of occupant comfort, New: Yes
a Heating , Refrigerating and Air-Conditioning Engineers (ASHRAE) improves building Addition : Yes
barrier standard 189. 1 . Appendix B durability, reduces pest Alteration : No
problems
Building envelope : Higher specifications for electric-heat buildings beyond 2009 Save energy, reduce peak New: Yes
5 electrically heated electrical demand , improve Addition : Yes
buildings International Energy Conservation Code (IECC) requirements occupant comfort Alteration : No
Building envelope : Stud cavity insulation installed to Residential Energy Services Network Improves performance of New: Yes
B installed insulation (RESNET) Grade I standard . Grade II allowed if exterior insulation insulation - energy savings, Addition : Yes
standards installed to Grade I . better occupant comfort, Alteration: Yes
better building durability
Control of loads in Lighting , switched outlets, and televisions will be controlled when guest Energy savings, operations New: Yes
7 hotel/motel guest rooms are unoccupied . HVAC set point will be relaxed by at least 5 F and maintenance savings Addition : Yes
rooms when room is unoccupied . through increased equipment life Alteration: Yes
Outdoor lighting o Electricity savings, CO2 New: Yes
8 controls Reduce outdoor lighting by 50 /0 2 hours after business closes reduction Addition : Part
Alteration: No
Occupant sensor controls to automatically reduce connected lighting New: Yes
Occupancy sensor power by at least 50% in corridors, enclosed stairwells, storage and Electricity savings, CO2
9 controls stack areas not open to the public, and parking garages when reduction Addition : Part
Alteration: No
unoccupied.
Energy assessments Energy assessments required prior to building alterations. No-cost Identify energyefficient New: No
10 9y 9Y q p g � y Addition : No
for alterations assessment provided by Fort Collins Utilities. opportunities Alteration : Yes
WATER EFFICIENCY + CONSERVATION
Water Efficient New: Yes
11 Fixtures See table ( based on Water Sense standard ) Water savings Addition : Part
Alteration : Part
(continued on other side)
Page 1 of 2
ATTACHMENT
# GB Practice Description* Intent Applicability
INDOOR ENVIRONMENTAL QUALITY (IEQ)
Protect ducts from contamination during construction Avoid introducing New: Yes
Air handling system access & ability to clean and maintain contaminants into supply
12 HVAC IAQ Design Addition : Yes
No friable materials in air plenums air and provide means for Alteration: Yes
maintaining air quality.
Flush out building contaminants by operating at prescribed outside air Remove pollutants New: Yes
13 Building flush-out generated from outgassing Addition : Part
setting for 14 days. of new materials Alteration: Part
Interior materials meet maximum VOC emissions standards :
• Sealants + adhesives
Low-Volatile Organic • Resilient flooring Improve indoor air quality New: Yes
14 Compound (VOC) • Carpeting for construction workers Addition : Part
materials • Paints, stains , varnishes and other site-applied finishes and occupants Alteration : Part
• Structural wood panels, hardwood veneer plywood , particle board , and
fiber board
Requirements for exterior-to-interior sound transmission , interior sound Reduce noise disturbances New: Yes
15 Acoustical control transmission , and background sound levels. for occupants Addition : Part
Alteration : No
COMMISSIONING / OPERATIONS + MAINTENANCE
Provide Fundamental Commissioning with addition of commissioning Ensure that building New: Yes
16 Commissioning systems are installed and Addition : Part
building envelope materials and assemblies. operate per owner's intent Alteration: No
*Visit the City of Fort Collins Green Building Program web site (www.fcciov. com/cibp) for more information :
• Fort Collins Building Code Green Amendments
• Expanded descriptions of each proposed green building practice
• Benefits and Costs of Proposed Building Code Green Amendments
Page 2 of 2
ATTACHMENT 3
Benefits and Costs of
Proposed Building Code Green Amendments
Executive Summary
The intent of the benefit cost analysis of the proposed building code green amendments is to consider
benefits and costs related to owners/occupants, the building sector and the community/ecosystem.
Results show:
• The proposed green amendments align with Fort Collins community goals embodied in the Energy
Policy (2009), Water Conservation Plan (2009) and the Climate Action Plan (2008), while
providing a variety of benefits for building owners and occupants.
• Costs incurred at the individual, building sector or community/ecosystem levels can produce
benefits at multiple levels.
• Near-term cost increases, associated with the design and construction of a building project, are
balanced by recurring benefits delivered over the life of the building. Other community-level
benefits improve the economic picture.
• Initial cost increases projected for building projects are not insignificant but represent relatively
small percentage increases (one to four percent); these are within typical variance ranges for
construction. It is anticipated that increased design and construction costs incorporated in this
analysis will decrease as contractors gain experience and infrastructure matures. There are
exemplary green, high-performance buildings in Fort Collins that deliver a strong array of benefits
with little or no cost increase compared with conventional construction.
• Reductions of energy, water and carbon are projected on the order of five to ten percent for
residential projects and on the order of 20% to 30% for commercial projects.
• The proposed green amendments do not provide a quick "payback" for building owners, based on a
traditional view of utility savings compared with increased design and construction costs.
• Increases in code enforcement time are estimated on the order of 45% for residential projects and
25% for commercial projects, requiring additional staffing.
Using generally conservative assumptions and the elements quantified to date, total benefits are
projected to exceed total costs. A benefit-to-cost ratio of 1 . 3 is projected.
1. Introduction
Staff has developed proposed building code green amendments for City Council consideration. One
package of amendments addresses residential buildings, the other addresses commercial buildings. Staff
worked with a consultant, The Brendle Group, to develop a benefit cost analysis for the proposed
amendments.
The charge from City Council to staff regarding "greening" the Fort Collins building code was to
develop amendments that align with City goals around reducing energy use, water use and carbon
emissions, while also addressing other green building opportunities such as improved indoor air quality.
Buildings complying with the proposed amendments will deliver additional benefits compared with
buildings complying with the current code. The changes also will, for many projects, mean higher initial
costs. This analysis has been prepared to support Council' s decision-making process by outlining and
1 of 11
ATTACHMENT 3
quantifying, where feasible, the range of benefits and costs associated with the proposal. Benefits and
costs are approached from a "triple-bottom-line" perspective, reflecting social, economic and
environmental impacts .
This report describes categories of benefits and costs related to green building, the analysis methodology
and results. Appendices provide additional detail. "Amendments-at-a-Glance" summaries of the
proposed packages and in-depth descriptions of each individual amendment (including benefits and
costs) are available on the Building Code Green Amendments web page at www. fcgov.com/lzbp.
There are many ways to design and build buildings. Tabulating benefits and costs is an imprecise
science. In developing the analysis, a generally conservative approach was taken so that benefits would
not be overstated and costs would not be understated.
2. Benefit Cost Categories
Figure 1 illustrates categories of benefits and costs related to green building. They occur at three inter-
related scales, represented by concentric circles:
• Individual. A specific project, where the impacts are traced to an owner or tenant.
• BuildingSector.ector. The building services industry, which includes design and construction
professionals and product suppliers.
• Community/Ecosystem. Local, regional or global costs or benefits.
Costs are shown on left-hand side of the diagram, benefits on the right-hand side. Each category is
described below.
2of11
ATTACHMENT 3
Figure 1 : Benefit Cost Categories
COSTS BENEFITS
COMMUNITY / ECOSYSTEM
I *,**
**** environment
BUILDING SECTOR
/ ♦ w - l `
/ INDIVIDUAL building valuation ✓ BEST
PLAES
/ z TO LIVE
utility jobs
training I , I savings 1 1 economic
+ support I I I health
materials
1 maintenance ► 1
1 training , savings g
1
` near-term
carbon
reduction
health
- productivity
' $ ' building sector 4
enforcement investment /
other costs
Oinfrastructure
QA +
evaluation
3of11
ATTACHMENT 3
Cost Categories (see Figure 1)
• Individual, Near-term. Increased, one-time cost to design/build a building. The "$" signs get smaller
in the graphic to represent decreasing costs as the industry moves along a prototypical learning
curve. The varying size of the "$" signs also represents the range of initial cost increases, depending
on the starting point of the construction team.
• Building Sector, Training. Building sector costs related to training on new construction techniques
and compliance requirements. These are near-term costs that will be amortized over many projects.
• Building Sector, Other. Other building sector costs, such as buying new tools or obtaining and
maintaining new certifications. These are primarily near-term costs that will decrease over time
based on market development, competition and adaptation.
• Community, Training + Support Materials. Pre-implementation phase (prior to the January, 2012
effective date of the green amendments in) costs borne by the City cover the development of support
materials, staff training and subsidization of industry training.
• Community, Enforcement. Increased implementation costs related to the City' s day-to-day
enforcement of the green amendments. These could be borne by building owners (through building
permit fees) or by the community as a whole or a combination.
• Community, Quality Assurance + Evaluation. Implementation costs, borne by the City, for on-going
quality assurance and program evaluation.
Benefit Categories (see Figure 1)
• Individual, Utility Savings . Lower utility costs for electricity, natural gas, water and wastewater.
• Individual, Maintenance Savings. Some green amendments will result in reduced maintenance costs,
which will accrue to the occupant and/or owner of the building.
• Individual, Building Valuation. Green buildings are expected to command an increased value in the
marketplace compared with conventional buildings.
• Individual, Occupant Health + Productivity. The green amendments will lead to improvements in
indoor environmental quality (improved thermal comfort, improved indoor air quality) . These, in
turn, will improve occupant health and productivity.
• Building Sector, Jobs. The building sector will realize an increase in job activity for a given amount
of construction activity. The green amendments support the expansion of related infrastructures,
higher-level contractor skills, increased demand for green services and increased demand for green
products.
• Building Sector, Investment. The building sector will realize increased investment through the
supply chain development cycle. Beyond the direct job impact described above, direct suppliers,
indirect suppliers, products and materials vendors will develop and mature, resulting in reduced cost
premiums over time.
• Community, Economic Health. The green amendments support the community' s values, pride and
identity as a vibrant, environmentally conscious place to live. The community' s reputation as such
also supports economic health as by attracting outside investment and local economic development.
Progressive public policy has been shown to increase activity in many instances related to green
building and clean energy.
4of11
ATTACHMENT 3
• Community, Infrastructure. Direct benefits of green building (reduced energy use, water use and
waste) have indirect impacts on community infrastructure requirements, such as extending the life of
existing investments in power supply, water supply and landfills.
• Community, Carbon Reduction. The direct results of green building (reduced energy use, water use
and waste) contribute directly to the community' s goals to reduce carbon emissions.
• Community. /system, Environment. In addition to carbon reduction, the green amendments
reduce environmental impacts associated with construction (resource use, waste, outdoor
environmental quality).
3. Analysis and Results
Benefits and costs have been quantified where feasible. They were assigned value using either of two
approaches :
• Component analysis. The impacts of each proposed amendment were analyzed to develop building-
specific benefits and costs, and code enforcement costs.
• Community-scale analysis. This approach, which included applying the results of research
performed elsewhere to Fort Collins, was used to estimate benefits related to building valuation,
occupant health and productivity, economic health and carbon reduction.
Other types of costs and benefits have not been quantified. Tables 1 and 2 show generally how each
category was handled in the analysis. More information follows in Sections 3 . 1 and 3 .2 .
The quantified elements have been compared to develop a benefit-to-cost ratio. It must be emphasized
that the benefit cost analysis is approximate, reflecting uncertainties in accurately quantifying both
benefits and costs.
The analysis focused on new construction. Existing building scenarios (alterations and additions, from
minor to very large) are too varied to be analyzed with this approach and timeframe. Also, many of the
proposed amendments do not apply to existing buildings or apply only in part (see "Applicability"
information in the "Amendments-at-a-Glance" summaries and the detailed description of each proposed
practice at www.fcgov. com/gbp).
5of11
ATTACHMENT 3
Table 1 : Quantified Benefits and Costs
Benefit Cost Category Analysis Approach
COST: Individual , Initial Component analysis
COST: Community, Training + Support Materials Estimated
COST: Community, Code Enforcement Component analysis
BENEFIT: Individual , Utility Savings Component analysis
BENEFIT: Individual , Building Valuation Community-scale analysis ; national studies applied
BENEFIT: Individual , Occupant Health + Productivity Quantified in part using community-scale analysis ; national
studies applied to estimate part of the benefit
BENEFIT: Building Sector, Jobs
BENEFIT: Building Sector, Investment Community-scale analysis ; these three categories are
represented as part of "economic impact' multiplier.
BENEFIT: Community, Economic Health
BENEFIT: Community, Carbon Reduction Community-scale analysis ; calculated based on utility
savings
Table 2 : Non-Quantified Benefits and Costs
Benefit Cost Category Notes
COST: Building Sector, Training Primarily near-term costs amortized over many projects .
COST: Building Sector, Other Primarily near-term costs that will decrease over time .
COST: Community, Quality Assurance + Evaluation Quality assurance and evaluation plans to be developed
BENEFIT: Individual , Maintenance savings Larger maintenance costs are episodic and challenging to
quantify. Savings could be significant over life of building .
Non-quantified "people" benefits related to health and
BENEFIT: Individual , Occupant Health + Productivity productivity have been tabulated for certain amendments;
see detailed description of each amendment at
www .fcqov.com/qbp .
Incremental benefits from greener building add to benefits
BENEFIT: Community, Infrastructure from other conservation / efficiency / renewables efforts for
potentially significant cumulative impact.
Non-quantified "environment' benefits have been tabulated
BENEFIT: Community/Ecosystem , Environment for each proposed amendment; see detailed description of
each amendment at www.fcgov . com/qbp .
6of11
ATTACHMENT 3
3 . 1 Quantified Elements
Costs and benefits quantified via component analysis and community-scale analysis are described in the
Subsections 3 . 1 . 1 and 3 . 1 .2, respectively. Results are summarized and combined to calculate the benefit-
to-cost ratio in Subsection 3 . 1 .3 .
3. 1 .1 Component Analysis
Primary benefits and costs of the proposed green amendments for typical projects were quantified via
component analysis. Primary benefits are the reduced utility costs (electricity, natural gas, water and
wastewater). Primary costs are increased design and construction costs. The analysis reflected each
proposed amendment.
Important aspects of the analysis include:
• Benefits and costs are generally presented as ranges. This reflects that, for each proposed code
amendment, there are often multiple ways to comply; different contractors have a range of
experience and a range of costs for products and labor; there is uncertainty in estimating benefits and
costs of building projects.
• It is assumed that all increased first costs are passed directly to the owner of the building.
• "Cost" represents retail cost
• Data sources included architects, builders, trade specialists, product suppliers, staff experience,
energy modeling, other studies and analyses.
• Generally, conservative values have been chosen so as to not overstate benefits or understate costs.
Building-specific benefits and costs were developed for two prototypical buildings to which the majority
of the proposed amendments could be applied:
• Residential
- 1 ,600 square foot ranch over full basement (3 ,200 sf conditioned area)
- Natural gas heat
- $250,000 sales price, financed with a 6%, 30-year mortgage
- $2,600 annual utility cost
• Commercial
- 15 ,000 square foot office building, two stories
- Natural gas heat
- $ 162 per square foot construction cost ($2 .4 Million)
- $ 14,000 annual utility cost
The team recognizes that these are limited examples of the many types and sizes of buildings in the
market. These were developed to provide a more tangible reference for benefits and costs.
Benefits and costs associated with each proposed amendment are provided in Appendix 1 (residential)
and Appendix 2 (commercial) . Totals are shown in Tables 3 and 4, representing the set of applicable
green building practices for each project. The base case is the prototype project meeting current Fort
Collins code requirements .
7of11
ATTACHMENT 3
Table 3 : Quantitative Results — Residential Prototype (1 ,600 square foot ranch)
Description Range ($) Range (%)
Sales Price Increase $2,800 to $5 , 600 1 % to 2% of sales price
Monthly Mortgage Impact $ 17 to $34 1 % to 2% of monthly payment
Annual Utility Cost Savings $65 to $171 3% to 7% of utility cost
Energy Savings -- 5% to 10 % of annual use
Water Savings -- 5% to 10 % of annual use
Carbon Savings -- 5% to 10% of annual emissions
Table 4 : Quantitative Results — Commercial Prototype (15,000 square foot office building)
Description Range ($) Range (%)
Construction Cost Increase $30 , 000 to $ 100,000 1 % to 4% of construction cost
Annual Utility Cost Savings $ 1 ,800 to $3 ,400 13% to 25% of utility cost
Energy Savings -- 24% to 36% of annual use
Water Savings -- 20% of annual indoor use
Carbon Savings -- 17% to 26% of annual emissions
Enforcement costs were also estimated using component analysis. The Building Official evaluated the
impact of each proposed amendment on the time required for plan review, field inspection and
administrative tasks. Estimated increases versus the workload associated with the existing codes are on
the order of 45% for residential projects and 25% for commercial projects (see Appendix 3 for more
detail). The increased workload translates to an additional 1 .5 full-time equivalent positions in the
Building Department, valued at approximately $ 158K annually for salary and benefits.
3. 1 .2 Community-Scale Analysis
The consultant reviewed published regional and national studies of green building benefits and costs
relative to individuals as well as communities, economies and ecosystems . The consultant also spoke
with City economic development staff. This research indicates there are many benefits associated with
green, high-performing buildings, including energy and environmental awareness, economic health,
community pride and the opportunity to hedge against utility rate increases.
Based on the available information, the consultant quantified four benefits with sufficient confidence to
inform the Fort Collins analysis. These are summarized here; additional information is provided in
Appendix 4. Note that all of these analyses should be considered "order-of-magnitude" in nature.
Because there are many uncertainties when applying the research to the green amendments proposal,
conservative assumptions have been made.
• Building valuation. Studies show that labeled "green buildings" command higher value in the
marketplace than their conventionally built counterparts. For this analysis, a one-percent increase in
valuation was applied.
• Occupant health and productivity. Research has shown that occupants of green buildings tend, on
average, to be healthier and/or more productive. The consultant extrapolated the research results to
estimate the 20-year net present value of health cost savings for occupants of residential buildings
8of11
ATTACHMENT 3
($28 per person) and increased productivity of commercial building occupants ($4. 61 per square
foot).
• Economic health. This term reflects increased local economic activity associated with increased
construction spending. It ties to three of the benefit categories illustrated in Figure 1 : Building
Sector, Jobs; Building Sector, Investment; and Community, Economic Impacts. Based on
conversations with City economic development staff, the consultant used an economic multiplier of
0. 5 of the increased construction cost. In other words, 50% of the increased cost attributed to the
green amendments is re-injected into the local economy
• Carbon reduction. Carbon savings are the only ecosystem benefit quantified in this analysis. Though
carbon is not yet widely traded in the United States, a variety of research provides a basis to estimate
the likely market value of savings. The consultant used a value of $20 per metric ton of carbon
savings.
3. 1 .3 Benefit-to-Cost Ratio
The benefits and costs that have been quantified can be totaled and compared. This was done using the
following approach and assumptions :
• A net present value approach was used to account for the stream of future benefits (such as annual
utility savings and improved occupant productivity) and compare them against costs incurred when
the building is built. Consistent with many building analyses, a term of 20 years was used. A 7%
discount rate, including 2% general inflation of goods and services, was assumed.
• Utility rates are assumed to stay constant at today' s values.
• Construction activity is assumed to be 200 new homes and 10 new commercial office building
projects per year (other commercial construction is not reflected in the analysis). Actual construction
activity is difficult to predict; the analysis model is readily scalable.
Tables 5 and 6 summarize the data reported above, as extrapolated to the community scale using the
construction activity assumptions in the previous bullet. These summaries represent the benefits and
costs associated with one year of construction.
Table 6 includes a roughly estimated cost ($ 100K) associated with training and development of support
materials prior to the effective date of the green amendments.
It is important to recognize that the quantitative analysis only tells part of the benefits and costs story.
Non-quantified aspects are discussed in the next section.
9of11
ATTACHMENT 3
Table 5 : Community-scale Benefit Summary
("K" = thousand, "M" = million, "NPV" = Net present value)
Benefit Commercial Residential Total Notes
Individual , Utility Savings $273K $250K $523K NPV of recurring benefits
Individual , Building Valuation $243K $500K $743K One-time benefit at time of sale
Individual , Occupant Health $69K $22K $91 K NPV of recurring benefits
+ Productivity
Community, Economic $331 K $420K $751 K One-time benefit at time of
Health construction
Community, Carbon $76K $50K $ 126K NPV of recurring benefits
Reduction
Total benefits $2 .23M
Table 6 : Community-scale Cost Summary
("K" = thousand, "M" = million)
Cost Commercial Residential Total Notes
Community, Training +
Support Materials $ 100K One-time cost (mostly in 2011 )
Individual , Initial $662K $840K $ 1 . 50M One-time cost at time of
construction
Community, Enforcement $ 158K One-time cost at time of
construction
Total costs $ 1 . 76M
Given the many assumptions underlying the data presented in this section, the ratio of benefits to costs
for the proposed green amendments is $2 .23 Million to $ 1 . 76 Million, equaling 1 .3 .
3.2 Non -Quantified Elements
As described above, not all benefits and costs have been quantified. Table 2 lists those that were not and
includes brief comments for each. Some of these categories could be quantified with more information.
Others are more inherently qualitative, such as the benefits of a darker night sky.
Non-quantified benefits associated with each proposed amendment are listed under the "People" and
"Environment" benefit headings in the detailed descriptions available at www.fcgov. com/gbp. Many of
these benefits can be grouped into categories such as improved comfort (from improved building
envelopes and better-performing heating and cooling systems), better indoor environmental quality
(from building materials with lower pollutant emissions, safer combustion appliances, whole-house
ventilation, building flush-out, acoustic requirements), improved outdoor environmental quality (Dark-
Sky lighting fixtures), and conservation of resources for future generations (energy-efficiency measures
and construction waste recycling) . Some of these benefits will accrue to the individual owner or
occupant while others are community benefits.
Non-quantified costs primarily reflect the process of change from conventional practices.
10 of 11
ATTACHMENT 3
4. Discussion
The proposed building code green amendments involve many types of benefits and costs . This analysis
suggests:
• Benefits and costs can be associated with individuals, the building sector, the community and
ecosystem. Costs incurred at one level can produce benefits at multiple levels .
• Near-term cost increases, associated with the design and construction of a building project, are
balanced by recurring benefits delivered over the life of the building. Other community-level
benefits improve the economic picture.
• Initial cost increases projected for building projects are not insignificant but represent relatively
small percentage increases (one to four percent); these are within typical variance ranges for
construction.
• The proposed green amendments align with Fort Collins community goals embodied in the Energy
Policy (2009), Water Conservation Plan (2009) and the Climate Action Plan (2008), while
providing a variety of benefits for building owners and occupants.
• The proposed green amendments do not provide a quick "payback" for building owners, based on a
traditional view of utility savings compared with increased design and construction costs.
• The relative magnitude of utility savings and associated carbon reduction is considerably higher for
commercial buildings than for the residential sector. The commercial opportunities are greater
because building code has lagged in addressing key opportunities in the areas of building envelope
and commissioning.
• The three largest projected benefits are utility savings, economic health gains and higher building
valuation. Making this latter benefit a reality will require education of the market and progress in
removing barriers in the appraisal and underwriting processes.
Based on the elements quantified to date, total benefits are projected to exceed total costs.
While there are uncertainties in accurately quantifying both benefits and costs, the intent of this analysis
was to capture the essence of the benefits and costs within the scope, budget and timeframe of this
proj ect.
To avoid overstating benefits or understating costs, the analysis team has generally made conservative
assumptions. For example, building cost increases used in the analysis generally reflect the current
situation in Fort Collins, in which some of the proposed amendments address practices for which many
contractors have little experience and the infrastructure to efficiently implement the practices is not well
developed. Experience with past code changes suggest that many costs are likely to significantly
decrease over time, as contractors move up the learning curve and infrastructure matures. It should also
be noted that there are exemplary green, high-performance buildings in Fort Collins that deliver a strong
array of benefits with little or no cost increase compared with conventional construction.
11 of 11
ATTACHMENT 3
Appendix 1
Component Analysis Summary : Residential Prototype
Direct Owner Financial Impact
2/15/2011 Initial Cost Impact Range Net Utility Savings Range ($/yr) Maintenance /
# GB Practice Notes Low High Notes Low High Durability Impacts ( 1 )
Construction waste Net change = increased
1 recycling cost less decreased $0 $200 $0 $0 N/A
recycling landfill cost
2 Certified wood No tropical hardwoods used $0 $0 $0 $0 N/A
in entry level home
Windows skylights Potential to avoid large maintenance/repair
, ,
3 $250 $350 $0 $0 costs related to exterior water leakage at
doors: installation
fenestration openings
Building envelope: N/A for gas-heated prototype N/A for gas-heated
4 thermal specifications, home $2,200 $2,500 prototype home $300 $400 N/A
electric-heat homes (2)
Avoid significant window replacement cost
Basement windows: when basement is finished
5 thermal specifications $45 $75 $3 $6
Reduced maintenance costs related to
condensation on windows
Hypothetical savings vs
2009 IRC requirement (7.0 Field study shows most new $100/yr Hypothetical: less maintenance / repairs to
A100/yr gas heat, $250/yr building due to moist air condensing in
6 Air sealing : homes already tighter than $50 $200 elec heat $0 $25 building cavities
tight construction proposed standard
Reality for most houses: $0 Reality: Typically $0 (already captured by
(already captured by even tight construction)
ti hter construction
7 Insulation: $200 $350 $30 $60 Minor savings possible
Installation
8 Heating + cooling
systems: design Evaluate benefits + costs for Equipment running within manufacturer
Heating, ventilation, air Evaluate benefits + costs for $400 $500 these two measures $30 $60 spec will need less maintenance and last
9 conditioning (HVAC) these two measures together together longer.
systems:
commissioning
10 Water-efficient fixtures $50 $200 Saves water, wastewater, $40 $60 N/A
natural qas
Low = sealed, tested
Safer combustion mechanical room Low = less air leakage
11 appliances: new $1 ,300 $2,500 $12 $60 Health benefits = maintenance savings
construction High = safer furnace + water High = 90 AFUE furnace
heater
Safer combustion
12 appliances: existing N/A for new construction N/A for new construction Health benefits = maintenance savings
buildin s 2
Health benefits = maintenance savings
Low-Volatile Organic
13 Compound (VOC) $200 $400 $0 $0 No info regarding durability of low-VOC
materials products versus conventional. Higher or
lower maintenance?
14 Whole-house ventilation Exhaust-only system $150 $400 Operating cost INCREASE ($60
rather than savings ) ($120) Health benefits = maintenance savings
15 Exterior lighting: $40 $120 Assume no change in lamp $0 $0 N/A
fixture design I I Iwattage
16 Building owner education $150 $300 $10 $20 Properly operated and maintained eqpt
should yield maintenance savings.
INITIAL COSTS UTILITY SAVINGS BENEFIT ( 1 )
TOTALS for new construction,
prototype home (2) Low High Low High
Purchase price
$2,835 $5 ,595 increase $65 $ 171 Annual utility bill decrease
1 ,600 sq ft ranch over full basement (3,200 sq ft total) $ 17 $34 Monthly mortgage
Natural gas heat payment increase $5 $ 14 Monthly utility bill decrease
$250,000 sales price, 6%, 30-yr mortgage o Percent of base price o 0
$2,600 annual utility cost 1 . 1 o/o 2 .2 /0 or payme 2.5 /0 6.6 /o Percent of base utility bill
nt
(1 ) Savings due to reduced maintenance / enhanced durability are not quantified or reflected here. They would improve the economic case for the building owner.
(2) Two measures not applicable to new, gas-heated prototype home are not included in total costs or benefits.
ATTACHMENT 3
Appendix 2
Component Analysis Summary : Commercial Prototype
Direct Owner Financial Impact
2/16/2011 Initial cost impact range Net utility savings range ($/yr) Maintenance I
# GB Practice Notes Low High Notes Low High Durability Impacts ( 1 )
Net change =
1 Construction & Site increased recycling $0 $600 $0 $0 N/A
waste recycling cost, decreased landfill
cost.
2 Certified Wood $0 $0 $0 $0 N/A
Requires next step of Allows monitoring of specific
Energy Distribution installed monitoring
3 Design Requirements $1 ,650 $1 ,950 equipment to realize $0 $0 systems, potentially leading to
savings maintenance savings.
Less infiltration and thus less
4 Building Envelope: Air ;$2,250
11 .250 $22,500 $750 $1 ,050 moisture transport through
Barrier building envelope resulting in
better durabilityBuilding Envelope: Does not apply to gas- Does not apply to
5 electrically heated heated building - not $3,750 gas-heated building - $450 $600
buildin s f21 included in total not included in total
Building Envelope: May improve building durability
6 Installed insulation $0 $0 $255 $315 by reducing condensation sites
standards within the envelope.
Control of loads In Assumes 15,000 SF of 050 $23100 $2250 $2850 Assumes 15,000 SF Longer life for lamps and
7 Hotel/Motel guest rooms. $16, , of rooms. . , equipement being controlled.
rooms 2
8 Outdoor lighting Cost for controls $450 $600 $ 180 $210 Longer life for lamps being
controls controlled.
9 Occupancy sensor Utility incentives would $1 ,200 $1 ,500 $60 $75
controls reduce cost
Energy assessments Assessement cost Savings result only if
10 covered by Fort Collins $0 recommendations $0 $0
for alterations (2) Utilities. are implemented.
Water savings only -
11 Water-efficient fixtures $0 $0 does not include $30 $330
natural gas or
store water.
Potentially improves
12 HVAC [Act Design $0 $0 $0 $0 maintainability of HVAC
e ui ement.
Costs represent HVAC Small one-time cost
13 Building Flush-out tech time to reprogram $900 $1 ,050 penalty for extra $0 $0
system. energy used to
condition outside air.
Health benefits = maintenance
savings
Low-Volatile Organic
14 Compound (VOC) $0 $1 ,500 $0 $0 No info regarding durability of
materials low-VOC products versus
conventional. Higher or lower
maintenance?
Depends on baseline A building envelope enhanced
15 Acoustical Control (2) $0 $25,500 $0 for acoustic purposes may also
building envelope. be more durable.
Based on complexity of Improved operations &
16 Commissioning systems to be $15.000 $75,000 S585 $1 ,455 maintenance for commissioned
commissioned. I I systems.
TOTALS for new construction, INITIAL COSTS UTILITY SAVINGS BENEFIT ( 1 )
prototype commercial
office building (2)
Low High Low High
15,000 sq ft office building $309450 $104,700 Construction $1 ,860 $3,435 Annual utility bill
Natural gas heat cost increase decrease
$2.4 Million construction cost Percent of
$14,000 annual utility cost 1 . 3% 4.4% construction 13% 25% Percent of base utility
cost bill
(1 ) Savings due to reduced maintenance / enhanced durability are not quantified or reflected here. They would improve the economic case for the building owner.
(2) Some practices apply only to unique situations or specific buildling types and were not included in the totals for the representative building.
ATTACHMENT 3
Appendix 3
Component Analysis Summary : Enforcement Costs
Enforcement costs were estimated using component analysis. The Building Official evaluated the
impact of each proposed amendment on the time required for plan review, field inspection and
administrative tasks, for the same prototype buildings used to estimate building-specific benefits and
costs. Results are summarized in Tables 1 and 2 .
Table 1 : Residential Enforcement Time Impacts
Scenario Plan Review Field Inspection Administrative Total
Current codes 6 . 0 to 8. 0 hrs 3 . 1 to 5.3 hrs 2 hrs 11 to 15 hours
Additional time for proposed 1 .6 to 2. 8 hrs 1 . 9 to 3.2 hrs 1 hr 5 to 7 hours
green amendments
Total time with green 7 . 6 to 10 .8 hrs 5. 0 to 8.5 hrs 3 hrs 16 to 22 hours
amendments
Approximate percentage 30% 60% 50% 45%
time increase
Table 2 : Commercial Enforcement Time Impacts
Scenario Plan Review Field Inspection Administrative Total
Current codes 16 to 24 hrs 5 . 9 to 9. 1 hrs 2 hrs 24 to 35 hrs
Additional time for proposed 2 . 3 to 3 . 8 hrs 2 .2 to 3 . 3 hrs 1 hr 6 to 8 hrs
green amendments
Total time with green 18 to 28 hrs 8 to 12 hrs 3 hrs 29 to 43 hrs
amendments
Approximate percentage 15% 40% 50% 25%
time increase
1
ATTACHMENT 3
Appendix 4
Community-Scale Analysis
To provide insight to complement the component analysis approach, the consultant reviewed published
regional and national studies of green building benefits and costs relative to individuals as well as
communities, economies and ecosystems. The consultant also spoke with City economic development
staff. This yielded additional information that supported the community-scale analysis.
The community-scale benefits and costs are challenging to quantify, given the range of variables and
factors involved. Based on the available information, the consultant felt that four benefits could be
quantified with sufficient confidence to inform the Fort Collins analysis: building valuation, occupant
health and productivity, economic health, and carbon reduction. This appendix provides information
about data sources and how the information they provided was applied to estimate each of these
benefits.
The studies used in this analysis represent often-referenced sources (e.g. , by U. S . Green Building
Council) and/or sources referred through the green amendment development project (by members of the
advisory committees and other stakeholders) on green building benefits and costs. They do not represent
an exhaustive literature search.
Because there are many uncertainties when applying the research to the green amendments proposal,
conservative assumptions have been made and the numbers generated through this approach should be
considered "order-of-magnitude" in nature.
1. Building Valuation
Two green building studies were used to inform the residential valuation analysis:
• ICF Incorporated (Nevin and Watson), Evidence of Rational Market Values for Home Energy
Efficiency, The Appraisal Journal, October 1998 .
• Earth Advantage Institute (Ann Griffin), Certified Home Performance: Assessing the Market
Impacts of Third-Party Certification on Residential Properties, May 2009.
The first study' s findings indicate a $20 increase in market value for every $ 1 in annual energy savings.
The second study reports three to five percent higher selling price for homes with a third-party
sustainable certification such as ENERGY STAR and LEED for Homes.
For the Fort Collins analysis, the method in the first study was used to calculate a one percent increase
in home value based on the estimated utility savings. This method is more conservative than the second
study and also reflects that no third-party certification is associated with the proposed amendments.
Two green building studies were used to inform the commercial building valuation analysis:
• McGraw-Hill - Business Benefits of Green Buildings SmartMarket Report: Building & Occupant
Performance Driving Green Investment in Existing Commercial Buildings, November 2010
• University of California Energy Institute (Eichholtz, Kok, and Quigley), Doing Well by Doing Good
— Green Office Buildings, August 2006
1
ATTACHMENT 3
These studies indicate that green high-performing buildings typically have increased value in the
marketplace compared with their conventionally built counterparts. According to the first study, green
buildings have a five percent higher valuation and occupancy rates, and one percent higher rental
incomes. The second study reports two percent higher rents; when adjusted for occupancy-level, this
translates into six percent higher effective rents.
Because the proposed green amendments do not address all of the green attributes in the buildings
studied and the regulatory approach does not include visible building labels, a conservative value of 1 %
was chosen to represent the increase in valuation.
Building valuation benefits tabulated in the benefit cost report were derived by applying the one percent
increase to the values used for the prototype buildings, multiplied by numbers of projected new
buildings. These benefits are considered one-time occurrences.
2. Occupant Health and Productivity
These studies were used to value occupant health and productivity:
• US Green Building Council (Gregory Kats), Greening America 's Schools — Costs and Benefits,
October 2006.
• Gregory Kats, The Costs and Financial Benefits of Green Buildings - A Report to California 's
Sustainable Building Task Force, October 2003 .
Overall, the studies were conducted on buildings that featured indoor air quality improvements related
to ventilation and controls for temperature and pollutant sources.
The first study, for schools, was used to estimate the health benefits for the residential sector. The study
indicates 20-year net present value (NPV) savings of $ 8 per square foot for reducing asthma and
colds/flu. A conservative 10% proration of this benchmark, multiplied by an estimated 35 square feet
per child (in a school setting), was used to calculate a dollar-per-person value that could be applied to
the prototype home. This approach yields a 20-year NPV benefit of $28 per person, $ 112 per home, for
health cost savings.
The second study, which indicates 20-year NPV productivity benefits of $37 to $55 per square foot for
LEED-certified buildings, was used to value increased productivity in commercial buildings. Because
the proposed green amendments are not as extensive as LEED requirements, a conservative 10%
proration to the average of the study findings, or $4.61 per square foot, was used. This rate per square
foot was then multiplied by the prototype commercial building size to estimate a 20-year NPV of $6,900
per building for productivity gains.
3. Economic Health
The economic health benefits of the code amendments were based on information provided by the
City' s Economic Advisor, Josh Birks, relative to a model used to assess the Mason Corridor. This
information included multipliers for direct, indirect and induced benefits. Direct benefits represent the
actual amount spent or invested. Indirect benefits (incremental) are defined in this model as increases in
economic health, by local suppliers, necessary to support local impact. Induced benefits are defined as
impacts on all local industries from wages derived from both direct and indirect impacts. The total
multiplier for all three benefits is 1 . 5 , based on 1 .0 for direct and 0 . 5 for indirect and induced.
2
ATTACHMENT 3
To ensure a conservative approach, only multipliers for indirect and induced benefits were used to value
the local economic benefits of the incremental cost to implement the proposed amendments for new
buildings (both commercial and residential). The result is an economic benefit of $2,000 per home and
$31 ,000 per commercial building. These benefits are considered one-time occurrences.
4. Carbon Reduction
Projected utility savings (electricity and natural gas) were used to calculate carbon dioxide equivalent
(COze) emissions reductions for both residential and commercial buildings. Point Carbon' s report,
Carbon 2010 Return of the Sovereign, March 2010, indicates an expected carbon price of $ 10 to $20 per
metric ton if trading is instituted in the United States. The Stern Review of the Economics of Climate
Change, March 2007, estimates the social cost of carbon to be $85 per metric ton.
Based on these two reports, $20 per ton, or the high end of the range in the Point Carbon approach, was
used to assign value to the carbon reduction benefit of utility savings. The annual value was then
converted to a 20-year NPV.
3
ATTACHMENT 4
utilities
City of eleotria - sturmwater • wastewater water
700 Wood Street
Fort Collins PO Box580
Fort Collins, CO 80522
970.221 ,6700
/0000 970.221 .6619 - fax
970.224.6003 - TDD
utilities ®/cgov.com
icgov.cowulditles
Memorandum
DATE: December 17, 2010
TO : Mayor and City Council Members
THRU : Darin Atteberry, City Manager
Kevin Gertig, Acting Utilities Executive Directoic
FROM : Patty Bigner, Utilities Customer and Employee Relations Manager fig
John Phelan, Utilities Energy Services Manager
Felix Lee, Utilities Green Building Codes Project Manager—::5r ^ � L
Steve Dush, Community and Neighborhood Services Director N7
RE : Work Session Summary — December 14, 2010
Update on Green Building Program and Proposed Building Code Green
Amendments
On December 14, 2010, City Council held a Work Session regarding an update on the
development of the Green Building Program and proposed building code green amendments. All
Council members were present. Staff members making presentations and answering questions
were Utilities staff Brian Janonis, John Phelan, Doug Swartz, Gary Schroeder, and Felix Lee;
Community Development and Neighborhood Services (CDNS) staff members Steve Dush and
Mike Gebo ; and, Deputy City Manager Diane Jones.
There was extensive discussion and many clarification questions regarding the information
presented. Each Councilmember provided their individual perspective and feedback. Council
was generally supportive of the objectives of green building, and a majority supported moving
ahead with the approach proposed by staff as specified below:
• Residential and Commercial amendment packages. A majority of Council supported the
proposed packages of building code green amendments and requested staff provide a more
detailed benefit and cost analysis.
• Options. Several Council members requested that the four green amendment options be further
developed , including detailed costs and benefits for each option. Several Council members also
requested staff to consider voluntary, incentive-based approaches as well as regulatory approaches
for implementing the options.
• Timeline. Council supports a March 2011 adoption date for building code green amendments and
a January 2012 implementation date for most provisions.
• Electrically heated building requirements. Council members requested staff to prepare the
proposed specifications for electrically heated buildings as soon as feasible.
ATTACHMENT 4
Fort Collins
• Implementation resources. Council has already approved funding to support additional staffing
resources in the Building Division to administer and enforce the proposed building code green
amendments.
• Green Building Program. Council encouraged staff to move ahead with developing voluntary
elements of an integrated Green Building Program to accelerate green building in Fort Collins.
Next Steps
• Develop building code green amendment ordinance language for the proposed residential and
commercial packages for City Council adoption on March 1 and March 22, 2011 .
• Deliver to Council a more detailed benefits and costs analysis for the building code green
amendments including a review/analysis of potential impacts .
• Deliver to Council information regarding development trends in Fort Collins, our region and
nationally.
• Develop and deliver to Council a clearer description of the four green amendment options,
including benefits and costs.
• Provide a list of green building amendment provisions that were considered by staff and the
technical review committees but were not included in the recommended packages.
• Review proposed ordinance with appropriate City boards and commissions, seeking their
recommendations for adoption, in January and February 2011 .
• Continue Green Building Program development, including building code green amendment
I
mplementation activities (training, education, etc.) and voluntary program elements.
ATTACHMENT 5
Membership of Stakeholder Advisory Committees
Commercial Technical Review Advisory Committee
Member Company Expertise
Aller Lingle Massey
Brad Massey Architects PC Architect
Steve Steinbicker Architecture West Architect
Beaudin-Gauze Consulting
Corey Rhodes Engineers Mechanical engineer
Rick Coen Sun Electric Systems Renewable energy
Gino Campana Bellisimo Inc. Construction management
Angela Milewski BHA Design Landscape design/LEED
Josh Guernsey/ Peter
Kast Brinkman Partners Real estate
Doug Dohn Dohn Construction Construction management
Greg Fisher Fisher Architecture Architect
Institute for the Built
Josie Plaut Environment LEED/green building
Green building/facility
Pete Hall PSD management
Starwood Construction
Sandy Willison Mgmt Construction management
HVAC systems /facility
Matt Horner Trane management
Building Officials*
Jurisdiction Representative
Larimer County Tom Garton
Safe Built Russ Weber
City of Longmont Chris Allison
City of Fort Collins Russell Hovland
* Building Officials were invited to attend both residential and commercial TRAC
meetings.
I of 4
ATTACHMENT 5
Residential Technical Review Advisory Committee
Member Company Expertise
Jeff Schneider Armstead Construction Builder / new + remodel
Gil Paben Aspen Construction Builder / new + remodel,
radon mitigation contractor
Rob Sabin Aspen Homes of Colorado Builder / production homes
Energy efficiency +
Alex Blackmer The Atmosphere Conservancy renewable energy, custom
builder
Chadrick Martinez Fort Collins Housing Authority Affordable housing developer
and owner
Dana McBride Dana McBride Custom Homes Architect and builder /
custom homes
Michelle Jacobs Fort Collins Board of Realtors Real estate
Bob Hand / John Habitat for Humanity Affordable housing builder
Sailer
Gordon Winner HighCraft Builders Remodel contractor
Laura Barrett / Institute for the Built Green building education and
Mark Benjamin Environment consulting (students)
Larry Buckendorf J&J Construction of Northern Developer and builder /
Colorado production homes
Michael Bello Larkspur Homes, LLC Builder and project manager
Rob Ross Merten Design Studio Project architect
Neil Kaufman National Center for Deconstruction and training
Craftsmanship
Dennis Sovick Sovick Design Builders Designer and builder / custom
homes + remodel
Lara Williams The Green Team Real Estate Real estate
James Mitchell The Group Real Estate Real estate
Linda Ripley Vaught-Frye-Ripley Design Master planning + landscape
architecture
Terence Hoaglund Vignette Studio Developer / landscape
architect / designer / builder
2 of 4
ATTACHMENT 5
Green Building Program Advisory Committee
Organization/Company Representative
American Institute of Architects/Colorado North Fred Roberts
Appraisal Institute/Colorado Chapter Marge Moore
Community for Sustainable Energy Andrew Michler
CSU-Institute for the Built Environment Brian Dunbar
Fort Collins Board of Realtors Todd Gilchrist
Fort Collins Chamber of Commerce Ann Hutchinson
Fort Collins Housing Authority Mike Salza
Fort Collins Sustainability Group Andrew Michler
International Facilities Management Association Matt Horner
Northern CO Commercial Association of Realtors Peter Kast / Joshua Guernsey
Home Builders Association of Northern CO Bob Peterson
Northern Colorado Renewable Energy Society John Fassler
Poudre School District Mike Spearnak
Rocky Mountain Sustainable Living Association Kellie Falbo
Sierra Club/Poudre Canyon Group Shane C Miller
USGBC-Northern CO branch Bill Hofinann
Individuals
Everitt Companies David Everitt
Sage2 Bill Franzen
Involved citizen Mark Wanger
Boards and Commissions
Affordable Housing Board Mike Sollenberger
Air Quality Advisory Board Rich Fisher
Building Review Board Alan Cram
Commission on Disability Mike Devereaux
Economic Advisory Commission Stu MacMillan
Electric Board John Graham
Landmark Preservation Commission Bud Frick
Natural Resources Advisory Board Glen Colton
Planning & Zoning Board Andy Smith
Water Board Phil Phelan
City Management
Neighborhood & Building Services Steve Dush
Economic Development Mike Freeman
3 of 4
ATTACHMENT 5
City Manager's Office Helen Migchelbrink
Natural Resources John Stokes
Fort Collins Utilities Patty Bigner
Fort Collins Utilities - Light & Power Steve Catanach
Fort Collins Utilities - Water Jon Haukaas
Fort Collins Utilities - Water Kevin Gertig
Advance Planning Joe Frank
Operations Services Ken Mannon
Neighborhood and Building Services Mike Gebo
4 of 4
ATTACHMENT 6
Green Building Practices Considered but Not Included
in Proposed Amendment Package
The residential list does not include numerous additional National Green Building Standard
green building practices that were initially coarsely screened in the early review process ; it
focuses instead on the development of prescriptive amendments beginning July 2010 .
The commercial list is more inclusive , reflecting the wide range of practices embodied in the
International Green Construction Code .
Residential Practices Not Included
GB Description Intent Reason not
Practice included
Continuous R-5 rigid insulated sheathing OR
Structural insulated panel systems OR
Insulated concrete forms OR
Double wall framing OR 2009 IRC requires some
Reduce Advanced framing including : Increase thermal of these details . Rely on
thermal • All corners: R-6 insulated , 3 stud max AND integrity of the education and training to
bridging • All headers : R-5 above windows + doors AND building envelope move this further.
• Framing limited at all windows + doors AND
• All int/ext wall intersections insulated AND
• Stud spacing : 16" for 2x4, 24" for 2x6 framing ,
no more than 5% undocumented studs
• Decrease solar The typical high-
gain contribution performance glazing now
to summer cooling in use has about half the
Maximum % of un-shaded glazing area to floor load . solar transmittance of the
Solar control area , for E through S through W elevations. clear glass that used to
• Increase prevail . The penalty of
summertime larger, un-shaded glass
thermal comfort areas has been
significantly reduced .
High cost increment
because these motors
are typically only
Heating + packaged with furnaces
cooling with other high-end
systems : Air handlers must incorporate efficient (DC) Save energy and features . In current
efficient air blower motors reduce peak proposal, the efficient
handler electrical demand motors are required only
blower motor when the air handler is
used to move ventilation
air, meaning many more
hours of operation than
for heating/cooling .
Properly Goal : get right The HVAC
designed amount of air to commissioning
and Visual check by building inspectors to identify each register, amendment will measure
installed , and eliminate common duct installation maintain the installed performance
tight problems . conditioned air and provide the feedback
ductwork temp throughout needed to improve duct
system installation practices.
1 of 9
ATTACHMENT 6
GB Description Intent Reason not
Practice included
Irrigation systems are
seldom installed at time
High Reduce water of building construction
efficiency Landscape irrigation systems must be low consumption for and have not been
volume/high efficiency systems approved by the landscape regulated through the
irrigation irrigation .
automatic City. building permit process .
This opportunity is being
pursued through other
channels.
Landscape design has
not been regulated
Reduced turf Establish limits for maximum proportion of a yard Reduce landscape through the building
area that could be planted as turf. irrigation water permit process. This
use opportunity is being
pursued through other
channels.
Improve indoor air Most expensive low-VOC
Low-VOC quality for item considered .
prefabricated Prefabricated interior cabinetry must meet CDPH construction Standards are in flux.
cabinetry 01350 standard workers and Address via education for
occupants now.
Commercial Practices Not Included
The first column includes references to sections in the International Green Construction
Code .
GB Practice Description / Intent Reason not included
502.2 Post constr. waste Storage areas provided in bldgs. for Difficult to define/enforce.
recycling recycling Insignificant impact.
502.3 Storage of lamps , Storage areas provided for items requiring No significant impact
batteries & electronics special disposal
503.2 Material selection Stipulates 55% Total materials in each bldg . Difficult to track, hard to tie to permit
project must be a combination of following or C .O . Makes more sense as
materials practices to be incentivized .
503.2 . 1 Used materials See 503. 1 see 503 .2
503.2 .2 Recycled content At least 25% post- & pre-consumer material see 503 .2
building materials
503.2 .3. Recyclable building materials manufactured to be recycled with See 503 .2 . Also, difficult to define
materials . at least 30% recovery rate the recyclability of a material .
503.2 .4 Bio-based materials 50% bio-based content or certified wood see 503 .2
503.2 .5 Indigenous Materials from 500 mi . radius see 503 .2
Materials
503.3 Environmental 75% of total materials must comply with Difficult if not impossible to track that
stewardship requirements for this section . Provide source of production meets clean
equivalent. requirements to the US or air, water, resource conservation
country produced , harvested , processed standards.
manuf. Whichever stricter: clean air; clean
water; resource conservation ; noise control
504. 1 Low mercury lamps Comply with 504.2 or 504.3, not more than Intent already met by most
5 mg of mercury/lamp manufacturers . Difficult to enforce
from a documentation aspect.
2 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
505. 1 Building service life To be included in constr. Document — sets Challenging and onerous to
plan design service life not less than 60 years document. Components as a
except BSLP of 25 years is permitted when system are more important than the
approved by code official individual materials . Good materials
assembled poorly could have a very
short service life and vice versa.
505. 1 . 1 Service life of core, See Table 505 . 1 . 1 See 505. 1
shell and site hardscape
components
505. 1 .2 Interior Requires plan to accommodate See 505. 1
reconfiguration , dismount. , & disassembly —
part of BSL plan
506. 1 Storage and handling Stored onsite must comply With Standard practice - Minimal impact
of materials manufacturer recommendation for storage
and handling — to prevent moisture damage
during constr.
506.2 Constr. phase Protect materials from moisture damage Standard practice - Minimal impact
moisture control
507.2 Waste management materials diverted from landfill Increased by Intent covered by construction waste
project elective 20% management practice
507.3 Material selection 50% , 80% of materials meet criteria of sec. This increases the requirement of
project electives 503 the base practice (503 .2), which
wasn't accepted.
507.4 Multi-story building Credit for reducing footprint by 45% , 70% There are much larger factors
project electives through stacking stories. driving whether or not a multi-story
project is built.
507.5 Reduced building Reduce floor-to-floor height Based on C-TRAC feedback, these
volume project elective heights would be too restrictive.
This could also limit daylighting
possibilities.
507.6 Service life project Extended service life beyond 505. 1 Base practice (505. 1 ) was not
electives accepted . This goes beyond that
requirement.
507.7 Moisture control Protect materials from moisture damage This is a standard building practice.
project elective
602. 1 TANEU Choose TANEU level TANEU too difficult to understand
and calculate (removed from ver. 2
of IGCC
602.3 Compliance Paths Bldgs. > 25 kSF use performance-based Not applicable to GB prescriptive
compliance , others can use Prescriptive or amendments
Performance
602.3 . 1 Prescriptive-base TANEU-based requirement
compliance
602.3 .2 Performance-based TANEU-based requirement
compliance
602.4 Documentation & Cannot exceed energy use of existing bld . Too restrictive . Requires
verification for exist. Bldgs . After alterations . measurement-based 3rd-party
verification . Significant additional
expense for builder. Could hold up
C. O.
603. 1 Energy use, peak methods for calculating energy, demand , & Based on TANEU . Difficult to
demand , & Co2e CO2e understand .
603. 1 . 1 Annual Energy Use Energy use converted to consistent units , Unconventional conversions, difficult
TANEU defined . to understand .
3 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
603. 1 .2 Peak energy proposed design demand < 0.90 times Would have to model a base case .
demand demand of reference design Uncertainty in modeling . Difficult to
prove until after the fact.
603. 1 .3 CO2e emissions re. Confusing calculations . Better to
electricity reference energy savings in kWh
and Therms and make conversion
from that.
603. 1 .4 CO2e emissions re. Doesn't fit in context of other CO2
non-renewable fuels reporting .
603.3 Calculation Per 506 .5 of IECC Does not add any significant value
Procedures to IECC 2009 requirements .
603.4 Qualified software Per 506 .6 of IECC Covered in IECC 2009
603.5 Design professional registered design professional in charge of Design professional certification is
for energy simulation energy simulation not clear.
604. 1 Buildings with tenants Metering collected for entire bldg . AND Electric metering already required .
each tenant. Tenant access to utility info. Water metering would be too
expensive for the value realized .
604.2 Intent Verify ongoing compliance with sections Not really a GB practice - just
602 and 603 - relates to commissioning clarifying intent
604.4 Energy type metering Bldgs. provided w/ capability to determine Smart meters will provide this
energy use and peak demand for all fuel
types (604 .4. 1 -604 .4.7)
604.5 Energy load type sub Bldgs. w/ 25,000 sq .ft. total bldg . floor area Added expense. No guarantee sub-
metering and larger all energy types must be sub- metered data will be maintained or
metered used.
604.5. 1 Bldgs. <25,000 Designed for future installation of sub- 604. 3 captures the spirit of this
sq .ft. metering system
604.6 Minimum energy Meters and sub meters must be connected Relates to sub-metering
measurement and to data management system requirements above
verification
604.6. 1 Annual emissions Data management system provides data Billing kWh and Therm data will
necessary to calculate annual CO2e provide the same information .
emissions . Mechanism not in place for CO2e
reporting .
604.7 Energy Display Permanent, readily accessible and visible Added expense that requires
display of energy use maintenance . Needs to be set up
properly. It has not been straight
forward to implement these on
existing projects that wanted to.
605 Automated Demand This has been very difficult to
Response infrastructure implement on a voluntary basis. Is
out of scope for code - issues with
design , implementation , verification ,
monitoring , and control.
605. 1 Establishing Bldg . control system integrated with Same as 605
infrastructure automated demand response relay
605.2 Software clients Demand response software clients Same as 605
communicate with demand response
automation server
605.3 HVAC systems System capable of reducing bldg . peak This capability is available at some
cooling HVAC demand by at least 25% level with Utilities' Load
Management Program . Smart grid
will enable enhanced features.
605.3 . 1 Rebound Avoidance Strategy w/ gradual return to normal HVAC Same as 605
operation
4 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
605.4 Lighting reduce total connected power of lighting in Can be component of voluntary
group B office spaces by 30% Load Management Program
605.5 Bldg . component reduce aggregate electric loads from Can be component of voluntary
specific strategies miscellaneous bldg . equipment by 25% Load Management Program
607. 1 Prescriptive Comply with IECC requirements and Already in adopted IECC 2009
Compliance provisions of this section for mechanical
systems
607.2 HVAC equipment Comply with federal standards/IECC No change from base requirements
607.3 Ventilation Provided in accordance with Chapter 4 of No change from base requirements
the International Mechanical Code
607.4 Duct and plenum Air ducts, plenums, air handlers and filter No change from base requirements
insulation , sealing and boxes are insulated and sealed in
testing accordance with IECC.
607.4 . 1 Testing System leak-testing . Rate of air leakage Most large duct systems are already
shall be 156.0 as determined by IECC tested as required by IECC 2009 .
equation 5-2. This adds lower pressure ducts,
which are a much smaller
percentage of leak issues .
607.5 HVAC piping Piping systems are insulated to reduce heat Piping insulation already required in
insulation gain/loss IECC. This just increases the
requirement. Codes will be
progressing over time.
607.6 Economizers Economizer on systems >54,000 Btu/h (4 .5 Already required in IECC 2009,
tons) where the requirement is also
simpler to understand .
607.7 Variable air volume VAV required for fans with motors 1 .0 hp Looking at just the motors does not
(VAV) fan control and greater consider the balance of the HVAC
system (VAV boxes, etc. ).
Considered this from building-size
perspective, but it is largely already
covered in the existing codes
607.8 Kitchen Exhaust Meet the provisions of the IECC with Does not apply to all buildings.
Systems qualifications Difficult to enforce, but this may
make sense to implement in future.
607.9 Laboratory exhaust Meet the provisions of the IECC Most new labs have well designed
systems exhausts stems .
608. 1 Prescriptive Meet the provisions of the IECC and No change from base requirements
Compliance Provisions for this section
608.2 Service water heating Equipment shall comply with federal No change from base requirements
equip . performance standards and IECC
608.3 Pools, hot tubs and Meet the efficiency requirements of IECC No change from base requirements
spas
608.3. 1 Pools in conditioned 25% of annual energy consumption and Very expensive to meet this
space 50% peak design space HVAC shall be met requirement. Very long payback,
by renewable energy or heat recovery both financially and for embodied
systems. energy
608.4 Snowmelt Systems Comply w/ IECC + get 25% of energy from This could be expensive to meet for
renewables (50% for electric systems) a system that is rarely on . Good
controls are more important.
Minimal community impact.
608.5 Rough-ins for future Provide for future installation of solar hot C-TRAC felt this was not a good
solar hot water water system investment. Most buildings can
accommodate solar and it is difficult
to plan for futures stems .
5 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
608.6 Waste waster energy Recover heat from waste water for Fairly large expense for return on
recovery system incoming system. investment. Revisit this in the
future.
608.7 Service water heating Thermal insulation for service water piping . This is largely covered in IECC
piping insulation
608.8 Circulating hot water Circulating systems must have automatic or This is largely covered in IECC
systems accessible, manual controls to turn off the
system when not in use.
609.4 .2 Exterior lighting and Lighting of building facades, signage, and Too controversial to require
signage shutoff landscape is controlled by time switch and businesses to turn off signs .
is shut off after one hour after building
closing or after midnight.
609.5 Automatic daylight Automatic daylight controls and minimum IECC 2009 requires automatic
controls fenestration provided . daylighting controls in daylit zones.
609.6 Plug Load Controls Use of occupancy sensors and time switch This is complex. There is a danger
controls to reduce energy use of turning off computers or other
important loads.
609.7 Fuel Gas lighting Count fuel gas lighting in lighting power minimal impact
system calculations
609.8 Electrical system efficiency for transformers, voltage drop in The transformer efficiencies listed
efficiency feeders are the same as the national
standards.
609.9 Exterior lighting Comply with IECC Covered in IECC 2009
609. 10 Verification of lamps Confirmation of compliance with IECC prior This is an unnecessary burden on
and ballasts to C.O . inspectors for something that should
be handled during commissioning
610.2 Permanent Elevators, escalators, food service equip . , Adds unnecessary complexity to
appliances and equipment conveyors inspection process . Some of this
equipment is not attached to the
building
610.3 Portable appliances Requires Energy Star portable appliances - Independent appliances don't fit with
and equipment humidifiers, room AC, washer/dryers, the building code. Difficult to
consumer electronics, and office machines . regulate .
611 . 1 Renewable energy Requires on-site renewables and/or RECs. Too expensive to require at this
systems requirements Performance = 2% or greater, Prescriptive time . Better addressed through
= 2% or greater or rated at . 5 W/SF, 4% incentives/recognition programs .
from RECS
611 .2 Solar photovoltaic PV provides at least 2% of the total See 611 . 1
systems estimated annual electric energy
consumption of the building or collective
bldgs. on a site.
611 .3 Wind Energy systems Wind energy systems provide at least 2% of Not adequate average wind speed in
the total estimated annual electric energy Fort Collins for this.
consumption of the building or collective
bldgs. on a site.
611 .4 Solar water heating At least 10% of the bldgs. annual estimated Seemed like too much to require PV
equipment hot water energy usage. & solar hot water.
611 .5 Renewable energy Systems are metered and monitored to See 611 . 1
system performance assess power generation .
monitoring and metering
6 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
612. 1 Mechanical systems Prior to passing the final mechanical Covered in commissioning
commissioning and inspection a registered design professional requirement
completion requirements must provide evidence of system
commissioning . Cx plan & TAB
612.2 Lighting and Electrical Prior to issuance of the C .O . a registered Covered in commissioning
systems commissioning and design professional must provide evidence requirement
completion requirements of lighting and electrical systems
commissioning
613.2 Post C.O . TANEU , Ongoing TANEU , energy demand and Goes beyond practices that were not
energy demand , and CO2e CO2e emissions reporting is required . accepted
emissions reporting
613.3 TANEU reduction Gain elective credit for lowering the number Goes beyond practices that were not
project electives of TANEU points below the maximum value accepted
allowed
613.4 Building thermal Language and requirement unclear. Dropped from second version of
envelope systems project IGCC
elective.
613.5 Mechanical systems Elective credit for efficient mechanical Adequately covered in IECC
project elective systems
613.6 Passive design Achieve 40% of the energy conserved in Difficult to regulate due to varied
project electives the proposed design . design options.
IgCC 702.2 - Leakage limits Tub spout leakage from combination Minor impact
on combination tub/shower tub/shower valves not more than 0 . 1 gpm .
valves.
IgCC 702 .8 - Efficient hot Water in piping between hot water source C-TRAC expressed concerns stating
water distribution system. and hot water outlet is 87 oz. maximum . that it would be very difficult to meet
this requirement.
ASHRAE 189 . 1 Section Hydrozoning of automatic irrigation systems Defer to Land Use Code (LUC)
6 .3. 1 .2 - Water conserving to water different plant materials such as
irrigation design . turf grass versus shrubs required .
Landscaping sprinklers not permitted to
spray water directly on building or within 3
ft. of a building
ASHRAE 189 . 1 ; Section Landscape sprinklers controlled by smart Defer to LUC
6 .3. 1 .3 - Controlled controllers that uses evapotranspiration rate
landscape sprinklers. ET and weather data to adjust irrigation
schedules
IgCC 702 . 14 , 702 . 15, At least 50% of rinse water is reused for To be considered as addition to
702. 16 - Efficient vehicle washing . Self-service spray wands limited Muni code
wash facilities. to a maximum of 3 gpm .
ASHRAE 189 . 1 6.3 .3. 1 ; Measurement devices with remote Sub-metering recommended for strip
IgCC 705.2 - Water communication capability shall be provided malls and 2, 3, & 4-plexes - add to
consumption management. to collect water consumption data for utility water metering standards in
domestic supply to the building . next update of Muni code
Potable and reclaimed water entering the
building project—monitored or sub-
metered .
Rentals in excess of 50,000 sq ft. separate
sub meters.
ASHRAE 189 . 1 6.4 .2.2 - ENERGY STAR dishwashers; Appliances not part of building code
Commercial Food Service boilerless/connectionless food steamers no
Operations Water Use more than 2 .0 gph ; ENERGY STAR air-
Reduction . cooled ice machines.
7 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
IgCC 801 .2 - Indoor Air A plan that addresses procedures used Focused code on a few specific
Quality ( IAQ) Management during design and construction of a building items
Plan with respect to IAQ to ensure compliance
with sections 802 and 805.
IgCC 805 - Asbestos use The use and installation of asbestos in Difficult to impossible to verify
control building construction is prohibited .
IgCC 808, ASHRAE 189 . 1 , Prescriptive and performance paths for Quality daylighting design is difficult
LEED 2009 - Daylighting daylighting to put into code. Needs to be
incentive-based
1003.2 . 1 - HVAC 1 . Fix non-functioning t-stats Concern from C-TRAC of added
2 . Seal leaking ducts burden to alterations
3. Fix OA dampers, controls , & linkages
4. Fix HW & steam leaks, traps, valves, &
controls
5. Fix CHW leaks
1003.2 .2 - Service water 1 . DHW < 110'F at point of use May be unnecessarily low for some
systems 2 . no leaks in pipes applications .
1003.2 .3 - Motor-driven No leaks in compressed air or pumped Need specific metric for leaks.
equipment water systems Nearly impossible to eliminate all
leaks .
1003.3 .2 - Metering devices Provide at least one metering device for Minimal impact and difficult to
electricity, water, natural gas, lighting , implement
motors, chiller, cooling , economizer, boiler,
process, irrigation .
1003.3 .3 - HVAC 1 . Time control Concern from C-TRAC of added
2 . OA economizers for >6- 1 /4 tons cost and time to alterations . Issues
3 . HVAC piping and duct insulated per code can be identified in energy
4 . Tune furnace combustion units assessment.
5. Boilers - clean & tune
6. Boilers - equip with outdoor air lock
7. Chiller - clean and tune
8. 5-yr. phase out plan for CFC refrigerants
9. BAS installed if equipment has capability
1003.3 .4 - Service water 1 . R-6 insulation Concern from C-TRAC of added
systems 2 . Insulate pipes per code cost and time to alterations . Issues
3. Seismic requirements can be identified in energy
4. Time clock on circulation systems assessment.
5. Fixture flow rates per code
1003.3 .5 - Lighting Per IECC Concern from C-TRAC of added
cost and time to alterations . Issues
can be identified in energy
assessment.
1003.3 .6 - Commercial 1 . Cleaned & tuned for efficiency Concern from C-TRAC of added
refrigeration 2 . Cases equipped with doors or strip cost and time to alterations . Issues
curtains can be identified in energy
assessment.
8 of 9
ATTACHMENT 6
GB Practice Description / Intent Reason not included
1003.3 .7 - Motor-driven Maintenance Concern from C-TRAC of added
equipment cost and time to alterations . Issues
can be identified in energy
assessment.
1003.3 .8 - Swimming pools 1 . Equip with cover Concern from C-TRAC of added
& spas 2. Time clock control for recirc. Pumps cost and time to alterations . Issues
3. Heaters tuned for efficiency can be identified in energy
assessment.
1003.3 .9 - Attic insulation Bring up to code if accessible Concern from C-TRAC of added
cost and time to alterations . Issues
can be identified in energy
assessment.
9 of 9
ATTACHMENT 7
Fort Collins New Single Family Home Size, 2005=2010
Data provided by Fort Collins Building Department
Number of New Homes
Square footage 2005 2006 2007 2008 2009 2010
0-999 3 1 1 2 1 0
11000- 15999 243 196 221 137 76 111
27000-21999 359 188 102 98 58 50
32000-31999 61 38 29 8 3 4
4 , 000-41999 5 5 5 2 2 4
52000-51999 3 1 1 1 0 1
61000-65999 1 2 0 0 0 0
Average size 2240 2161 2005 2038 1972 1980
Total # homes 675 431 359 248 140 170
Total # homes
3, 000 sf and larger 70 46 35 11 5 9
Average New SF Home Size , FC 2005 =2010
3000
2500
2240
0 2161
0
2005 2038
c 1972 1980
2000
0
w
=a
c
0
a
R 1500
a
Q
1000
2005 2006 2007 2008 2009 2010
ATTACHMENT 7
New SF Homes Size Distribution , FC 2005 =2010
400
M < 1000 sf
■ 1000- 1999 sf
❑ 2000-2999 sf
300 ❑ 3000-3999 sf
■ 4000-4999 sf
y M 5000-5999 sf
A
■ 6000-6999 sf
Q 200
a
E
0
z
100
0
2005 2006 2007 2008 2009 2010
New Homes 3 , 000 Sq Ft and Larger, FC 2005 =2010
70
60
50
❑ 3000-3999 sf
40 ■ 4000-4999 sf
o-
❑ 5000-5999 sf
30
E ■ 6000-6999 sf
z
20
10
0
Flm� 17-ism
2005 2006 2007 2008 2009 2010
ATTACHMENT 8
Development Trends
2005 to 2010
The following information is intended to give a quick overview of the construction and inspection activity
that has occurred in Fort Collins , as well as other Northern Colorado jurisdictions , over the past five years .
It includes data on total number of permits issued , residential construction , commercial construction and
building inspections . It also touches very briefly on national construction trends .
Total Permits Issued
Fort Collins saw a steady decline in number of permits issued from 2005-2008 . The numbers started to
rebound slightly in 2009 and continued in 2010 . 2010 total permits issued were 13% below 2005 totals .
Fort Collins Building Permits - 2005-2010
All Permits
7500
6750
6000
5250
4500
3750 ■ All Permits
3000
2250 -
1500
750
0
2005 2006 2007 2008 2009 2010
Year
Fort Collins Building Permit Valuations ($M )
2005 - 2010
350
300 $272
250
�. 200
c 150 116
E 100
Q 50
0
2005 2006 2007 2008 2009 2010
Year
- lof5 -
ATTACHMENT 8
Although overall permit issuance has remained quite high , the types and values of permits have changed
significantly. 2010 Fort Collins permit valuation was 51 % below 2005 , resulting in significantly less
revenues .
Other Northern Colorado jurisdictions , for the most part, followed the same pattern as Fort Collins , with
numbers declining from 2005 until modest increases were realized in 2009 and 2010 . Fort Collins fell in
the top two jurisdictions for total permits issued for all six years , and led in numbers two of the six years .
All Permits Issued Comparison
2005-2010
10000
8000
LM
6000
3 4000
z
2000
0 - - Itki
2005 2006 2007 2008 2009 2010
Year
❑ Broomfield ■ Fort Collins ❑ Greeley ❑ Larimer County
■ Longmont ❑ Loveland ■ Thornton ❑ Westminster
Residential Construction
New construction for both residential and commercial projects has seen the largest declines since 2005 ,
declining steadily through 2009, with a slight rebound in 2010 .
Fort Collins Residential Building Permits
2005 - 2010
1400
1200
a 1000 ❑ 2005
v
■ 2006
N 800 -
w ❑ 2007
600 ■ 2008
E ■ 2009
Z 400 ❑ 2010
200 - Ffi
0
New Residential Dowelling Units Additions/Alterations Miscellaneous
Type of Permit
Total 2010 permits issued for new residential construction were 76% below 2005 totals . Dwelling units
- 2 of 5 -
ATTACHMENT 8
have followed suit, with 2010 totals 73% below 2005 totals . In contrast, residential additions/alterations
have stayed quite strong ; 2010 totals are only 4% below 2005 totals.
Other Northern Colorado jurisdictions , for the most part, followed the same pattern as Fort Collins for new
construction , with numbers declining from 2005 until slight increases were realized in 2010 . Fort Collins
fell in the top four jurisdictions for all six years . Results for residential alterations/additions differed
amongst the communities . Fort Collins fell in the top four jurisdictions for all six year for this construction
type , and in the top two jurisdictions for three of the six years .
Residential - New Construction Comparison
2006-2010
1400
1200
L 1000
£ 800
3 600
Z 400
200
0
2005 2006 2007 2008 2009 2010
Year
❑ Broomfield ■ Fort Collins ❑ Greeley ❑ Larimer County
■ Longmont ❑ Loveland ■ Thornton o Westminster
Residential - Alteration/Addition Comparison
2005-2010
1400
1200
1000
800
3 600
Z 400
200
0 " " ,UIAA
2005 2006 2007 2008 2009 2010
Year
❑ Broomfield ■ Fort Collins ❑ Greeley ❑ Larimer County
■ Longmont ❑ Loveland ■ Thornton ❑ Westminster
- 3 of 5 -
ATTACHMENT 8
Commercial Construction
Fort Collins Commercial Building Permits
2005 - 2010
350
300
250 ❑ 2005
w
3 ■ 2006
N 200 ❑ 2007
150 ■ 2008
E ■ 2009
3
Z 100 ❑ 2010
50
0
New Commercial Additions/Alterations Miscellaneous
Type of Permit
Commercial new construction has declined steadily from 2005 through 2010 . Total 2010 permits issued
for new commercial construction were 77% below 2005 totals . In contrast, commercial
additions/alterations have stayed strong ; 2010 permit numbers are actually 20% above 2005 totals .
Commercial - New Construction Comparison
2005=2010
70 —
60
L 50
40
30
Z 20
10
0 iA 144
2005 2006 2007 2008 2009 2010
Year
* Broomfield ■ Fort Collins ❑ Greeley ❑ Larimer County
■ Longmont ❑ Loveland ■ Thornton ❑ Westminster
Other Northern Colorado jurisdictions followed similar patterns for new commercial construction , with
numbers declining from 2006 . Only two jurisdictions are seeing increases in new commercial
construction . Fort Collins fell in the top four jurisdictions for all but one of the six years .
- 4 of 5 -
ATTACHMENT 8
Commercial Addition/Alteration Comparison
2005=2010
600
500
a� 400
£ 300
z 200
100 - A
0
2005 2006 2007 2008 2009 2010
Year
❑ Broomfield ■ Fort Collins ❑ Greeley ❑ Larimer County
■ Longmont ❑ Loveland ■ Thornton ❑ Westminster
Results for commercial alterations/additions differed amongst the communities . Fort Collins fell in the top
three jurisdictions for all six years for this category.
National Trends
On a national basis , residential construction has followed the same trends . According to the Census
Bureau , during 2009 , 433 , 600 single family homes were started in the U . S . This compares to 1 . 75 million
new homes starts in 2005 . New housing starts are not yet available for 2010 .
As of April 2010 , the Mortgage Bankers Association forecast new single-family housing starts to total
556 , 000 for 2010 , 790 , 000 in 2011 and 1 , 058 , 000 in 2012 .
According to the Congressional Budget Office , the number of housing starts over the next few years will
depend on three factors :
1 . The underlying demand for new housing units ;
2 . Cyclical and financial conditions such as unemployment rates and lending standards ; and
3 . The number of excess vacant units that are available .
Commercial construction has seen severe reductions in retail centers and malls but relatively strong
growth in hotel/motels , higher education , health care and office facilities . The slowing economy has had
an impact. According to the Census Bureau , non-residential construction valuation reached $357 billion
in 2007 and $410 billion in 2008 . The adjusted number for 2010 had dropped to $302 . 7 billion .
It is anticipated that over the long term , there will be continuing demand from the health care sector for
new or remodeled properties as the percentage of Americans over age 65 continues to grow, increasing
demand for medical care .
Resources for this information :
1 . http://www . plunkettresearch . com/real %20estate%20construction %20market%20research/industr
y%20overview
2 . http://www . cbo. gov/ftpdocs/98xx/doc9885/ 11 - 17- HousingStarts . pdf
- 5 of 5 -
ATTACHMENT 9
The Business Case for Green Building
Source : U. S . Green Building Council web site,
www.us bg c.or isplUPage. aspx?CMSPaaeID=2331
1 . COMPETITIVE DIFFERENTIATOR
Green buildings with lower operating costs and better indoor environmental quality are more
attractive to a growing group of corporate, public and individual buyers. Green features will
increasingly enter into tenants' decisions about leasing space and into buyers' decisions about
purchasing properties and homes.
2. MITIGATE RISK
Green building certification can provide some measure of protection against future lawsuits through
third-party verification of measures installed to protect indoor air quality, beyond just meeting code-
required minimums. Faster permitting or special permit assistance can also be considered a type of
risk mitigation. Another risk management benefit of green buildings in the private sector is the faster
sales and leasing of such buildings, compared to similar projects in the same town. Green buildings
tend to be easier to rent and sell, because educated tenants increasingly understand their benefits.
3. ATTRACT TENANTS
Today's savvier tenants understand and are looking for the benefits that green building spaces have to
offer. The new Class A office space is green; lease-up rates for green buildings typically range from
average to 20 percent above average.
4. COST EFFECTIVE
The cost per square foot for buildings seeking LEED certification falls into the existing range of
costs for buildings not seeking LEED certification. An upfront investment of 2% in green building
design, on average, results in life cycle savings of 20% of the total construction costs — more than ten
times the initial investment. Additionally, building sale prices for energy efficient buildings are as
much as 10% higher per square foot than conventional buildings.
5. INCREASE RENTAL RATES
A 2008 CoStar Group study, which found that green buildings outperform their non-green peer assets
in key areas such as occupancy, sale price and rental rates — sometimes by wide margins. According
to the study, LEED buildings command rent premiums of $ 11 .33 per square foot over their non-
LEED peers and have 4. 1 percent higher occupancy. Rental rates in Energy Star buildings represent a
$2.40 per square foot premium over comparable non-Energy Star buildings and have 3 . 6 percent
higher occupancy.
ATTACHMENT 10
Green Building Program Community Engagement Log
Updated -2/16/2011
Event / Setting /
Date Staff Stakeholder(s) Venue Notes
Ann Hutchison , FC
ES GB Chamber of
Team , Patty Commerce and Met, at request of Michelle and Ann , to
Bigner, Jeff Michelle Jacobs , FC discuss general ideas about ramping green
9/28/2009 IScheick Board of Realtors City Hall building efforts back up .
ES GB
Team , At WB's request sent cover memo with copy
Robin of 9/30/09 GBP update memo to Council via
9/30/2009 Pierce Water Board 700 Wood St. CMO .
City Hall / regular Heads-up about evolving GBP plans
12/2/2009 FL , DS Electric Board meeting including code element
Heads-up about evolving GBP plans
including code element. Concern expressed
Natural Resources 215 N . Mason /regular about process taking too long and will the
12/16/2009 FL , GS Advisory Board meeting NGBS be watered down .
Heads-up about evolving GBP plans
including code element. Concerns about
how the NGBS would impact the limited
City Hall / regular buildable lots and interface with the IECC as
12/17/2009 IFL , DS Building Review Board meeting a mandated code .
Heads-up about evolving GBP plans
Planning and Zoning 281 N . College / work including code element. Concerns about
12/4/2009 FL , GS Board session costs to certify projects as with LEED .
Heads-up about evolving GBP plans
including code element. Some serious
concerns about adding small % cost
increase will exclude many buyers in our
market. One member very concerned
builders had not yet been included in
discussions . Staff reassured that the
Affordable Housing 281 N . College / industry will be well-represented at the table
1 /7/2010 IFL , GS Board regular meeting when the public dialogue begins .
Heads-up about evolving GBP plans
including code element. Board members
concerned about the NAHB as the primary
Air Quality Advisory 215 N . Mason /regular development organization created
12/21 /2009 FL , JP Board meeting excessively low performance stds .
ES GB City Council + citizens City hall / Work GBP development plan presented , feedback
1 /12/2020 Team , Patty (via Ch 14 and City session gathered . See Work Session Summary.
including opportunity for possible code
Commission on City Hall / regular amemdment that awards incentive points for
1 /14/2010 FL , GS Disability meeting " Universal Design " features in SF homes .
Invited by Ann Hutchison . Presented GBP
plans that had just been given the green
FC Chamber of light by Council . Lots of questions and
Commerce Legislative FC Chamber of comments , some cautionary, some
1 /15/2010 IDS , FL, JP Affairs Committee Commerce supportive .
Invited by Mike Gebo . Presented GBP plans
with additional focus on how the GB code
I-Code Review 281 N . College / element will proceed . Lots of questions and
1 /26/2010 DS , FL Committee regular meeting comments .
Page 1 of 3
ATTACHMENT 10
Patti Mason , Director Met, at request of Patti , to discuss GBP
2/5/2010 DS , FL, GS of Advocacy, USC plans and potential roles for USGBC
Citizens (including via Sustainability Plus GBP plans briefly mentioned by one of the
2/10/2010 DS Ch 14 and City web program , Residential panelists , DS available to answer questions
DS (+ Green Drinks Green Drinks monthly Brief presentation on GBP plans , DS
2/24/2010 others?) participants gathering , InSitu available to answer questions
Ken Waido received original invite to talk
Community for about Plan Fort Collins ; he asked me to join
DS (+ Ken Sustainable Energy CFORSE invitation to him to address Green Building Program .
4/8/2010 Waido ) (CFORSE ) visit at their office Few questions specifically on GBP .
Begin series of focused meetings on GB
code review and development with R-TRAC
and C-TRAC , each meeting approximately
4/28/2010 GB Team TRAC meetings begin Most at Streets Facility 2x/month .
News release re Costs
+ Benefits meeting
5/ 17/2010 and
upcoming TRAC
5/7/2010 Lisa Kokes Media + public meetings
GB Team +
Brendle Costs + Benefits Fort Collins Utilities / Proposed methodology and survey tool
5/17/2010 Group Analysis public meeting presented ; feedback solicited
Landmark Preservation
5/26/2010 JP Commission Update on Green Building Program
6/17/2010 DS & FL Water Board Update on Green Building Program
Staff available to answer questions on the
6/17/2010 FL I-Code Open House 215 Community Room GBP
Plan Fort Collins Open
6/29 & 6/30 AS , FL House Drake Centre Staffed table with information on the GBP .
Affordable Housing
7/1 /2010 FL Board Update on Green Building Program
GB Program Advisory Update on Green Building Program and
7/7/2010 GB Team Committee Meeting Planned Costs and Benefits .
Landmark Preservation Update on GB program and amendment
11 /10/2010 FL &DS Commission proposal
Downtown Update on GB program and amendment
11 /12/2010 JP , GS , DS Development Authority proposal
Planning and Zoning Update on GB program and amendment
11 /12/2010 DS Board work session proposal
Air Quality Advisory Update on GB program and amendment
11 /15/2010 FL , GS Board proposal
Economic Advisory Update on GB program and amendment
11 /17/2010 FL , JP Committee proposal
GB Program Advisory Update on GB program and amendment
11 /17/2010 ALL Staff Committee Meeting proposal
Update on GB program and amendment
11 /17/2010 IALL Staff Community Open House proposal ; Approximately 20 attendees .
Natural Resources Update on GB program and amendment
11 /17/2010 JP Advisory Board proposal
Update on GB program and amendment
11 /18/2010 DS , GS , FL Building Review Board proposal
Update on GB program and amendment
12/ 1 /2010 JP Electric Board proposal
Affordable Housing Update on GB program and amendment
12/2/2010 FL , DS Board proposal
Page 2 of 3
ATTACHMENT 10
Chamber of
Commerce Legislative Update on GB program and amendment
12/10/2010 FL , JP Committee proposal
Update on GB proposal and Benefits/Cost
1 /27/20111 FL , DS Building Review Board Summary
Update on GB proposal and Benefits/Cost
2/2/2011 JP , DS Electric Board Summary
Affordable Housing Update on GB proposal and Benefits/Cost
2/3/2011 FL , DS Board Summary
Landmark Preservation Update on GB proposal and Benefits/Cost
2/9/2011 FL , DS Commission Summary
USGBC Green and 215 N . Mason -
2/9/2011 DS , GS , FL Grub Community Room GB program overview and update
Fort Collins Board of
2/15/2011 DS , AS Realtors 110 Harvard Street GB Program Update
Economic Advisory Update on GB proposal and Benefits/Cost
2/16/2011 Scheduled Committee Summary
Natural Resources Update on GB proposal and Benefits/Cost
2/16/2011 Scheduled Advisory Board Summary
Update on GB proposal and Benefits/Cost
2/17/2011 Scheduled Water Board Summary
GB Program Advisory Update on GB proposal and Benefits/Cost
2/23/2011 Scheduled Committee Meeting Summary
Recommendation on and discussion of code
2/24/2011 IScheduled Building Review Board proposal
Air Quality Advisory Update on GB proposal and Benefits/Cost
2/28/2011 Scheduled Board Summary
Downtown Update on GB proposal and Benefits/Cost
3/10/2011 Scheduled Development Authority lSummary
Page 3 of 3
ATTACHMENT 11
Draft Affordable Housing Board Minutes
CITY OF FORT COLLINS
AFFORDABLE HOUSING BOARD
DRAFT MEETING MINUTES
281 N. College Ave.
Conference Rooms A & B
Fort Collins, Colorado
February 3 , 2011
4 : 00 — 6 : 00 PM
Chair: Ben Blonder
Staff Liaison : Ken Waido, 970-221 -6753
City Council Liaison: Lisa Poppaw
Board Members Present: Ben Blonder, Mike Sollenberger, Dan Byers, Wendy
Robinson
Board Members Absent: Karen Miller, Marie Edwards
Advance Planning Department Staff Present: Ken Waido,
Council Members Present:
Other Staff Present: Doug Swartz, FTC Utilities, Felix Lee, FTC Utilities
Others : Marilyn Heller, League of Women Voters
Meeting called order by Ben Blonder at 4 : 07 PM.
A. Open Public Discussion :
Marilyn announced a new coalition website and handed out printed copies of the site .
B. New Business.
Approval of Minutes of the January 6, 2011 Meeting.
Dan Byers made a motion to approve the January minutes, Mike Sollenberger seconded.
Passed Unanimously.
Green Building Program — Recommendation to the City Council :
Presenter Doug Swartz:
1 of 22
ATTACHMENT I
We are going to City Council for the first reading. This is an update on the refinements,
and to give you some costs that will interest you. We are asking for support of the
proposal from the Affordable Housing Advisory Board. Your recommendations will be
forwarded to the City Council. This program is intended to match with City goals . We
want to make decisions to build buildings and provide benefits to green design buildings
that are with us a long time. This is the Green Building framework to balance regulation
and voluntary measures that will move everything forward and gradually create a market
transformation. Due to a push from council we have been focusing on the code piece and
we are hopefully getting close to the voluntary part as well. Instead of proposing a new
code we are proposing to amend the existing code to make it greener. For the residential
side it is primarily the IRC . Last time we showed you specific details on the proposals.
This is a reminder of looking at amendments in terms of a systems approach trying to hit
all of the important bases . Most want a performance based approach, and a broader
approach to green as council directed. Since December we have been to council and they
gave us the green light on the same track. We have been defining the proposal with a
flushed benefit costs analysis . Felix has been spearheading the effort to translate it into
ordinance language.
The three refinements on the residential side are: Low VOC materials (cabinets
excluded), Certified tropical hardwood, and envelope requirements for electrically heated
buildings
Blonder: I didn't see anything about drywall. Since we had the Chinese issue with
drywall, I wondered how that is addressed.
Swartz: It is not addressed specifically because they felt it was an anomaly.
Blonder: It is phased out now, but it has been a big issue.
Swartz: We have exclude cabinets because of availability. We did not want to make it a
formidable barrier. We wanted to provide a lot of push on the bottom end with regulation
and pull on the top end with information. We had some options in December that we took
to council for a preliminary reaction. The only one going forward is the Certified from
some agency coming from a sustainable managed forest. We went for the one that was
the most critical eco system impact. Plus, these woods are not used typically in a low
level project.
This is a small step and similar to the previous one in that it will help get people talking
about certification and why we are concerned about upstream issues. We are pushing the
envelope requirements for insulation, electrical heat (resistance heat) and cost, not ground
force heat pumps . Electric resistance heat is a more expensive heat source.
Cost & benefits:
There are three scales that interrelate and have different cost components at each level.
This is just an overview. It has a lot of pieces to consider and it is not an exact science.
There are some assumptions and we used methodologies about how to put numbers
2 of 22
ATTACHMENT I
around this. We came at this from two directions. The component analysis (bottom up
cost and benefits) on new prototype buildings and a community scale analysis. We tried
to be conservative in the assumptions . Some things could be quantified, but others could
not. Others have ranges to use different builders. This is an overview of the numbers .
• Energy water carbon savings
• Benefits at multiple levels
• Near-term costs, recurring long-term benefits
• Initial cost increases: Residential 1 % to 2%
• Commercial 1 % to 4%
• No quick payback for owners
• Increased enforcement time + cost
• Total benefits exceed total costs.
Sollenberger: Have homes here or anywhere with new requirements been observed to
see if this works in practice or is it just theory?
Swartz: There are a lot of volunteer green building programs around the country that
incorporate a lot of the same concepts.
Sollenberger : I just wondered if this has this been tested, or has it been proven to do
what you say it will? I would hate to see something implemented that did not do what we
purport.
Swartz: I do not know of anything on the list that has not been used elsewhere for
several years.
Sollenberger : For example: a certain efficiency furnace has been tested to save energy
over other furnaces.
Swartz: A lot of this is coming from volunteer programs . These are modest steps to try to
codify based on City Council ' s direction. We are encouraging the market to go beyond
this on a volunteer basis.
Blonder: Is this coming from LEED or Energy Star?
Swartz: Some ideas are from national green building standards. We have listed several
sources. Some ideas are from Energy Star' s new version, which are addressing some
problems seen in housing here.
Blonder: The second class point increased the cost. Is that a cost of the City, or is that a
cost that will be passed on to the home builders?
Swartz: It can be either or both. In the short terms, 2011 - 12, the City is covering that
piece with the 2B tax revenue. The City Council has stated that starting in March, the
3 of 22
ATTACHMENT 11
enforcement part will be covered. The Building Department is in a position where it
needs to review costs and revenue as a whole.
Sollenberger: So, these changes raise the threshold on the existing code. Have you asked
the entry level builders what it will do to the product they are already building?
Swartz: We had some builders on our residential advisory committee, so we had that
feedback all the way through.
Sollenberger: Are they already complying with this?
Swartz: Journey did not stick with us on the committee due to time constraints, so we
have gotten very little feedback from them in the last six months . There will be some
increases that will vary by builder. Habitat is a leader and is doing some of this already.
Big picture:
These numbers represent one year of construction with both residential and commercial
together. It is the costs over one year and benefits over a 20 year period. $2 .2 Million in
benefits to $ 1 . 8 Million in costs after one year of construction. Residential + commercial,
quantified elements only.
Costs summary:
$ 1 . 8 Million most in initial costs, next enforcement + one time costs for materials and
training.
Benefits:
Utility savings over 20 years, Building Valuation (will have a higher value in the market
place), Health + Productivity (hard to find national numbers on this), Economic Health is
a reflection that when you spend more money on construction that will revolve in the
economy counted as conservative . 5 multiplier which is .25 value. The carbon reduction
is hypothetical because nobody is buying carbon right now. It is based on an expectation
of the near future.
Sollenberger: I have a concern. Your costs are nailed down but this is a lot of assuming
and to base our decision on this is a leap .
Blonder : I like that you are being conservative. I think the building valuation increase in
value is extremely conservative. I know many buyers want the green buildings.
Swartz: National suggested 1 % to 5 %. Code does not have the instant recognition like
LEED . Part of this is to provide that market place recognition. Mike, I agree there are
many assumptions and we tried to mark them and where they come from.
Sollenberger : The hard costs we know, but the hard benefit is the blue. The rest has
some softness .
4 of 22
ATTACHMENT 11
Swartz: Our goal was to present what we knew to decision makers and help them
understand what we think is the big picture.
Speaker Unknown : The problem is that we are used to looking at hard dollars and return
on investment.
Swartz: (Screen on acronyms on "Return on Green".) The decisions we make when we
decide to build green reflect on our health and quality of life. We tried to put numbers to
them.
Sollenberger : What is the ROI?
Swartz: We could calculate based on our numbers and we can give it to the public.
However, it would not be attractive if you just look at the cost benefits.
Sollenberger : I think it is something the public should know.
Byers : Would the cost per month be greater than the cash benefit?
Sollenberger : Yes, what are the costs up front? When do the increases in costs get
returned?
Lee: That depends on the financing time. The finance costs could be greater than the
benefits over 20 years.
Blonder : Wasn't the utilities cost inflation rate very conservative?
Swartz: We tried to nail it down, but then we took the center of those numbers.
Blonder: There is a lot to all of this . Some will be very expensive. It seems like your
numbers are really low.
Swartz: Some are refinements of what is already in the code. The costs side will be
highest in the first days of the code. After a couple of years it is less and infrastructure is
improved and costs come down. We are trying to reflect day one costs . In reality, after a
couple of year' s refinement it will be considerably lower.
Blonder: I appreciated Appendix 1 . It is well broken down. Do you think you will
exceed these numbers?
Swartz: No, we don't think so.
Sollenberger: Using high side puts it at $5600 which give it a 2-3 year payback plus
other benefits .
Byers : What have you found looking at other cities? Is it in code or is it voluntary?
5 of 22
ATTACHMENT 11
Swartz: Use is on the increase. Santa Fe, Longmont, Boulder, Albuquerque, (others
listed) has adopted varied green building codes. We have not looked at them in detail. We
have been honing in to our own codes .
Byers : Have you considered adopting a reward program for voluntary compliance
instead of a code?
Swartz: Council is looking at a combination of both. To move the market we want to
reward builders who go beyond this. Council said to look at pushing the bottom end
quicker. These are small steps . Not radical.
Blonder: Under# 4 in Appendix 1 is one of the highest dollar items on the list. Is that
included in the ROI?
Swartz: That is not included as said in the footnote. For example: The Campus Crest
development is very contentious. We keep hearing they are proposing electric heat, and
people are concerned. Recently the owners approached CSU and said we need to learn
about green building. They said they are beginning to understand that Fort Collins is
different. A design cheret was held about three weeks ago and we participated. There
were about 60 people there. The owners were very clear that they misread what they were
getting into. They will have to go back and redesign the project to meet the expectations
of this community and apply it to other projects they take around the country. Message is
that Fort Collins is recognized as a leader in this kind of change. This is one step along
that path. We will be looking at ways to significantly reward builders that go beyond the
basic code.
Swartz: Next steps : We are taking this to Boards and Commissions January and
February. The City Council reading is in March.
Byers : It is hard to see a proposal like this and not see a conflict with the Affordable
Housing community. How do we reconcile this increase in costs even though they are
good things? Can we exempt some affordable housing construction in town for some of
this?
Swartz: There is no easy answer. I have not seen sentiment to exempt affordable
housing. The feeling is that all need the benefits that come from this . Maybe we need to
look at more creative financing approaches that can help take this into account? We are
seeing some of the affordable housing builders are some of the leaders and already
implementing some of these codes.
Sollenberger: All of those items were covered with a grant. The CDBG and some
Housing Authority rehabs were grant covered. They are a leader when it is free money.
And those costs are not passed on to tenants.
Swartz: Challenge is reconciling the individual cost vs. the benefit to community.
6 of 22
ATTACHMENT I
Sollenberger: It is hard for us to find balance. The other problem is the tax that is not
presented as a tax and it will increase mortgage and annual payment. They did not get to
vote on this. I have a problem because the people are getting hurt and we can't vote on it.
I am not swayed by council ' s desires . They are out in three months. I do not want to ram
it through on their watch. We should have more time. It is hard for me to be supportive.
Blonder: Do you see this as a 1 -2% increase in rent for tenants?
Swartz: I think it would carry through the same way.
Sollenberger: One of the problems with gas forced air in units is they do not make units
for the down size in the apartments. If we did multi-family units, it would be a less
favorable picture.
Swartz: After the Council adopts the Green Building, we want to make sure the builders
have enough support for the transition. If adopted in March, it will be effective the next
January. We want to have enough time to figure out the details and train the building
industry and put into place a quality assurance plan beyond the classroom training.
Next Steps:
• Alternative compliance path details
• Certification requirements
• Performance testing protocols
• Compliance forms, templates
• Fact sheets, field guides
• Staff + contractor training
• QA/mentoring plans
Blonder: I think the city should participate more in the costs of the project.
Waido: Currently the Affordable Housing Fund is to help compensate for the increase in
costs. They could put more money into the fund to help people buy houses. If you
increase the cost of housing, you immediately wipe out a segment of population from
getting into home ownership. They might not be there long enough to recover the costs.
Sollenberger: We are not suggesting that the owner will be there 33 years. Just that
someone will be there the life cycle of the structure (33 years), then it is the first owner
who is standing that cost increase.
Byers : I like the idea to increase the Affordable Housing fund.
Sollenberger : Yes, it needs to be done if you are going to mandate people to do this.
Qualified affordable is definable. Can we exempt out or something? The nonprofits are
eligible for all of that stuff. A private builder is not.
7 of 22
ATTACHMENT 11
Waido : There is an increase in costs, yet one of the benefits is that there will be a market
demand in the future. What if a qualified low-income buyer had that house discounted
and didn 't have to pay into that, would they pay for the increase in costs?
Sollenberger : The builder can bank that. It is no different than our down payment
assistance. That gets repaid.
Waido : This adds 1 % to cost of housing. On a $200,000 house that is $2000. Low
income pays $ 198 ,000 and not the $200,000 until they sell at an appreciated $206,000 for
example. Just a question. I don't have the answer.
Swartz: Regulation: In 201 lwe will have pre-implementation with refinements to City
Council. It will be implemented in January with Quality Assurance in 2012 . There will be
Amendments down the line. Some ideas are water metering for units vs. the building, and
land use code amendments ideas that were handed off to the Planning Department. Next
land use code update with Plan Fort Collins would consider some of these things .
Waido: Some examples could be like lot size and orientation.
Swartz: In review last year we decided to work on greening our code because regulations
are already supporting these concepts . Even though a lot of this is new in other places,
much of it is not new in Fort Collins. So the idea was to review and see where the
opportunities lay and take steps in other areas.
Incentives, Recognition, Education + training, regulation, costs + benefits are all above
code.
Please vote on this. Proposed Motion: The affordable housing board recommends the
proposed building code green amendments for residential and commercial
construction be adopted by council.
Sollenberger: How else does it affect the buyer? (Quick math on sample costs.) Possibly
a $ 17-34 difference in a monthly bill.
Byers : What we are talking about is $204 or $ 12/month at 6% . Utility savings is
$65/year. It will look at costs at the low end $ 165/year. That is a fairly small number.
(Discussion around the increase costs to renters or low income home buyers .)
Blonder : Worse for tenants than owners.
Byers : Rent is based on income. If it is city subsidized, the renter would not have to bear
the costs.
Blonder: I am more worried about the renters.
Waido: There is a city subsidy in town. City paid 10% at Province Town from CDBG.
8 of 22
ATTACHMENT 11
Sollenberger: Tax payers are not shelling out for that, it is HUD money.
Robinson: I like the idea of green, and that is where we need to go, but I don't want to
see a family not get a home because of this extra expense. I would at least want to see a
back-up plan for them, like a waive. At least propose this feedback to Council even if
they are already going to pass it.
Sollenberger: This is a more altruistic thought process, that we should do it for the
benefit of the people even if some can' t afford it.
Blonder: It is an image thing as well.
Sollenberger: Are we looking for a decision tonight?
Lee: It would be good to have something to put in the Council packets before March 1 .
Blonder : Let' s draft it and send it out by email.
Byers : Can we ask for a potential increase in the Affordable Housing funds .
Waido: We have rarely done any rental assistance, but no mortgage assistance program.
We could use homebuyer assistance to help buy down the interest rate or increased costs.
Many 1 " time buyers are only buying condos and townhomes. They can't afford a house.
Sollenberger : We are really only talking about the impact on the rentals .
Byers : The builders can 't pass the costs on to affordable housing renters because their
rent is based on income and they are maxed out.
(Discussion about construction of rental apartments and the justification of building.)
Sollenberger: Market rents just don't work in Affordable Housing. Rents have to be
above 1 .25/sq. ft. Does it make any difference? No one is building single family homes
that qualify for affordable. We are looking at apartment buildings only. I would like to
recommend it.
Byers : Council needs to know that this could have an effect on Affordable Housing in
Fort Collins .
Blonder: It is such a small amount. I agree with Mike and I agree with most of this.
Byers : I think it needs to be voluntary only.
Sollenberger : I agree.
9 of 22
ATTACHMENT I
Robinson : I would like to think it will make Fort Collins more attractive and bring in
more jobs .
(Short discussion.)
Byers : We should write a memo to support it, but these are our concerns and thoughts.
Sollenberger: Let' s mull it over and get feedback to Ben by February 11 ?
Members agree to draft a recommendation and present it by February 11 , 2011 .
Plan Fort Collins Update :
Presenter Ken Waido :
The next steps : Plan adoption is Feb 15 . The paperwork is to go to the council and staff is
presenting the updates to City Plan, Transportation Master Plan, and Pedestrian Plan for
adoption. Some land use code implementation items will be on March 1 first readings,
March 22 second readings. Regarding the ordinances, we talked about the changes to the
L and M zone. The density ranged is being changed at both ends. There are some changes
in terms of housing mix % requirements and what qualifies as a housing mix. Different
lot sizes. (2000 sq ft difference, above 5000 and below 5000 .) Can't do it in a single
housing type. Only with 3 housing types or more. The part of what has been up to this
point is being carried forward is the change in density in urban estate zone. P&Z meeting
county people were totally against it. Board will not recommend to the council. This is an
optional thing. The board has had a lot of comments sent previously. Do you want to
make a recommendation or just say something as comments?
Sollenberger: I don' t think it affects us from product type. We would assist with projects
that are small.
Waido : The Affordable Housing strategic plan is affecting us the most.
Robinson : Was the plan updated last year?
Waido : Yes, in July.
Blonder : Does anyone want to make a recommendation? Maybe Ken and I can meet on
this .
Waido : I am 70% devoted to Affordable Housing. My time is totally consumed by Plan
Fort Collins and will be until the end of March. Then I will be able to pick up some more
Affordable Housing projects. I want to look at the 6-month planning calendar. Some
months are blank and I am asking you what else you want to put on this such as
discussion interviews. The incentives is a good one.
10 of 22
ATTACHMENT 11
Sollenberger: Have a member of the attorney staff explain why they think the Housing
Authority has to have a controlling interest before they give a tax credit. That will shut
down the Housing Authority participating in tax credit deals .
Waido: The June Meeting is schedule for June 2 and I will need to be out of the office.
We might have to look at rescheduling to another date. Ben won't be here for August
meeting.
C. Other Business
Waido : Donna Murton is changing her Union Place project. It will be a senior rental
project. I think it will be 50-60 units but I have not seen the final numbers .
Sollenberger: If a manufactured product has a HUD stamp can it ignore local code? That
has a lower standard on everything than FTC has .
Lee: I do not know.
D. Next Month' s Agenda
1 . Please refer to the AHB 6 Month Planning Calendar.
E. Future Meetings
1 . Any additions to the AHB 6 Month Planning Calendar?
Meeting Adjourned at 6 : 45 PM.
11 of 22
ATTACHMENT I
DRAFT ELECTRIC BOARD MINUTES
11 .2-2
Board Present Board Members Tom Barnish, John Harris, John Graham, Peggy Plate, Ed
DeCourcey, and Steve Wolley
Board Absent Vice Chairperson Steve Yurash
Staff Present Steve Catanach, Ellen Switzer, Robin Pierce, Tom Rock, Kraig Bader,
Katy Bigner, Jenny Lopez-Filkins, Patty Bigner, John Phelan, and Felix Lee
Guests Rick Coen
Selection of Board Member to Chair Meeting
Wolley
Call Meeting to Order
5 : 32 p.m.
Officer Elections
Chair nominations : Steve Wolley, Ed DeCourcey
Wolley by a vote of 4 to 1 (Wolley abstained)
Vice Chair nominations: Steve Yurash (incumbent), Ed DeCourcey
DeCourcey by a vote of 4 to 2.
Approval of Minutes
Page 2, paragraph about letters received by the Mayor. "Most of these citizens were part
of a group who favor of tiered rates, who believe they could be . . . . ".
Page 1 , "If significant changes are made . . . ".
Page 2, third paragraph. "Staff will recommend a more rapid implementation schedule for
the electric heat amendments than the other code amendments."
Board Member Barnish moved to approve as modified; Board Member Graham seconded
the motion. It passed unanimously.
Monthly Financial Report
(Presentation available upon request)
Utilities Financial Operations Manager Ellen Switzer presented the Monthly Financial
Report. Ms. Switzer noted the information has not been audited yet. , and purchase
power expense increased 8 . 7 percent above 2009 . Figures exclude depreciation and
grants.
Operating revenues represent revenue from meter reading activity.
12 of 22
ATTACHMENT 11
Key Financial Results:
How does the Southwest Annexation cost match up with the amount budgeted_ _ _ . would
like to see this information included each month. Part of the -4. 8 percent variance for
capital additions relates to less cable replacement than anticipated, as well as managing
projects low and delaying.
Is it an issue for the Utility to not spend capital money? We have identified revenue and
expenditures, which should balance. We 've been budgeting a loss in the last few years to
draw down reserves.
Two types of capital budgets: lapsing (those funds if not used in the year, they are not
available to spend the next year, but do go into reserves); non-lapsing (the funds stay with
the life of the project).
Energy and Demand by Month:
Planning Engineering Manager Bob Micek uses this information to report to Platte River
Power Authority. It was suggested to normalize the annual peak demand by reflecting
average temperature; interest in seeing how much it fluctuates over time.
Operating Revenue:
In 2010, operating revenue increased 11 percent from 2009 due to a 7 .4 percent rate
increase and increased kWh sales in the residential class.
Non-Operating Revenue:
Sale of equipment and parts, repair of damaged equipment; interest income.
How are grant revenues tracked? Only available for the grant projects, so it is tracked
with the project but not in the budget.
Capital Projects (non-lapsing budgets) :
Total project cost compared to budget.
2010 Total Revenue Compared to Expense :
Purchase power represents 70-80 percent of our total expenses. Would like to see the top
three items that account for the reason why we came in under budget.
2010 Summary:
Additional appropriations approved by Council are required if we need to spend over our
budget. Contingency funds for unexpected events are placed in one line item of the
budget for ease in keeping track of where they are. Philosophy of not spending just
because we have the budget.
Ms . Switzer thanked board members for their suggestions and will make those changes .
13 of 22
ATTACHMENT 11
Building Code Green Amendments
(Presentation available upon request)
Green Building Code Project Manager Felix Lee and Energy Services Manager John
Phelan presented this topic to the Board. Council directed staff to develop mandatory
building code green amendments to be integrated into the City' s existing building codes
for residential and commercial construction. Council will consider the proposed "green"
amendments to the Fort Collins building code at their March 1 and March 22 meetings.
The purpose of the Green Building Program is to align . . . . (from presentation slide).
The substance of the proposed amendments remains the same since staff provided an
update to the Board at the December 1 , 2010, meeting. Refinements to the proposal since
that time include:
- Low-VOC materials : cabinets excluded
- Daylighting deleted
- Occupancy control of lighting in defined spaces
- Certified tropical hardwood
- Special provisions for electrically heated buildings (increase envelope insulation
requirements)
The Board received a comprehensive benefits and cost summary. The benefit-to-cost
ratio represented as one year of construction, residential and commercial, quantified
elements only with a 0 percent inflation rate, costs total $ 1 .76 million, and benefits total
$2 .23 million. Benefits include carbon reduction, utility savings, building valuation,
health and productivity, and economic impact on the community. Mr. Phelan explained
the concept of economic multipliers .
Staff will round to boards and commissions through February. More information can be
obtained by visiting www. fcgov.com/gbp .
Was there consideration at making these voluntary rather than codifying them ? There
was a lot of discussion around this. Staff proceeded to develop those things that make
sense to codify and represent minimum standards.
Some of the example codes staff was comparing to revolutionary or evolutionary? Mr.
Lee, as a code official, was initially supportive of the two sets of standards in the
marketplace until he closely examined them. This change is evolutionary.
Did the City and stakeholders examine whether this would prevent developers from
coming to Fort Collins ? Staff discussed this factor and determined this is not a big
driver, compared to other costs such as infrastructure, etc. This is not viewed to be a
strike against new business .
Upgrade to Foothills Fashion Mall? If an addition was added or changing out major
systems, it may come under some of these code changes, but when the footprint does not
change, it normally wouldn't.
14 of 22
ATTACHMENT I
Six to twelve month lead times and bureaucracy in Fort Collins would be prohibitive
when developers can go elsewhere and build much quicker. Mr. Phelan noted planners
would counter that people want to live and develop here for the very reason of our high
standards. Energy Services and Development Review are both investing in time with our
community contractors to teach them how to get through the planning and permitting
processes. Fees from developers to Development Review will help support this program.
Concern that adding these products puts a home with these upgrades out of a lot of
people 's reach. It was noted one of the only remaining entry level residential builders in
the community would see no cost increase from these amendments; they are already
incorporating these measures in their products .
What was the stakeholders ' biggest issues ? It varied between the residential to
commercial groups. "Greening our code" in comparison to adopting a green building
model code was the biggest challenge for the residential group. The commercial group
was concerned about the practicality of enforcing these changes and implementing the
program.
Motion: Board Member Graham moved that the Electric Board recommends the
proposed building code green amendments for residential and commercial
construction to be integrated into the City' s existing building codes. Vice
Chairperson DeCourcey seconded the motion.
Vote on the motion: 5 for; 1 against.
Reason for nay vote : Board Member Barnish voted against out of concern that it will cost
the community too much (see other concerns above).
Board Member Graham recognized the effort put in by staff to develop this.
15 of 22
ATTACHMENT 11
Landmark Preservation Commission Memo
Fort Collins
Memorandum
DATE : February 16, 2011
TO : Mayor and City Council Members
THRU : John Phelan - Energy Services Manager
Doug Swartz - Energy Services Engineer
FROM: Karen McWilliams - Landmark Preservation Commission staff
RE : Landmark Preservation Commission Green Building Recommendation
On February 9, 2011 , Green Building Staff members attended the Landmark Preservation
Commission meeting to provide an update on the Green Building Program and the
building code green amendment proposal. After the presentation and discussion, the
Landmark Preservation Commission voted unanimously to recommend that Council
adopt the code changes, as proposed.
Thank you,
Karen McWilliams
Historic Preservation Planner
Community Development and Neighborhood Services
16 of 22
ATTACHMENT 11
Draft Building Review Board Minutes
The Building Review Board will provide a final recommendation for Council following
the Board's February 24`h meeting.
Minutes to be approved by the Board at the February 24, 2011 Meeting
FORT COLLINS BUILDING REVIEW BOARD
Regular Meeting — January 27, 2011
1 . 00 P. M.
Chairperson: Alan Cram IlPhone : 472- 1752(H)
Council Liaison: Kelly Ohlson IStaff Liaison: Mike Gebo (416-2618)
A regular meeting of the Building Review Board was held on Thursday, January 27, 2011 in the
Council Chambers of the Fort Collins Municipal Building at 300 LaPorte Avenue, Fort Collins,
Colorado.
BOARD MEMBERS PRESENT:
Alan Cram
Andrea Dunlap
Brice Miller
Jim Packard
Rick Reider
Jeff Schneider
George Smith
BOARD MEMBERS ABSENT:
None
STAFF MEMBERS PRESENT :
Delynn Coldiron, Customer & Admin. Services Manager
Russ Hovland, Plans Analyst — Permit Plan Review
AGENDA:
1 . ROLL CALL
The meeting was called to order and meeting instructions given.
2 . APPROVAL OF MINUTES
A motion was made to approve the November 18, 2010 minutes as written. The motion was
seconded.
3 . Green Building Program Update
The presenter stated they would provide information on work that has been accomplished on the
ordinance language and the benefit cost analysis. The green building team will meet with the
17 of 22
ATTACHMENT 11
Building Review Board again on February 24 h to review the ordinance language. They will be
looking for board input at that time.
The presenter reviewed the green building program goals which are to align with the city policies
of reduced carbon emissions, reduced energy and water use, to create better buildings, to avoid
lost opportunities and to continue our leadership role in Fort Collins. The green building code
amendments are a component of the larger green building program. As the code development
work is completed, the City will move to more market based recognition and incentive type
programs.
The amendments can be clustered into different categories, but the City is focusing on a system
approach. The presenter discussed changes that have taken place since the last presentation to the
Board. Cabinets have been removed from the low VOC proposal. The commercial and multi-
family list no longer contains a day lighting measure, and there is an additional measure for
occupancy control for specific spaces — mostly corridors and stairwells. Also, lighting in those
areas will be reduced to 50% when those areas are unoccupied.
The presenter stated that four options were previously being considered. Three of those options
have been removed. The remaining option is certified tropical hardwoods. The proposal for
higher electric heat building requirements would be implemented before January 1 , 2012.
The presenter also discussed changes that will be made to the 2009 I-Codes. Amendments have
been made to the ICR which governs single family homes and duplexes. Residential three-plex to
multi-family three story structures are covered under Chapter 4 of the IECC, and Chapter 5 of the
IECC covers multi-family buildings that are greater than three stories. Amendments have been
made to those two chapters of the IECC.
The presenter referenced benefit cost categories in Figure 1 . The green building team looked at
things from an individual perspective, from the building sector perspective, and the community or
the ecosystem. He added that the cost analysis is an inexact science. There are many moving
parts, and also many limitations on staff s time and resources. Staff has done the best they can,
but there is some variability.
A component analysis and a community scale analysis were completed. The component analysis
looked at each specific proposal and analyzed it. There are some studies and different pieces of
information to look at on the community scale analysis. There are both quantified and
nonquantified costs and benefits. Some are straight forward and easy to quantify. Some are
difficult to quantify; i.e. , benefits of a dark night sky from dark sky pictures. The results were
presented in ranges, recognizing that different builders would have different levels of experience
and different access to resources. The same is true with benefits. There are a lot of moving parts,
different size buildings, different configurations, so there is no single number.
They used prototype buildings for new residential and commercial construction to give grounding
to the numbers. The costs for the most part are near term costs, and the benefits are recurring
long-term benefits.
The presenter also discussed cost increases. They range from 1 % to 2% on the residential side
and from 1 % to 4% on the commercial side. There is no quick direct payback to owners, and
there will be increased enforcement time and costs. Overall analysis shows that total benefits do
exceed the costs, and the total benefit cost ratio is 1 . 3 . This is based on the analysis of one year
18 of 22
ATTACHMENT 11
of construction. There are some enforcement costs and then some training and support materials.
The training and support materials are really a one time cost, so they are a little different.
Regarding benefits, utility savings are about a quarter of the benefits, followed by building
valuation which is another big piece of the pie. Economic health, carbon reduction, and health
and productivity fill in the smaller wedges.
City Council will have the first reading of the ordinance on March lst. The second reading will
be March 22nd. Activities to be completed in 2011 include testing protocols and forms, templates,
fact sheets, training for staff and contractors and setting up a quality assurance program to use
when the program is implemented. The amendments will be implemented in 2012 . There may
also be a few instances where the ordinance needs further revision. Those tweaks could be
accomplished late in 2011 .
Once that is completed, staff will address the market driven aspects of the program with
recognition incentives, education, and training. There is a lot of information on the website that
addresses green building practice summaries, benefit cost analysis, and minutes from the track
meetings.
Chair Cram asked if any of the audience participants wished to speak
Axel Severts stated that he works for W.J. Bradley in Fort Collins. He is a lender. Mr. Severts
stated that his biggest concern is that the cost of new buildings will increase with the green
building program. In order for a remodeled house to get appraised with the added costs, there
would need to be similar green houses in the exact same neighborhood in order for FANNIE and
FREDDIE to accept the value. FANNIE and FREDDIE would actually have to change their
guidelines in order for lenders to add a line on the appraisal form to adjust it for a house that' s
green. Mr. Severts stated that his biggest concern is how homeowners would ever get an
appraisal to account for the green build remodels. In a new subdivision that is entirely green, the
appraiser could simply use the house next door.
Mr. Severts stated that he felt first time home buyers would be priced out of those neighborhoods
because they are the most sensitive about price. They are struggling to get into that first home
regardless of whether it is or is not green. There currently is discussion about FANNIE and
FREDDIE trying to get the green guidelines into their product mix, but there is also talk about
them going away. Every investor in the country underwrites to their guidelines. If it goes
private, how would green built ever get added to the appraisal form?
Board members addressed questions to the presenters.
A Board member commented that he has found a number of inconsistencies in the cost analysis
figures. A range of 1 % to 4% has been discussed, but 1 % to 2% is referenced for residential land
and up to 7% for commercial. So, 1 % to 4% doesn't jive with anything else in the rest of the
document. Another example is the initial costs in Appendix 1 . One percent of $250,000 is
$2,500, but the calculation is $2,835 . If staff is using 1 % as the low figure, then the rest of the
tables should match that concept. The presenter suggested that perhaps they could review those
specific areas with the Board member.
A Board member asked if anyone from the Board of Realtors and the real estate community has
been contacted for their comments and concerns. A presenter responded they have been
represented on the green building program advisory committee and some members from the real
19 of 22
ATTACHMENT 11
estate community have been on both the residential and commercial tracks. Staff realizes what a
challenge the underwriting will be.
A Board member questioned the cost impacts, ranges, and utility savings that were arrived at
based on the prototypes. He stated that the ranges are based on an entry level home in Fort
Collins, but the code will impact everyone across the range for construction. An example would
be that in a home that sells for $200,000 to $250,000, vinyl windows would be used for the
basement as well as the upper levels of the house. But in a $ 1 million home that uses Andersen
Windows, that impact could be significant. He would want to ensure that everyone knows the
project costs are based on a $200,000 to $250,000 home.
The Board member also discussed construction waste recycling. The low is zero and the high is
200. He asked if the Brendle Group or staff is assembling the numbers. A presenter responded
that they are most concerned about the cost impact to the entry level buyer. They did think that if
they put costs in percentage terms, even for a more expensive home, they would probably not see
a huge different range of percentages. They were clear in the report about the prototype that was
used, and the numbers for more expensive homes can be scaled up. They talked with builders,
contractors, subcontractors and service providers. They attempted to bracket the range in a
reasonable value that they were confident about. On construction waste recycling, the reason the
low is zero is because some services will be paid for related to recycling construction waste. Less
material will also be sent to the landfill. They are aware of some projects that have actually saved
money by implementing construction waste recycling. They also did not attempt to quantify the
existing construction, the remodels, and the additions because there were just too many different
combinations.
The Board member also asked about those alterations that don't require a building permit. In
those instances, the City will not know if the home owner installed a water efficient fixture.
Hovland stated that the intent has always been that the green code is applied to new construction
and then alterations with a permitted alteration. The City will never see a nonpermitted item.
The Board member stated that the philosophy behind the code program is to help conserve
electricity, conserve water, and reduce carbon emissions. Why wouldn't it also be mandatory for
all citizens in Fort Collins regardless of the work that' s being done? He stated he did not
understand why staff is looking at only one portion of it. A presenter responded that it is a
practical cut-off point. He added that the green building codes go above the baseline codes of
life, health and safety. The Board member disagreed, saying that the definition needs to be
changed because the new code is mandating that these changes occur on new construction;
therefore, the new code is the minimum standard for life, health, and safety.
A presenter added that the intent of the green building program is market transformation. It is a
bit of the 80/20 rule. We are getting the lions share of the savings for most buildings. Overall the
market is changing and water efficient fixtures will be the fixtures that are available at Home
Depot two years from now. It is going to be difficult for the consumer to purchase a toilet that
isn't 1 .28 gallons per flush.
A member asked if the additional interest that will be paid over 30 years on the increased loan
amount was considered in the calculations for the cost of those items or if it was just calculated
on the basis of how much more an item will cost. A presenter responded that the interest piece is
shown in the mortgage payment. It is best summarized at the bottom of the page on Appendix 1 .
A member also asked if the record-keeping and bookkeeping costs to the contractor have been
calculated. A presenter said they haven't explicitly quantified that, but they do reflect the
20 of 22
ATTACHMENT 11
contractor margin in the estimated costs so they are accounting for some of that burden. The goal
behind the code changes is not to increase burden. Staff is very interested in working with the
building community to try to make this as easy as possible. The goal is better buildings, not more
paperwork.
A Board member asked what percentage of costs for administration will be for the building
department. A presenter referenced Appendix 3 and stated there will be a substantial increase in
staff time. The funds for the additional staff have been appropriated by City Council so it is
available should they adopt the amendment. The Board member asked if the presenter was
comfortable with those numbers. The presenter responded that they felt the numbers were
conservatively high. The 45% falls within the national average for this program. There have
been some recent discussions that it may not have been enough. He added that these costs as well
as the initial costs will probably come down as staff becomes more experienced. Staff is trying to
represent in the cost estimate what' s going to happen in the near term. Based on passed
experience, watching other code changes, we will find this easier and less expensive than it seems
looking at it in the future.
The Chair thanked the Green Building Team for presenting today. He stated they are making
headway in producing a living viable document that works for everyone.
4. Election of Officers
Alan Cram was nominated for Chair. Jeff Schneider was nominated as Vice-Chair. The motion
was seconded.
Vote :
Yeas : Cram, Dunlap, Miller, Packard, Schneider, Smith
Nays : None.
Abstain: Reider
5 . 2010 Annual Report
A member made a motion to accept the 2010 Annual Report as presented. The motion was
seconded.
Vote :
Yeas : Cram, Dunlap, Miller, Packard, Reider, Schneider, Smith
Nays : None.
6. Follow-Up Reports:
• A & J Construction — Coldiron reported that this was the gentlemen who was
struggling with the English language that was at a previous meeting with John Estabrook. The
board required that he frame a house within the City of Fort Collins. This has been done, and he
passed inspection. The City has finalized his full framer license at this point based on the Board' s
recommendation.
• February meeting — Coldiron announced that a luncheon is planned for the February
meeting. She offered to contact the City Manager' s office and invite Kelly Ohlson. Paul Eckman
will be invited to offer some coursework in board duties and responsibilities. Rick Reider will
21 of 22
ATTACHMENT 11
also be formally welcomed to the Board. A decision was made to start the meeting at noon. A
member suggested that lunch be kept simple and light to contain costs.
• Code Class — Coldiron stated the code class has been delayed so the green building
amendments could be included. She will schedule a room that will hold 200 to 250 people and
try to have it videotaped so it meets the ordinance requirements that the City has for contractors
who need to either take a class or take the amendments exam. That video could be available to
show quarterly to meet the needs of contractors.
7. Other Business
• Members provided Coldiron with new contact information.
• A Board member suggested that it would be helpful if it could be determined before
the Board meetings how many of the Board members will be attending. Coldiron stated that staff
would confirm attendance in the future.
• Coldiron reported that a new Building Development Review Tech has been hired.
Board member Schneider participated in 12 interviews with perspective applicants. Molly
Packard will be joining staff on February 22.
Meeting adjourned at 2 : 00 p.m.
Mike Gebo, Chief Building Official Alan Cram, Chair
22 of 22
ATTACHMENT 12
Advisory Committee Member Comments
In the most recent meetings of the Technical Review Advisory Committee and Green
Building Program Advisory Committee meetings, members were asked to individually
comment about their sense of the proposed building code green amendment package.
Residential Technical Review Advisory Committee
♦ No items in particular seem like they would be a problem. It would be great to see
some order of what has the best payback.
♦ Concerned about a prescriptive code. Certified wood, DC blower motor,
commissioning and safe combustion are adding cost to the house.
♦ Cost is a big deal - especially in this economy. Whole-house ventilation is a big
concern because you are requiring a high efficiency, expensive fan because that is the
only way to meet energy requirements. Also, this negatively pressures the house and
essentially gets rid of heat recovery ventilation systems in Fort Collins.
♦ This is a good start. Not surprisingly, with such a diverse group of stakeholders, the
final package is predictably diluted.
♦ The proposal is on the right track.
♦ Agreed: this is on the right track. Electrical efficiency seems like it was left out of the
code proposal, though. Energy-efficient lighting package not addressed. Could
include requirements around daylighting and phantom load controls . These options
could be easy and low cost.
♦ The standards could be further increased beyond the proposal. Electric heat versus
gas heat requirements may push people to use a non-renewable energy source (gas) as
opposed to an electric system that could be powered by renewable energy.
♦ The code proposal is not too heavy-handed; it strikes a good balance. Makes
improvements but won't create a big push back. Convince the council that this is a
good place to start and then monitor it to make sure it is working and how it could be
improved.
♦ This is a good start. Electric heat homes are viable.
♦ From the enforcement side this is all very doable. This is going to increase cost on the
industry's part. Would like to have the building department verify compliance for the
new measures as opposed to requiring third-party verification.
1 of 5
ATTACHMENT 12
♦ This is a good start. It' s not as heavy-handed as it looked like it might be. Builders
may have some challenges document that materials are low-VOC or certified wood.
When do additions or remodels come in? Whole house ventilation should be
considered when looking at HVAC system design. It is not a simple, stand-alone
item.
♦ Concerns about the cost to the customer and impacts on affordable housing. For
someone who is just getting into the market, a big upfront cost may be too much and
drive them out of the community. Remodels need to be addressed. Cost and length of
inspections is a concern. This will be a lot of information for the inspectors.
♦ Recycling plan needs to have a template to provide consistency. Insulation
installation requirement could be a judgment call on behalf of the inspector.
Commissioning should be verified by the City. Low-VOC material list is going to be
difficult to verify and enforce.
♦ The proposal sets a good direction. Be sure to think through the implementation
details carefully so that it works. The builder has little control when it comes to
interior lighting/material selections.
♦ If City Council wants a prescriptive code then this is a good start. A points-based
system would encourage people to look at green building from a broader perspective.
We have spent a lot of time on new construction - how is this code going to affect
remodels and infill?
♦ Some sections may be more appropriate to incentivize instead of mandate. A points-
based system would foster creativity.
♦ The code is well balanced and hits a lot of different topics. Remodel aspect of the
code is huge. Training and education are important and should be considered for the
implementation plan. Will the low-VOC requirements really have that much of an
effect? Perhaps the code should focus on the material that off-gas for the longest
period of time.
♦ The code proposal should also include future items that staff would like to include in
the next version. This will allow the market to plan ahead and possibly change faster
than the next round of code adoptions.
♦ The timeline for this project seemed short at some points but it kept the group and
process focused. It would have been great to get builders in the room who are
building to lower standards. The amendments are a good start to pushing green
building in the building community.
♦ City Council should not have asked for a prescriptive code. It would have been better
to have a voluntary green building program. The enforcement of some of these
2 of 5
ATTACHMENT 12
amendments will add cost to both the City and builders. The City needs to be careful
about requiring too much documentation.
♦ It seems like increasing regulations causes a negative reaction from some developers.
Voluntary and educational programs can have a more positive impact on the
development community. Fortunately, the regulations that did come out of this
process do not seem like they are too onerous.
Commercial Technical Review Advisory Committee
♦ Some of the items are very important and some are becoming the building standard. It
would be interesting to do a prioritization exercise to identify key items from the
proposed code that should not be discarded. Incentives are important as well as
implementation and enforcement.
♦ This is the beginning of a cultural shift in the industry. Hate to carry a stick around to
make people do things but in today's economy it may be necessary. This is a good
place to start. The biggest potential in our community will be in the existing building
side of things . The requirement for energy assessments prior to alterations is a good
start. That will help building owners see where the improvements can be made.
♦ Construction waste management, building envelope, insulation are all important to
green building. Some good steps have been made but I still worry that this is not
enough to really catch us up but making us less behind. When this is presented to
Council, Staff should focus on other values to society not just capital investments.
♦ This is starting out at a good spot. It is taking a step in the right direction but not
adding too much burden to economy. Some more documentation of first costs and
savings is important.
♦ The City is headed in the right direction. Stakeholder process is important and staff
did a great job of including the community.
♦ We are up in front at looking at this type of code. This is a strong beginning to create
a green building code. Glad IGCC was thrown out and that staff was able to see how
the code could apply additions, remodels, etc. Also glad staff looked at local impacts
to builders . Didn't want the code to be too cumbersome.
♦ This is a fragile place in the economy. This proposal is a positive start. Education is
important. The market is going this direction. As long as builders know what to do
and have all of the available resources, this is a good start.
♦ This is a good common ground for items that have a lot of impact. Building envelope
is critical to the GB code. Many builders are uneducated about it and it is being done
wrong over and over again. Education is important for these items. Worried that the
3 of 5
ATTACHMENT 12
City is not going to fund the building department to implement this code. You should
not necessarily have to save money to do the right thing.
♦ Building envelope is huge. From an inspection standpoint, staff has been learning
how the systems integrate. It is going to take a lot of time and training to understand
how it all works. The process does work but sometimes it is a cultural change that
you can't really put a solid savings to. Integrated design is important.
♦ Don't want to be so far out that we get ourselves in trouble. This puts us in front but
not too far in front.
♦ Wish that there was more of a push. The challenges that we face as a society are so
big and the changes that we are proposing are so small. It is difficult to create change
in the current system because we need more radical change. This is a step in the right
direction but it is not big enough.
Green Building Program Advisory Committee
♦ Education and incentives are extremely important to the success of this program. The
costs to the City and building community should be seriously considered.
♦ The City' s energy policy goals will be very difficult to achieve without some of the
mandates that are outlined in the amendment proposal. This also supports other City
goals.
♦ Council is going to need more specific information before they can make a decision.
Overall, the amendment proposal is on the right track. Deconstruction should be
considered for the proposals.
♦ Staff has done a great job of summarizing everything. Some of these items will add
cost but they are on the lighter side of green building regulations. Integration is
important for these proposals. If builders look at each item as something that has to be
added it is going to cost more than if these practices are integrated into the design and
construction.
♦ The code proposals are a great compromise between people who want more and those
who want less. The TRACs worked hard to find items that would make a difference
but not push things too far. A market for green does exist in our community.
♦ Council needs to be careful about putting too much burden on the building
community. Existing homes need to be addressed in this code.
♦ A lot of gaps exist in the information that is available in the proposals and cost and
benefit information. These are all good measures, but more information is needed for
Council to make an informed decision.
4 of 5
ATTACHMENT 12
♦ The City could research how other existing programs, like ENERGY STAR New
Homes and National Green Building Standard, could be used in our community.
♦ From a realistic, practical standpoint from the residential sector, this code is pushing
things too far. The market is starting to move this way but a lot of people are not
ready to pay more for " green. "
♦ The adoption of this code should be delayed to give staff and the community more
time to understand the details and decide if it is the right move.
♦ The financial piece and how this code will impact the business community is a big
concern. Incentives are important to help move green building forward and address
the existing building stock in Fort Collins.
♦ City Council is looking for something that is more aggressive. The C-TRAC really
tried to find practices that could be implemented as soon as possible and have big
impacts. The IGCC would have been a huge burden on builders and owners . These
proposals are a great compromise. It should be up to City Staff and City Council to
decide when the code should be implemented.
5 of 5
ATTACHMENT
Green Building Program and
Building Code Green Amendments
City Council Meeting
March 1 , 2011
Green Building Program
• Provide incentives
Voluntary, . Recognize innovation and success
market-driven ,
above-code • Provide education and training
Regulation • Building Code Green Amendments
• Research local costs and benefits
Foundation
• Metrics and quality assurance
• Address City barriers
2
Building Code Green Amendments
Residential and Commercial Practices
• GB Practices
— Building Envelope Performance
— Mechanical Systems Performance
— Indoor Environmental Quality
— Energy Efficiency
— Water Efficiency
— Construction Waste Recycling
— Owner Education
3
Ftff
Tonight' s Council Session
First Reading of Building Code Green Amendments
• Ordinances amending sections of:
— International Building Code
— International Energy Conservation Code
— International Residential Code
— International Mechanical Code
— International Fuel Gas Code
— Colorado Plumbing Code
4
i `rt_fl
Green Building : Moving Towards
Sustainability
IZero
Mandatory
Market Driven
Building
Performance
Requirements
BuildingVoluntary
Programs (GB practices
Impacts becoming code)
Building Code
Green Amendments
11 ' I -Codes
Today Future
`''Collin '
5
Benefit Cost Analysis
• Component and community-scale analysis ,
based on :
— Prototype residential and commercial buildings
— One year of typical construction activity
— Twenty year benefits , net- present-value
— Conservative assumptions
6
Benefit Cost Analysis Summary
• Near-term costs , recurring long -term benefits
• Energy , water, carbon savings
• Initial cost increases
— Residential 1 % to 2 %
— Commercial 1 % to 4 %
• No quick payback
• Increased ( City) verification time / cost
• Total benefits exceed total costs
— B/C ratio 1 . 3
City of
7
i.tf�
ollin
Implementation
• Education and Training
— Design professionals ,
— Contractors
— Staff
• Support
— Alternative compliance paths
— Certification requirements
— Performance testing protocols
— Compliance forms , templates
— Fact sheets , field guides
• Quality assurance
8
,: rtfi
Next Steps — Regulation
Jill
• Water metering
amendments
• Provide incentives (2011 /2012 )
• Recognize innovation and success Land Use Code
• P education and training amendments
• Regulation (2011 /2012 )
• 2012 I -Codes (2013)
• Research local costs and benefits
• Metrics and quality assurance Green amendments
• Address City barriers update (2013)
city or
Fort Collins J
9
Next Steps — Market-Driven
• Adjust existing
programs for new
• Provide incentives code baseline
• Recognize innovation and success
• Provide education and training Develop and
implement new
• Regulation pieces to accelerate
market
• Research local costs and benefits transformation
• Metrics and quality assurance
• Address City barriers
10
rtfl
Green Amendments = Outcomes
• The Green Amendments are the next steps towards making
GB practices mainstream , by:
— Establishing GB practices in code
— Advancing the performance of buildings
• Building Code Green Amendments — part of a larger picture
— Implementation support
— Regular code updates
— Market elements
C or
11
Questions
- F�or"tll
12
ORDINANCE NO . 030, 2011
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE II, DIVISION 2 , OF THE
CODE OF THE CITY OF FORT COLLINS FOR THE PURPOSE OF
AMENDING THE 2009 INTERNATIONAL BUILDING CODE AS ADOPTED
WHEREAS, the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural environment,
reduced carbon emissions, reduced energy use and reduced water use; and
WHEREAS, City staff has conducted a significant public outreach program, working with
three advisory committees comprised of representatives from the residential and commercial
construction industries, housing industry, real estate and appraisal industries, construction recycling
industry, specialized-trade contractors, and regional code officials ; and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of the
amendments ; and
WHEREAS , on February 9, 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS, on February 16, 2011 , the substance of the amendments was presented to the
Economic Advisory Commission, and the Economic Advisory Commission recommended approval
of the amendments; and
WHEREAS, on February 16, 2011 , the substance of the amendments was presented to the
Natural Resources Advisory Board, and the Natural Resources Advisory Board recommended
approval of the amendments ; and
WHEREAS, on February 17, 2011 , the substance of the amendments was presented to the
Water Board, and the Water Board considered water related elements and recommended approval of
those amendments ; and
1
WHEREAS, on February 24, 2011 , the substance of the amendments was presented to the
Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28 , 2011 , the substance of the amendments was presented to the
Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS , based on input obtained through this outreach process, together with City
Council and advisory board review and comment, staff has developed proposed amendments to the
2009 International Building Code ("IBC") as set forth in this Ordinance ; and
WHEREAS , the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that the IBC as adopted be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF FORT
COLLINS as follows :
Section 1 . That the opening paragraph of Section 5 -27 of the Code of the City of Fort
Collins is hereby amended to read as follows :
Sec. 5-27. Amendments and deletions to code.
The 2009 International Building Code adopted herein§ 5-26 is hereby amended in 4he
following respeetsto read as follows :
Section 2 . That Subsection ( 16) of Section 5 -27 of the Code of the City of Fort Collins
is hereby amended by the addition of a new subparagraph which reads in its entirety as follows :
( 16) Section 202. DEFINITIONS, teffns hereby amended Ito add the
following definitions in alphabetical sequence it the folio cii. r . as follows :
"The term " COMMISSIONING " is hereby added to read as follows :
"COMMISSIONING. A process to verify and document that the selected building and
systems have been designed, installed, and function in accordance with the construction
documents, manufacturers ' specifications, and minimum code requirements. "
"The term " VOLATILE ORGANIC COMPOUND (VOC) " is hereby added to read as
follows :
"VOLATILE ORGANIC COMPOUND (VOC) : "Any compound of carbon, excluding
carbon monoxide, carbon dioxide, carbonic acid, metallic carbides or carbonates, and
ammonium carbonate, which participates in atmospheric photochemical reactions . VOCs
include a variety of chemicals, some of which may have short-and long-term adverse health
effects emitted as gases from certain solids or liquids . "
2
Section 3 . That Section 5 -27 of the Code of the City of Fort Collins is hereby amended
by the addition of a new subsection which reads in its entirety as follows :
A new chapter is hereby added to read as follows :
"CHAPTER 36
SUSTAINABLE BUILDING CONSTRUCTION PRACTICES
SECTION 3601
GENERAL
3601 . 1 Scope. The provisions of this chapter shall govern sustainable building construction
practices for new construction and additions that require a building permit, unless otherwise
noted.
SECTION 3602
RESOURCE EFFICIENCY
3602. 1 Construction waste management. A construction waste management
plan, acceptable to the Building Official, including recycling of concrete, wood,
metals and cardboard, is required at the time of application for a building permit
for new construction. The construction waste management plan shall be
implemented and conspicuously posted on the construction site. Substantive
changes to the plan shall be subject to prior approval by the Building Official.
3602.2 Certified tropical hardwood. All tropical hardwoods used
in new construction, additions and alterations requiring a building permit,
shall be certified by the Forest Stewardship Council or other approved
agency. Certification demonstrating compliance shall be required with
delivery of such materials and shall be available for inspection.
"SECTION 3603
INDOOR ENVIRONMENTAL QUALITY (IEQ)
3603. 1 Indoor Air Quality (IAQ)
3603. 1 . 1 Heating, Ventilating, and Air Conditioning Design . Prior to and during
construction, reasonable efforts shall be made to minimize the release and
accumulation of debris and particulates, and the specific requirements of this section
shall apply.
3603 . 1 . 1 . 1 Air handling system access. The arrangement and location of air
handling system components including, but not limited to, air handler
units, fans, coils and condensate pans shall allow access for cleaning and
repair of the air handling surfaces of such components. Piping, conduits, and
other building components shall not be located so as to obstruct the required
access.
3603. 1 . 1 .2 Durability of air handling surfaces. Surfaces exposed to airflow
3
within air handling systems shall be constructed of materials that are resistant
to deterioration and will not break away, crack, peel, flake off, or show
evidence of delamination or continued erosion when tested in accordance
with the erosion test in UL 181 .
3603 . 1 . 1 .3 Airstream surfaces. Materials exposed to airflow within ducts,
within air plenums, or on top of suspended ceilings, shall not break away,
crack, peel, flake off, or show evidence of delamination or continued erosion
when tested in accordance with the erosion test in UL 181 .
3603 . 1 .2 Building pollutant flush-out. After all interior finishes are installed, the
building shall be flushed-out by ventilating at a minimum rate of 0 . 30 cftn per ft2 of
outside air or the design outdoor airflow rate determined from Chapter 4 of the IMC,
whichever is greater, for at least 14 days while maintaining an internal temperature
of at least 60°F, and relative humidity not higher than 60 percent. Occupancy shall be
permitted to start one day after start of the flush-out, provided that flush-out
continues for the full 14 days . The building shall not be "baked out" by increasing
the temperature of the space above the occupied set point. Where continuous
ventilation is not possible, the aggregate of flush-out periods shall be equivalent to
14 days of continuous ventilation. Flush-out reports shall be provided to the Building
Official prior to issuance of a permanent Certificate of Occupancy.
Exception : All residential buildings .
3603 .2 Low-volatile organic compound (VOC) materials. Construction materials, floor
coverings and site-applied finishes, including sealants and adhesives, resilient flooring,
carpeting and pad, site-applied paints, stains and varnishes, structural wood panels,
hardwood veneer plywood, particle board and fiber board building products, and insulation
shall meet specified volatile organic compound (VOC) emissions limits in accordance with
relevant standards California Department of Public Health (CDPH) 01350 ; GREENGUARD
Environmental Institute GGPS . 001 standard for building materials and finishes ; and Green
Seal® standards . Documentation demonstrating compliance shall be required with delivery
of such materials and shall be available for inspection.
3603 .3 Acoustical control. Minimum requirements for exterior-to-interior sound transmission,
interior sound transmission, and background sound levels in new construction and additions
thereto, except as noted hereunder, shall be provided as specified herein.
3603 .3. 1 Sound transmission. Buildings and tenant spaces shall comply with the following
sound transmission requirements :
Exceptions .
I . Portions of buildings or structures that have the interior environment open to
the exterior environment.
4
2 . Concession stands and toilet facilities in Group A-4 and A- 5 occupancies .
3603 .3 . 1 . 1 Exterior sound transmission. Where a Group Al , A3 , E and I
occupancy building, a Group B occupancy building used for educational purposes, or
a Group R occupancy building is constructed at a location listed herein, the wall and
roof-ceiling assemblies making up the building thermal envelope shall have a
composite sound transmission class (STC ) rating of 40 or greater in the following
locations :
1 . within 500 feet (300 m) of a multi-lane highway (road) designed for
high-speed travel by large numbers of vehicles, and having no traffic
lights, stop signs, nor other regulations requiring vehicles to stop, fire
station, heavy industrial or manufacturing zone or facilities,
commercial storage facility with back-up alarms, outdoor music
amphitheater, or sports arena or stadium;
2 . within 250 feet ( 150 m) of a truck route roadway containing four or
more traffic lanes ; or
3 . within 1 ,000 feet (900 m) of an active railway.
3603 .3 . 1 .2 Interior sound transmission. Interior wall and floor/ceiling assemblies,
separating interior rooms and spaces shall be designed in accordance with the
following requirements :
1 . Wall and floor-ceiling assemblies separating adjacent tenant spaces,
tenant spaces and public places, hotel rooms, motel rooms, and
patient rooms in nursing homes and hospitals and adjacent
classrooms shall have a composite STC rating of 50 or greater.
2 . Wall and floor-ceiling assemblies separating classrooms from rest
rooms and showers shall have a composite STC rating of 53 or
greater.
3 . Wall and floor-ceiling assemblies separating classrooms from music
rooms, mechanical rooms, cafeteria, gymnasiums, and indoor
swimming pools shall have a composite STC rating of 60 or greater.
Exception : Residential Group R occupancies addressed in Section 1207 of
this code .
3603 .3. 1 .3 Background Sound. The average background sound levels within
unoccupied rooms (from heating, ventilating and air conditioning and other building
systems) shall be below the maximum A-weighted sound level for specific
5
occupancies from Table 3603 below. This shall be confirmed by spot checks during
the commissioning process .
TABLE 3603
MAXIMUM ALLOWABLE BACKGROUND SOUND IN ROOMS
Occupancy Maximum
A-weighted
sound level (dB.)
Small auditoriums (<500 seats) 39
Large auditoriums, large live indoor theaters, and large churches (for very good speech articulation) 35
(>500 seats)
TV and broadcast studios (close microphone pickup only) 35
Small live indoor theaters (< 500 seats) 35
Private residences:
Bedrooms 39
Apartments 48
Family rooms and living rooms 48
Schools:
Lecture and classrooms
Core learning space with enclosed volume < 20,000 cu ft (<566 cu m) 35
Core learning space with enclosed volume > 20,000 cu ft (>566 cu m) 40
Open-plan classrooms 35
Hotels/motels:
Individual rooms or suites 44
Meetingibanquet rooms 44
Service support areas 57
Office buildings :
Offices
executive 44
small, private 48
large, with conference tables 44
Conference rooms
Large 39
Small 44
Open-plan areas 48
Business machines, computers 53
Public circulation 57
Hospitals and clinics
Private rooms 39
Wards 44
Operating rooms 44
Laboratories 53
Corridors 53
Public areas 52
Movie theaters < 500 seats 48
Churches, small (<500 seats) 44
Courtrooms 44
Libraries 48
Restaurants 52
Light maintenance shops, industrial plant control rooms, kitchens, and laundries 62
Shops and garages 67
6
SECTION 3604
COMMISSIONING, OPERATIONS & MAINTENANCE
3604. 1 Building commissioning. For new buildings and additions with a gross floor of greater
than 15 ,000 ft2 ( 1 , 395 in ), commissioning shall be performed in accordance with this section. A
commissioning process shall be incorporated into the design and construction of the building
project that verifies that the delivered building and its components, assemblies, and systems
comply with the documented owner project requirements (OPR) . Procedures, documentation,
tools and training shall be provided to the building operating staff to sustain features of the
building assemblies and systems for the service life of the building. This material shall be
assembled and organized into a systems manual that provides necessary information to the
building operating staff to operate and maintain all commissioned systems identified with the
building project. The owner shall retain the system manual and final commissioning report
described below. An electronic formatted copy of the final commissioning report shall be
provided to the Building Official.
The following commissioning activities shall be completed prior to issuance of a
permanent Certificate of Occupancy:
1 . Designate an approved project commissioning authority (CxA) to lead, review, and
oversee completion of the commissioning process activities .
2 . The owner, in conjunction with the design team as necessary, shall develop the
owner 's project requirements (OPR) to guide the CxA. The OPR will be distributed
to all parties participating in the project programming, design, construction, and
operations, and the commissioning team members .
3 . The design team shall develop the basis of design (BOD) .
4. The CxA shall review the both the OPR and BOD for clarity and completeness.
5 . Construction phase commissioning requirements shall be incorporated into project
specifications and other construction documents developed by the design team.
6 . Develop and implement a commissioning plan containing all required forms and
procedures for the complete testing of all equipment, systems, and controls included
in Section 3604 . 1 . 1 .
7 . Verify the installation and performance of the systems to be commissioned.
8 . Complete a final commissioning report satisfactory to the Building Official.
9 . Verify the owner requirements for training operating personnel and building
occupants are completed.
10 . Verify that a system manual in a form satisfactory to the Building Official has been
prepared. At a minimum, the system manual shall include operations and
maintenance documentation and full warranty information, and shall provide
operating staff the information needed to understand and operate the commissioned
systems as designed.
3604. 1 . 1 Systems. The following systems, if included in the building project, shall be
commissioned:
1 . heating, ventilating, air-conditioning, indoor-air-quality, and refrigeration systems
7
and associated controls ;
2 . building thermal envelope systems, components, and assemblies to verify thermal,
air, and moisture integrity;
3 . all lighting controls and shading controls ;
4 . service water heating systems ;
5 . renewable energy systems ; and
6 . background sound levels . "
Section 4 . That Section 5 -27 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Chapter 35 REFERENCED STANDARDS is hereby amended by adding the following
additional referenced standard in alphabetical sequence :
"CDPH California Department of Public Health
1615 Capitol Avenue
Sacramento, CA 95814
CDPH 01350 Standard Method for Testing VOC emissions from indoor sources
Referenced in Amended 09 IBC Section 3603.2 Maximum Allowable Background Sound in
Rooms"
"FSC Forest Stewardship Council U. S . (FSC-US)
212 Third Avenue North, Suite 504
Minneapolis, MN 55401 "
"GEI GREENGUARD Environmental Institute
2211 Newmarket Parkway, Suite 110
Marietta, GA 30067
GGPS . 00I . GREENGUARD IAQ Standard for Building Materials, Finishes and Furnishings
Referenced in Amended 09 IBC Section 3603.2 Maximum Allowable Background Sound in
Rooms"
"Green Seal®
1001 Connecticut Avenue, NW
Suite 827
Washington, DC 20036-5525
GS- I I Paintings and Coatings
GS-43 Recycled Content Latex Paints
Referenced in Amended 09 IBC Section 3603.2 Maximum Allowable Background Sound in
Rooms"
Section 5 . That all subsections in Section 5 -27 of the Code of the City of Fort Collins
are hereby renumbered in sequential order as they appear in the IBC .
8
Section 6 . That the requirements set forth herein above will be effective as to all
applications for building permits filed on or after January 1 , 2012 .
Introduced, considered favorably on first reading, and ordered published this 1st day of
March, A.D . 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
Passed and adopted on final reading on the 22nd day of March, A . D . 2011 .
Mayor
ATTEST :
City Clerk
9
ORDINANCE NO . 031 , 2011 ,
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE II, DIVISION 2 , OF THE CODE
OF THE CITY OF FORT COLLINS FOR THE PURPOSE OF
AMENDING THE 2009 INTERNATIONAL
ENERGY CONSERVATION CODE AS ADOPTED
WHEREAS, the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural
environment, reduced carbon emissions, reduced energy use and reduced water use, and;
WHEREAS , City staff has conducted a significant public outreach program, working
with three advisory committees comprised of representatives from the residential and
commercial construction industries, specialized-trade contractors, housing industry, real estate
and appraisal industries, construction recycling industry, and regional code officials; and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of
the amendments ; and
WHEREAS , on February 9 , 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Economic Advisory Commission, and the Economic Advisory Commission recommended
approval of the amendments ; and
WHEREAS , on February 16 , 2011 , the substance of the amendments was presented to
the Natural Resources Advisory Board, and the Natural Resources Advisory Board
recommended approval of the amendments ; and
WHEREAS , on February 17, 2011 , the substance of the amendments was presented to
the Water Board, and the Water Board considered water related elements and recommended
approval of those amendments ; and
1
WHEREAS , on February 24, 2011 , the substance of the amendments was presented to
the Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28, 2011 , the substance of the amendments was presented to
the Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS , based on input obtained through this outreach process, together with City
Council and advisory board review and comment, staff has developed proposed amendments to
the 2009 International Energy Conservation Code ("IECC") as set forth in this Ordinance ; and
WHEREAS , the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that IECC as adopted be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF FORT
COLLINS as follows :
Section 1 . That the opening paragraph contained in Section 5 -31 of the Code of the
City of Fort Collins is hereby amended to read as follows :
Sec. 5-31 . Amendments and deletions to code.
The 2009 International Energy Conservation Code adopted min § 5 -26 is hereby
amended in the following respects :
Section 2 . That Section 5 -31 of the Code of the City of Fort Collins is hereby amended
by the addition of a new subparagraph which reads in its entirety as follows :
Section 101. 4. 3. 1 is hereby added to read as follows :
" 101 .4.3. 1 Energy assessment. Prior to any alterations, an energy
analysis of the entire building shall be required and submitted to the
Building Official .
Exceptions : Energy assessments are not required in the following
cases .
1 . First-time interior finishes .
2 . A building that has undergone an energy assessment within the previous three
years .
3 . Alterations with a construction valuation of less than $30,000 . "
Section 3 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
2
Section 202 DEFINITIONS, is hereby amended to add the following definitions in
alphabetical sequence as follows :
"CONTINUOUS AIR BARRIER. The combination of interconnected
materials, assemblies, and flexible sealed joints and components of the building
thermal envelope that provides air tightness to a specified permeability.
ELECTRIC HEAT. An indoor environmental primary heat source that is electric . A
ground-source electric heat pump designed by a licensed professional engineer to operate
without the use of supplemental electric resistance heat shall not be considered electric
heat.
NON-ELECTRIC HEAT. An indoor environmental primary heat source that is gas or
that is a ground-source electric heat pump designed by a licensed professional engineer to
operate without the use of supplemental electric resistance heat. "
Section 4 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 401. 2 is hereby amended in its entirety to read as follows :
"401 .2 Compliance. Compliance shall be demonstrated by conforming with mandatory
Sections 401 , 402 . 2 . 12 , 402 .4, 402 . 5 , 403 , 1 , 403 .2 .2 , 403 . 2 . 3 , and 403 . 3 through 403 . 9 .
Section 5 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 402, TABLE 402. 1. 1 is hereby amended in its entirety to read as follows :
"TABLE 402. 1 . 1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT
HEATING FENESTRATION SKYLIGHT" GLAZED CEILING WOOD MASS FLOOR BASEMENT` SLABa CRAWL`
SYSTEM U-FACTOR" U-FACTOR FENESTRATION R-VALUE FRAME WALL R- WALL R- SPACE
TYPE SHGC WALL R- VALUEe R-VALUE VALUE WALL
R-VALUE VALUES & R-
DEPTH VALUE
Non- 0.35 0.60 NR 38 20 or 13/17 30 10/ 13 10, 2 10/ 13
electric 13+5f ft
heat
Electric 0.30 0.60 NR 49 20+5 15/19 30 15/ 19 10,4 15/ 19
heat I I ft
For SL• 1 foot + 304. 8mm
a. R-values are minimums. U-factors SHGC are maximums. R- 19 batts compressed into a nominal 2x6 framing cavity
such that the R-value is reduced by R- 1 or more shall be marked with the compressed batt R-value in addition to the full
thickness R-value.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
C. " 15/19" means R- 15 continuous insulation on the interior or exterior of the foundation wall or R- 19 cavity insulation at
the interior of the foundation wall. " 15/19" shall be permitted to be met with R- 13 cavity insulation on the interior of
the foundation wall plus R-5 continuous insulation on the interior or exterior of the foundation wall. "10/13" means R-
10 continuous insulation on the interior or exterior of the foundation wall or R- 13 cavity insulation at the interior of the
foundation wall.
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Or insulation sufficient to fill the framing cavity, R- 19 minimum.
3
f. " 13+5" means R- 13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25 percent or less of
the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more
than 25 percent of the exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.
g. The second R-value applies when more than half the insulation is on the interior of the mass wall.
Section 6 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 402 TABLE 402. 1. 3 is hereby amended in its entirety to read as follows :
"TABLE 402. 1 .3
EQUIVALENT U-FACTORSa
HEATING FENESTRATION SKYLIGHT CEILING FRAME MASS FLOOR BASEMENT CRAWL
SYSTEM U-FACTOR U-FACTOR R-VALUE WALL WALL U- WALL SPACE
TYPE U- U- FACTOR U-FACTOR WALL
FACTOR FACTOR` U-
FACTOR
Non-electric 0.35 0.60 0.030 0.057 0.082 0.033 0.059 0.065
heat
Electric heat 0.30 0.60 0.026 0.043 0.060 0.033 0.050 0.055
a. Non-fenestration U-factors shall be obtained from measurement, calculation or an approved source.
b. When more than half the insulation is on the interior, the mass wall U-factor shall be the same as the frame wall U-
factor."
Section 7 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 402. 2. 12 is hereby added to read as follows :
"402.2 . 12 Specific insulation requirements. All insulation shall be installed to meet
Residential Energy Services Network (RESNET) Grade I standard.
Exceptions : RESNET Grade II is acceptable for:
1 . cavity insulation in exterior walls that include continuous rigid insulating
sheathing and/or insulated siding with a minimum R-value of 5 ; and
2 , rim joists"
Section 8 . That Section 5 -31 of the Code of the City of Fort Collins is hereby amended by
the addition of a new subparagraph which reads in its entirety as follows :
TABLE 402. 4. 2 title is hereby amended to read in its entirety as follows :
"402.4.2 Air sealing verification. Building thermal envelope air tightness shall be
demonstrated to comply with either Section N1102 .4 .2 . 1 (new construction) or Section
N1102 .4 .2 .2 (existing buildings) :
402.4.2. 1 Performing testing. In new construction, air sealing compliance shall
be demonstrated through performance testing by an approved agency in accordance with
the methods and standards specified herein. Documentation of testing results shall be
submitted to the Building Official prior to receiving a Certificate of Occupancy. When
4
tested with a blower door at a pressure of 50 pascals (33 . 5 psf), the maximum building
thermal envelope air leakage rate shall not exceed:
1 . three air changes per hour (ACH) in buildings with electric heat; or
2 , four air changes per hour (ACH) in buildings with non-electric heat.
Isolation of attached garages from adjoining conditioned areas shall be verified
with an approved differential pressure test.
Testing shall occur after rough-in and after installation of penetrations of the
building thermal envelope, including but not limited to penetrations for utilities,
plumbing, electrical, ventilation and combustion appliances.
During testing :
1 . exterior windows and doors , fireplace and stove doors shall be
closed, but not sealed;
2 , dampers shall be closed, but not sealed, including exhaust, intake,
makeup air, backdraft, and flue dampers ;
3 , interior doors shall be open;
4, exterior openings for continuous ventilation systems and heat
recovery ventilators shall be closed and sealed;
5 , heating and cooling system(s) shall be turned off;
6 , heating, ventilating and air conditioning ducts shall not be sealed;
7 , supply and return air registers shall not be sealed;
8 , combustion air inlets shall not be closed or otherwise obstructed;
and
9 . garage doors to the exterior shall be closed.
402.4.2.2 Visual inspection. In additions or alterations to existing buildings, air-
sealing compliance shall be considered acceptable when the items listed in Table
N1102 .4 .2 , applicable to the method of construction, are field-verified. "
Section 9 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 402. 5 is hereby amended to read as follows :
"402.5 Maximum fenestration U factor and SHGC. The area-weighted average
maximum fenestration U factor permitted, using trade-offs from International
Residential Code Section N1102 . 1 . 3 or N1102 .4. 5 , shall be 0 .40 for vertical fenestration
and 0 . 75 for skylights. "
Section 10 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 403. 6 is hereby amended as follows :
5
11403.6 Heating and cooling systems. Heating and cooling systems shall be designed in
accordance with International Residential Code Section M1401 . 3 and performance will
be verified in accordance with International Residential Code Section M1507 .4 . "
Section 11 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 404. 2 is hereby added to read as follows :
"404.2 Occupant sensor controls. In multifamily buildings, occupant sensor controls
shall be provided to automatically reduce connected lighting power by not less than 50
percent during periods when occupants are not present in common corridors and common
enclosed stairwells .
Lighting in means of egress shall comply with the luminance or uniformity criteria
required by the International Building Code when occupied.
Exception : Automatic power reduction shall not be used to control battery back-
up emergency lighting and exit signage ."
Section 12 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 502. L is hereby amended by adding the following :
"502. 1 General. All insulation shall be installed to Residential Energy Services Network
(RESNET) Grade I standard.
Exception : RESNET Grade II is acceptable for cavity insulation in exterior walls
that include continuous exterior insulation as specified in Table 502 .2( 1 ) installed
to RESNET Grade I standard. "
Section 13 . That Section 5 -31 of the That Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
An exception to Section 502. 1. 1 is hereby added to read as follows :
"Exception : For buildings using electric heat at the power density of 1 . 5 Watts per
square foot or greater, building thermal envelope values in Table 502 .2(3 ), shall be
mandatory. "
Section 14 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
An exception to Section 502. 1. 2 is hereby added to read as follows :
"Exception : For buildings using electric heat at the power density of 1 . 5 Watts per
square foot or greater, building thermal envelope values in Table 502 .2(3 ), shall be
mandatory. "
6
Section 15 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
TABLE 502. 2(3) is hereby added to read as follows :
"TABLE 502 .2 (3)
BUILDING THERMAL ENVELOPE REQUIREMENTS FOR ELECTRIC HEAT
Opaque Elements Assembly Max. Insulation Min . R-Value
Roofs
Insulation Entirely above Deck U -0 . 039 R-25 . 0 ci
Metal Building U -0 . 035 R- 19 . 0 + R- 11 . 0 Ls
Attic and Other U -0 . 021 R-49 . 0
Walls , Above Grade
Massa U -0 . 080 R- 13 . 3 ci
Metal Building U -0 . 052 R- 13 . 0 + R- 13 . 0 ci
Steel Framed U -0 . 055 R- 13 . 0 + R- 10 . 0 ci
Wood Framed and Other U -0 . 051 R- 13 . 0 + R-7 . 5 ci
Wall , Below Grade
Below Grade Wall C-0 . 092 R- 10 . 0 ci
Floors
Mass U -0 . 064 R- 12 . 5 ci
Steel Joist U -0 . 032 R-38 . 0
Wood Framed and Other U -0 . 026 R-30 . 0 + R-7 . 5 ci
Slab-On -Grade Floors
Unheated F-0 . 540 R- 10 for 24 in .
Heated F-0 .440 R- 15 . 0 for 36 in . + R-5 ci below
Opaque Doors
Swinging U -0 . 400
Non-Swinging U -0 . 400
Fenestration Assembly Max. U
Vertical Fenestration , ( up to 40% of Wall
maximum )
U-0 . 25
Nonmetal framing : alIb U-0 . 35
Metal fr: curtainwall/stonefront° U-0 . 70
Metal framing : entrance door° U-0 .45
7
Metal framing : all other'
Skylight ( up to 3 % of Roof maximum ) Uaii-0 . 60
The following definitions apply: ci = continuous insulation, Ls = liner system, NR = No (insulation) requirement.
' Mass walls with a heat capacity greater than 12 Btu/fe-'F which are unfmished or finished only on the interior do
not need to be insulated.
b Nonmetal framing includes framing materials other than metal with or without metal reinforcing or cladding.
Metal framing includes metal framing with or without thermal break. The "all other" subcategory includes operable
windows, fixed windows, and non-entrance doors."
Section 16 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 502. 4. 3 is hereby amended by adding the following :
"502.4.3. 1 Design requirements . The building thermal envelope shall be designed and
constructed with a continuous air barrier that complies with the following requirements to
control air leakage into, or out of, the conditioned space . All air barrier components of
each building thermal envelope assembly shall be clearly identified on construction
documents and the joints, interconnections, and penetrations of the air barrier components
shall be detailed and comply with the following :
1 . The air barrier shall be continuous throughout the building thermal envelope (at the
lowest floor, exterior walls, and ceiling or roof), with all joints and seams sealed and
with sealed connections between all transitions in planes and changes in materials and
at all penetrations .
2 . The air barrier component of each assembly shall be joined and sealed in a flexible
manner to the air barrier component of adjacent assemblies, allowing for the relative
movement of these assemblies and components .
3 . The air barrier shall be capable of withstanding positive and negative combined
design wind, fan, and stack pressures on the air barrier without damage or
displacement, and shall transfer the load to the structure, and shall not displace
adjacent materials under full load.
4. The air barrier shall be installed in accordance with the manufacturer's instructions
and in such a manner as to achieve the performance requirements .
5 . Where lighting fixtures with ventilation holes or other similar objects are to be
installed in such a way as to penetrate the continuous air barrier, provisions shall be
made to maintain the integrity of the continuous air barrier.
502.4.3 .2 Compliance. Compliance of the continuous air barrier for the
opaque building thermal envelope shall be demonstrated by the following :
8
1 . Materials. Using air-barrier materials that have an air permeability not to
exceed 0 . 004 cfm/ft2 under a pressure differential of 0 . 3 in. water ( 1 . 57 lb/ft2)
(0 . 02 L/sam2 under a pressure differential of 75 Pa) when tested in accordance
with ASTM E2178 ;
2 . Assemblies . Using assemblies of materials and components that have an
average air leakage not to exceed 0 . 04 cfm/ft2 under a pressure differential of
0. 3 in. water ( 1 . 57 lb/ft2) (0. 02 L/sm2 under a pressure differential of 75 Pa)
when tested in accordance with ASTM E2357 or ASTM E1677 ;
3 . Building. Testing the completed building and documenting that the air
leakage rate of the building thermal envelope does not exceed 0 .25 cfm/ft2
under a pressure differential of 0 . 3 in. water ( 1 . 57 lb/ft2) (0. 02 L/s oM2 under a
pressure differential of 75 Pa) in accordance with ASTM E779 or an
equivalent approved method."
Section 17 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 505. 2. 2. 1 is hereby amended in its entirety to read as follows :
"505.2.2. 1 Occupant sensor controls. In new construction and additions that require a
building permit, occupant sensor controls shall be provided to automatically reduce
connected lighting power by not less than 50 percent during periods when occupants are
not present in the following locations :
1 . corriders and enclosed stairwells;
2 , storage stack areas not open to the public ;
3 , library stack areas; and
4 . parking garages.
Lighting in means of egress shall comply with the luminance or uniformity criteria
required by the International Building Code when occupied.
Exception : Automatic power reduction shall not be used to control battery back-
up emergency lighting and exit signage . "
Section 18 . That Section 5 -31 of the Code of the City of Fort Collins is hereby amended
by the addition of a new subparagraph which reads in its entirety as follows :
Section 505. 2. 3 is hereby amended in its entirety by adding the following :
"505.2.3 Sleeping unit controls. In hotels and motels with over 20 guest rooms, the
lighting switched outlets, permanently wired luminaires, television, and heating,
ventilating and air conditioning system equipment serving each guest room shall be
automatically controlled so that lighting, switched outlets, permanently wired luminaires,
and televisions will be turned off and the heating, ventilating and air conditioning system
9
set point raised at least 5 degrees Fahrenheit (3 degrees centigrade) in the cooling mode
and lowered at least 5 degrees Fahrenheit (3 degrees centigrade) in the heating mode
whenever the guest room is unoccupied.
505.2.3 . 1 Sleeping unit bathroom controls. All permanently wired luminaires located in
bathrooms within sleeping units in hotels, motels, boarding houses or similar buildings
shall be equipped with occupant sensors that require manual intervention to energize
circuits . "
Section 19 . That Section 5 -31 of the Code of the City of Fort Collins is hereby amended
by the addition of a new subparagraph which reads in its entirety as follows :
Section 505. 2. 4 is hereby amended in its entirety by adding the following :
"505.2.4 Exterior lighting controls. In addition to any other applicable requirements of
this IECC, all outdoor lighting controls shall comply with the following requirements : For
lighting of building fagades, parking lots, garages, canopies (sales and non-sales), and all
outdoor sales areas, automatic controls shall be installed to reduce the sum of all lighting
power (in Watts) by a minimum of 50 percent two hours after normal business closing and
to turn off outdoor lighting within 30 minutes after sunrise.
Exceptions .
1 . Lighting required by a health or life safety statute, ordinance, or regulation,
including but not limited to, emergency lighting.
2 . Lighting that is controlled by a motion sensor and photo-control.
3 . Lighting for facilities that have equal lighting requirements at all hours and are
designed to operate continuously.
4. Temporary outdoor lighting.
5 . Externally illuminated signs and signs that are internally illuminated or have
integral lamps . "
Section 20 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section 505. 8 is hereby added to read as follows :
"505.8 Electricity distribution design requirements and load type isolation . Electric
distribution systems within, on or adjacent to and serving a building shall be designed in
such fashion that each primary panel supplies only one electricity load type as defined in
Sections 505 . 8 . 1 through 505 . 8 . 5 . The energy load type served by each distribution panel
shall be clearly designated on the panel with the use served, and adequate space shall be
provided for installation of metering equipment or other data collection devices,
10
temporary or permanent, to measure the energy use associated with each distribution
panel.
Exceptions :
1 . Buildings with less than 15 ,000 square feet of floor area are exempted
from this requirement.
2 . Electrical systems that are designed and constructed in such fashion that
the total usage of each of the load types as described in Sections 505 . 8 . 1
through 505 . 8 . 5 shall be permitted to be measured through the use of
installed sub-meters or other equivalent methods as approved.
505.8. 1 Heating, ventilating, and air conditioning system electric load. This category
shall include all electricity used to heat, cool, and provide ventilation to the building
including, but not limited to, fans , pumps, and cooling energy.
505.8.2 Lighting system electric load. This category shall include all electricity for
interior and exterior lighting used in occupant spaces and common areas .
505.8.3 Plug loads. This category shall include all electricity use by devices, electric
appliances and equipment connected to convenience receptacle outlets .
505.8.4 Process loads. This category shall include all electricity used by any single load
associated with activities within the building, such as, but not limited to, data centers,
manufacturing equipment and commercial kitchens, that exceed 5 % of the total energy
use of the whole building. "
505.8.5 Miscellaneous loads. This category shall include all electricity use for all other
building operations and other operational loads . "
Section 21 . That Section 5 -31 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Chapter 6 REFERENCED STANDARDS is hereby amended by adding the following
additional referenced standard in alphabetical sequence :
"Under the heading of ICC :
IgCC PV 2- 10 International Green Construction CodeO. . . . . . . 609 . 3 "
"RESNETO Residential Energy Services Network, Inc .
P . O . Box 4561
Oceanside, CA 92052-4561
http : //resnet.us
RESNETO reference standard Grade I and Grade II Insulation"
Referenced in Amended 09 IECC Section 502. 1 General.
Section 22 . That all subsections in Section 5 -31 of the Code of the City of Fort Collins
are hereby renumbered in sequential order as they appear in the IECC .
11
Section 23 . That the requirements of Sections 3 , 4 , 5 , 6, 13 , 14 and 15 of this
Ordinance will be effective as to all applications for building permits filed on or after the
effective date of this Ordinance.
Section 24 . That the requirements of Sections 2 , 7 , 8 , 9, 10, 11 , 12, 16, 17, 18 , 19, 20
and 21 of this Ordinance will be effective as to all applications for building permits filed on or
after January 1 , 2012 .
Introduced, considered favorably on first reading, and ordered published this I st day of
March, A.D . 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
Passed and adopted on final reading on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
12
ORDINANCE NO . 032, 2011 ,
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE II, DIVISION 2 , OF THE CODE
OF THE CITY OF FORT COLLINS FOR THE PURPOSE OF
AMENDING THE 2009 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED
WHEREAS, the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural
environment, reduced carbon emissions, reduced energy use and reduced water use, and;
WHEREAS , City staff has conducted a significant public outreach program, working
with three advisory committees comprised of representatives from the residential and
commercial construction industries, housing industry, real estate and appraisal industries,
construction recycling industry, specialized-trade contractors, and regional code officials ; and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of
the amendments ; and
WHEREAS , on February 9, 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Economic Advisory Commission, and the Economic Advisory Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Natural Resources Advisory Board, and the Natural Resources Advisory Board
recommended approval of the amendments ; and
WHEREAS , on February 17, 2011 , the substance of the amendments was presented to
the Water Board, and the Water Board considered water related elements and recommended
approval of those amendments ; and
1
WHEREAS , on February 24, 2011 , the substance of the amendments was presented to
the Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28, 2011 , the substance of the amendments was presented to
the Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS, based on the input obtained through this outreach process, together with
City Council and advisory board review and comment, staff has developed proposed
amendments to the 2009 International Residential Code ("IRC") as set forth in this Ordinance;
and
WHEREAS , the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that the IRC as adopted be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF
FORT COLLINS as follows :
Section 1 . That the opening paragraph of Section 5 -30 of the Code of the City of Fort
Collins is hereby amended to read as follows :
Sec. 5-30 Amendments and deletions to code.
The 2009International Residential Code adopted hefeinin § 5 -26 is hereby amended in
the following respects :
Section 2 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section R303. 3 is hereby amended in its entirety to read as follows :
"R303.3 General. Mechanical ventilation systems shall be required as specified
hereunder.
R303.3 . 1 . Bathroom ventilation. Mechanical ventilation of bathrooms shall be
provided in accordance with Section M1507 . 3 . Ventilation air from the space
shall be exhausted directly to the outside.
R303.3 .2. Kitchen ventilation. Mechanical ventilation of kitchens shall be
provided in accordance with Section M1503 and Section M1507 . 3 .
R303.3 .3. Whole dwelling unit ventilation. Mechanical ventilation of the whole
dwelling unit shall be provided in accordance with Section M1507 .4 . "
Section 3 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
A new section is hereby added to read as follows :
2
"SECTION R324
RESOURCE EFFICIENCY
R324. 1 Construction waste management. A construction waste management plan,
acceptable to the Building Official, including recycling of concrete, wood, metals and
cardboard, is required at time of application for a building permit for new construction.
The construction waste management plan shall be implemented and conspicuously posted
on the construction site . Substantive changes to the plan shall be subject to prior approval
by the Building Official.
R324.3 Certified tropical hardwood. All tropical hardwoods used in new construction,
additions and alterations requiring a building permit, shall be certified by the Forest
Stewardship Council or other approved agency. Certification demonstrating compliance
shall be required with delivery of such materials and shall be available for inspection. "
Section 4 . That Section 5 -30 of the Code of the City of Fort Collins is hereby amended
by the addition of a new subparagraph which reads in its entirety as follows :
A new section is hereby added to read to read as follows :
"SECTION R325
INDOOR ENVIRONMENTAL QUALITY (IEQ)
R325. 1 Low-volatile organic compound (VOC) materials. Construction materials,
floor coverings and site-applied finishes, including sealants and adhesives, resilient
flooring, carpeting and pad, site-applied paints, stains and varnishes, structural wood
panels, hardwood veneer plywood, particle board and fiber board building products, and
insulation shall meet specified volatile organic compound (VOC) emissions limits in
accordance with California Department of Public Health (CDPH) 01350 ;
GREENGUARD Environmental Institute GGPS . 001 standard for building materials and
finishes ; and Green Seal® standards . Documentation demonstrating compliance be
required with delivery of such materials and shall be available for inspection. "
Section 5 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
A new section is hereby added to read as follows :
"SECTION R326
OUTDOOR ENVIRONMENTAL QUALITY (OEQ)
R326. 1 Exterior lighting. All exterior lighting fixtures associated with new
construction shall have the "Fixture Seal of Approval" from the International Dark-Sky
Association or meet equivalent criteria approved by the Building Official. "
Section 6 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
3
A new section is hereby added to read as follows :
"SECTION R327
OPERATIONS AND MAINTENANCE AND BUILDING OWNER EDUCATION
R327. 1 Operations and maintenance manual. A building operation and maintenance
manual, in a form satisfactory to the Building Official, shall be provided for the building
owner and/ or occupant at time of or prior to issuance of a Certificate of Occupancy. "
Section 7 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section R703. 8. 1 is hereby added to read as follows :
"R703 .8. 1 Fenestration installation. All fenestration installations shall be in
accordance with American Architectural Manufacturers Association (AAMA) Standards/
Specifications for Windows, Doors and Skylights and shall be supervised and inspected
by an individual certified as an Installation Master by Architectural Testing, Inc. (ATI),
or other approved agency. (Also see Section R612) "
Section 8 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1101. 2 is hereby amended in its entirety to read as follows :
"N1101 .2 Compliance. Compliance shall be demonstrated by conforming with the
requirements of the International Energy Conservation Code conforming with the
requirements of this Part IV — Energy Conservation. Climate Zone 5b shall be used in
determining the applicable requirements thereunder.
N1101 .2. 1 Electric heat. For buildings with electric heat, envelope
values in Tables N1102 . 1 and N1102 . 1 .2 shall be mandatory. "
Section 9 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1102, TABLE NII02. 1. 1 is hereby amended in its entirety to read as follows :
"TABLE N1102. 1 . 1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT
HEATING FENESTRATION SKYLIGHT" GLAZED CEILING WOOD MASS FLOOR BASEMENT` SLAB$ CRAWL`
SYSTEM U-FACTOR" U-FACTOR FENESTRATION R-VALUE FRAME WALL R- WALL R- SPACE
TYPE SHGC WALL R- VALUE R-VALUE VALUE WALL
R-VALUE VALUES & R-
DEPTH VALUE
Non- 0.35 0.60 NR 38 20 or 13/17 30 10/ 13 101 2 10/ 13
electric 13+5f ft
heat
Electric 0.30 0.60 NR 49 20+5 15/19 30 15/ 19 1054 15/ 19
heat ft
For SL• 1 foot + 304. 8mm
4
a. R-values are minimums. U-factors SHGC are maximums. R- 19 batts compressed into a nominal 2x6 framing cavity
such that the R-value is reduced by R- 1 or more shall be marked with the compressed batt R-value in addition to the full
thickness R-value.
b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
C. " 15/19" means R- 15 continuous insulation on the interior or exterior of the foundation wall or R- 19 cavity insulation at
the interior of the foundation wall. " 15/ 19" shall be permitted to be met with R- 13 cavity insulation on the interior of
the foundation wall plus R-5 continuous insulation on the interior or exterior of the foundation wall. " 10/13" means R-
10 continuous insulation on the interior or exterior of the foundation wall or R-13 cavity insulation at the interior of the
foundation wall.
d. R-5 shall be added to the required slab edge R-values for heated slabs.
e. Or insulation sufficient to fill the framing cavity, R- 19 minimum.
f. " 13+5" means R- 13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25 percent or less of
the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more
than 25 percent of the exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.
g. The second R-value applies when more than half the insulation is on the interior of the mass wall.
Section 10 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1102, TABLE N1102. 1 is hereby amended in its entirety to read as follows :
"TABLE N1102. 1
EQUIVALENT U-FACTORSa
HEATING FENESTRATION SKYLIGHT CEILING FRAME MASS FLOOR BASEMENT CRAWL
SYSTEM U-FACTOR U-FACTOR R-VALUE WALL WALL U- WALL SPACE
TYPE U- U- FACTOR U-FACTOR WALL
FACTOR FACTOR` U-
FACTOR
Non-electric 0.35 0.60 0.030 0.057 0.082 0.033 0.059 0.065
heat
Electric heat 0.30 0.60 0.026 0.043 0.060 0.033 0.050 0.055
a. Non-fenestration U-factors shall be obtained from measurement, calculation or an approved source.
b. When more than half the insulation is on the interior, the mass wall U-factor shall be the same as the frame wall U-
factor."
Section 11 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1102. 2. 12 is hereby added to read as follows :
"N1102.2 . 12 Specific insulation requirements. All insulation shall be installed to meet
Residential Energy Services Network (RESNET) Grade I standard.
Exceptions : RESNET Grade II is acceptable for:
1 . cavity insulation in exterior walls that include continuous rigid insulating
sheathing and/or insulated siding with a minimum R-5 value; and
2 . rim joists"
Section 12 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1102. 4. 2 is hereby amended to read as follows :
"N1102.4.2 Air sealing verification. Building thermal envelope air tightness shall be
demonstrated to comply with either Section N1102 .4 .2 . 1 (new construction) or Section
5
N1102 .4 .2 .2 (existing buildings) :
N1102.4.2. 1 Performance testing. In new construction, air sealing compliance
shall be demonstrated through performance testing by an approved agency in
accordance with the methods and standards of this Section. Documentation of
satisfactory testing results shall be submitted to the Building Official prior to
receiving a Certificate of Occupancy. When tested with a blower door at a pressure
of fifty (50) pascals (33 . 5 psf) , the maximum whole-building air leakage rate shall
not exceed:
1 . three air changes per hour (ACH) in buildings with electric heat; or
2 . four air changes per hour (ACH) in buildings with non-electric heat.
Isolation of attached garages from adjoining conditioned areas shall be verified
with an approved differential pressure test.
Testing shall occur after rough-in and after installation of penetrations of the
building thermal envelope, including but not limited to penetrations for utilities,
plumbing, electrical, ventilation and combustion appliances .
During testing :
I . exterior windows and doors, fireplace and stove doors shall be closed, but
not sealed;
2 , dampers shall be closed, but not sealed, including exhaust, intake,
makeup air, backdraft, and flue dampers ;
3 , interior doors shall be open;
4. exterior openings for continuous ventilation systems and heat recovery
ventilators shall be closed and sealed;
5 . heating and cooling system(s) shall be turned off;
6 , heating, ventilating and air conditioning ducts shall not be sealed; and
7 . supply and return air registers shall not be sealed.
8 , combustion air inlets shall not be closed or otherwise obstructed.
9 . garage doors to the exterior shall be closed.
N1102.4.2.2 Visual inspection. In additions or alterations to existing buildings,
air sealing compliance shall be considered acceptable when the items listed in
Table N1102 .4 . 2, applicable to the method of construction, are field-verified. "
Section 13 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1102. 5 is hereby added to read as follows :
"N1102.5 Maximum fenestration U factor and SHGC. For new construction
and additions that require a building permit, the area-weighted average
maximum fenestration U factor permitted using trade-offs from Section
6
N1102 . 1 . 3 or NI 102 .4 . 5 shall be 0.40 for vertical fenestration, and 0 . 75 for
skylights ."
Section 14 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section N1103. 6 is hereby amended as follows :
"N1103 .6 Heating and cooling systems. For new construction and additions that require
a building permit, heating and cooling systems shall be designed in accordance with
Section M1401 . 3 and performance shall be verified in accordance with Section M1309 . "
Section 15 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section M1309 is hereby added to read as follows :
"M1309 Performance verification. Installed heating, cooling and ventilation systems
shall be performance-tested by an approved agency and adjusted to operate within design
specifications, in accordance with ANSUACCA QI 5 -2007 HVAC Quality Installation
Specification. Documentation of results shall be submitted to the Building Official prior
to receiving a Certificate of Occupancy."
Section 16 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section M1401. 3 is hereby amended in its entirety to read as follows :
"M1401 .3 Heating and cooling system design. The design of heating and cooling
systems shall meet the requirements of this Section. Design documents shall be
submitted to the Building Official at the time of application for a building permit.
M1401 .3 . 1 Equipment sizing. Heating and cooling equipment shall be sized in
accordance with ACCA Manual S, based on design building loads calculated in
accordance with ACCA Manual J, or other equivalent methodology approved by the
Building Official, using thermal design parameters in Table NI 10 1 . 1 as amended. The
total equipment output capacity shall be between the following limits, as applicable for
the equipment type :
I . 95 % and 115 % of calculated system cooling load, for air conditioners and
heat pumps;
2 . 95 % and 125 % of calculated system cooling load, for heat pumps with winter
heating dominated requirements ;
3 . 100% and 140% of calculated system heating load, for warm air systems,
unless dictated by the cooling equipment selection; and
4. 100% and 115 % of calculated system heating load, for heating boilers .
Where no available equipment is within the applicable capacity limits, the next largest
nominal piece of equipment that is available may be used.
7
M1401 .3 .2 Room loads. Room-by-room design heating and cooling loads shall be
calculated.
Exception. Equipment replacement in an existing building.
M1401 .3 .3 Matched components. Air-conditioning, Heating and Refrigeration Institute
(AHRI) matched evaporators, condensing units and air handlers shall be required. "
Section 17 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section M1503. 1 is hereby amended to read as follows :
"M1503 . 1 Exception : Excluding range hoods serving gas ovens as required by Section
G2447 . 6, ,
d14r#iog .q ,.,, ,, .v hoods s�. , ii ,, .t i,o , o,,, , ;, oa to a ; s h ,, .o to the ,, , ta , ,, Misted and labeled
ductless range hoods shall not be required to discharge to the outdoors for which
mechanical or natural ventilation is otherwise provided. "
Section 18 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section M1507. 3 is hereby amended to read as follows, TABLE M1507 . 3 remains
unchanged:
"M1507.3 Exhaust ventilation. Kitchen exhaust systems that are vented to the outside
and bathroom mechanical exhaust systems shall be designed to have the capacity to
exhaust the minimum air flow rate determined in accordance with Table M1507 . 3 .
Exhausts shall have gravity dampers that close when the ventilation system is not
operating. Design documents shall be submitted to the Building Official at the time of
application for a building permit. Performance of installed mechanical ventilation
systems shall be verified in accordance with Section M1309 . "
Section 19 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section M1507. 4 is hereby added as a new section to read as follows :
"M1507.4 Whole dwelling unit ventilation. A mechanical exhaust system, supply
system, or combination thereof shall be installed for each dwelling unit to provide whole-
dwelling unit ventilation. Such system shall comply with Sections M1507 .4 . 1 through
M 1507 .4.4 .
M1507.4. 1 Whole dwelling unit ventilation rate. The mechanical ventilation
system shall provide outdoor air at no less than the rate specified in Table
M1507 .4. 1 . 1
8
TABLE M1507.4. 1 . 1
DWELLING UNIT VENTILATION AIR REQUIREMENTS, CFMI
CONDITIONED NUMBER OF BEDROOMS
FLOOR AREA
(square feet) 0- 1 2-3 4-5 6-7 > 7
< 11500 30 45 60 75 90
11501-31000 45 60 75 90 105
31001-41500 60 75 90 105 120
41501-61000 75 90 105 120 135
61001-7500 90 105 120 135 150
> 7, 500 105 120 135 150 165
1 .Equation M1507 .4 . 1 can be used as an alternative to Table M1507 . 4 . 1 . 1
Equation M1507.4. 1 : Qfan = O. OlAfloor + 7 . 5 (Nbr + 1 )
Where :
Qfa„ = fan flow rate in cubic feet per minute (cfm) .
Afloor = conditioned floor area in square feet (ft) .
Nbr = number of bedrooms ; not to be less than one.
M1507.4.2 System design. The design of the required whole-dwelling unit ventilation
system shall comply with the requirements of this Section. System design documents
shall be submitted to the Building Official at the time of application for a building permit.
M1507.4.2. 1 System type. The system shall consist of one or more supply or
exhaust fans, or a combination thereof, and associated ducts and controls .
Exhaust fans shall be permitted to be part of a mechanical exhaust system.
Outdoor air ducts connected to the return duct of a forced air furnace shall be
sized to provide adequate mechanical ventilation in accordance with ASHRAE
62 . 2 and shall meet the manufacturer' s requirements for minimum return air
temperature to the furnace heat exchange .
M1507.4.2.2 Outdoor air intakes. Outdoor air intakes shall have automatic
dampers that close when the ventilation system is not operating .
M1507.4.2.3 . Exhausts. Exhausts shall have gravity dampers that close when the
ventilation system is not operating.
M1507.4.2.4. Air circulation fan motors. Motors for air circulation fans used in
the ventilation system, rated at one-quarter horsepower or greater, shall meet at
least one of the following criteria:
1 . Where the furnace serves as an air handler for the ventilation
system, the furnace shall be certified as an "electrically Efficient
Furnace" by the Air-conditioning, Heating and Refrigeration
9
Institute (AHRI) .
2 . The blower motor shall be specified as a `Brushless DC" (BL or
BLDC) motor by the manufacturer.
3 . The blower motor shall be specified as `Brushless Permanent
Magnet" (BPM) motor.
4. The blower motor shall be specified as "Electronically
Commutated Motor" (ECM)".
5 . The blower shall meet equivalent criteria acceptable to the
Building Official .
M1507.4.2.5. System controls. The mechanical ventilation system shall be
provided with readily accessible and labeled controls that enable occupant
override.
M1507.4.2.6. Sound ratings for fans. Whole-dwelling unit ventilation fans shall
be rated for sound at a maximum of 1 . 0 sone, in accordance with the procedures
of the Home Ventilating. Institute (HVI 915, Procedure for Loudness Rating of
Residential Fan Products) .
Exception : Heating, ventilating and air conditioning air handlers and
remote-mounted fans need not meet sound requirements . To be considered
for this exception, a remote-mounted fan must be mounted outside the
habitable spaces, bathrooms, toilets and hallways, and there must be a
least 4 ft ( I m) of ductwork between the fan and the intake grille.
M1507.4.3 System installation. The installation of the whole-dwelling unit ventilation
system and equipment shall be carried out in accordance with the manufacturers ' design
requirements and installation instructions .
M1507.4.4 Performance verification. Performance of installed mechanical ventilation
systems shall be verified in accordance with Section M1309 . "
Section 20 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section G2406. 2 is hereby amended to read as follows :
"G2406.2 Prohibited locations. For new buildings and new appliances within
additions, natural draft appliances shall not be located within the building thermal
envelope or be located in a space where the only access to that space is from sleeping
rooms, bathrooms, toilet rooms, or storage closets.
Exceptions .
6 . Where natural draft appliances are located in an enclosed mechanical
room and sealed to air flow from adjoining conditioned area and the following
conditions are met:
a. The access to the mechanical room is through a self-closing,
10
gasketed door;
b. No other exhaust appliances are located within the mechanical
room;
c . The mechanical room is provided with outside combustion air as
specified in this code ;
d. The isolation of the mechanical room from adjoining conditioned
areas is verified with a differential-pressure test performed by an
approved agency;
e . Such natural draft appliances pass a combustion safety test under
worst-case depressurization conditions conducted by an approved
agency, in accordance with Building Performance Institute (BPI)
Technical Standards for the Heating Professional ; and
f. Documentation of satisfactory testing results are submitted to the
Building Official prior to receiving a Certificate of Occupancy.
7 . Natural draft fireplaces that pass a combustion safety test, under worst-
case depressurization conditions, conducted by an approved agency, in
accordance with the Building Performance Institute (BPI) Technical Standards
for the Heating Professional, prior to issuance of a permanent Certificate of
Occupancy."
Section 21 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section G2408. 1 is hereby amended by deleting the second paragraph and replacing it to
read as follows :
"Where natural draft appliances are replaced in existing buildings, such appliances shall
pass a combustion safety test under natural conditions, conducted by an approved agency
in accordance with the Building Performance Institute (BPI) Technical Standards for the
Heating Professional .
Such appliances shall also be combustion safety tested under worst-case depressurization
conditions, by an approved agency in accordance with Building Performance Institute
(BPI) Technical Standards for the Heating Professional. Should an appliance not pass
such test, a disclosure form reporting the test results shall be provided to the homeowner.
A copy of such disclosure form, signed by the homeowner, shall be submitted to the
Building Official prior to issuance of a Letter of Completion. "
Section 22 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section P2903. 2 is hereby amended to read as follows :
"P2903.2 Maximum flow and water consumption. The maximum water consumption
flow rates and quantities for all plumbing fixtures and fixture fittings shall be in
11
accordance with Table P2903 .2 and such fixtures shall be Environmental Protection
Agency (EPA) WaterSense® labeled fixtures . "
Section 23 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Section P2903. 2 TABLE P2903. 2 is hereby amended to read as follows :
"TABLE P2903.2
MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING
FIXTURES AND FIXTURE FITTINGSb
PLUMBING FIXTURE PLUMBING FIXTURE
OR FIXTURE FITTING OR FIXTURE FITTING
Lavatory faucet 1 .5 gpm at 60 psi
Shower heads 2.0 gpm at 80 psi
Sink faucet 1 .8 gpm at 60 psi
Water closet 1 .28 gallons per flushing cycle, with minimum MaP threshold of 350 grams
For SI: 1 gallon per minute (gpm) = 3 .785 L/m.
1 pound per square inch (psi) = 6.895 kPa
a. A handheld shower spray is also a shower head
b. Consumption tolerances shall be determined from referenced standards."
Section 24 . That Section 5 -30 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subparagraph which reads in its entirety as follows :
Chapter 44 REFERENCED STANDARDS is hereby amended by adding the following
additional referenced standards in alphabetical sequence :
"Add the following referenced title standard to ACCA;
ANSI/ACCA QI 5 -2007 HVAC Quality Installation Specification.
Referenced in Amended 09 IRC Section M1309 Performance verification
"ATI Architectural Testing, Inc .
130 Derry Court
York, PA 17406
Installation MastersTM Testing and Certification Program
Referenced in Amended 09 IRC Section R703.8. 1 Fenestration installation
"CDPH California Department of Public Health
1615 Capitol Avenue
Sacramento, CA 95814
CDPH 01350 Standard Method for Testing VOC emissions from indoor sources
Referenced in Amended 09 IRC Section R325. 1 Low-volatile organic compound
(VOC) materials."
"FSC Forest Stewardship Council U. S . (FSC-US)
12
212 Third Avenue North, Suite 504
Minneapolis, MN 55401 "
"GEI GREENGUARD Environmental Institute
2211 Newmarket Parkway, Suite 110
Marietta, GA 30067
GGPS . 00I . GREENGUARD IAQ Standard for Building Materials, Finishes and
Furnishings
Referenced in Amended 09 IRC Section R325 . 1 Low-volatile organic compound
(VOC) materials."
"Green SealO 1001 Connecticut Avenue, NW
Suite 827
Washington, DC 20036-5525
GS- I I Paintings and Coatings
GS-43 Recycled Content Latex Paints
Referenced in Amended 09 IRC Section R325 . 1 Low-volatile organic compound
(VOC) materials."
"HVI Home Ventilating Institute
1000 N Rand Rd, Ste 214
Wauconda, IL 60084 USA
HVI referenced standard HVI 915 , Procedure for Loudness Rating of Residential Fan
Products
Referenced in Amended 09 IRC Section M1507.4.2 .6. Sound ratings for fans."
"IDA International Dark- Sky Association
3225 N. First Avenue
Tucson, Arizona 85719
IDA fixture seal of approval (FSA) third-party certification for luminaires that minimize
glare, reduce light trespass, and don 't pollute the night sky.
Referenced in Amended 09 IRC Section R326. 1 Exterior Lighting."
"RESNETO Mortgage Industry National Home Energy Rating Systems Standards
Residential Energy Services Network, Inc.
P . O . Box 4561
Oceanside, CA 92052-4561
http : Hresnet.us
RESNETO reference standard Grade I and Grade II Insulation
Referenced in Amended 09 IRC Section N1102 .2 Specific insulation requirements."
Section 25 . That subparagraph (61 ) of Section 5 -31 of the Code of the City of Fort
Collins is hereby deleted in its entirety as follows :
13
"
1%11401 .3 Sizing and testing. Heating and eooli � A I A 4 shall be sized based ofl.
methodologies . The total sensible eapaeity of the cooling equipment shall not exee-e
total sensible lead by mofe than 15 petvent for- eoofing only appfie4ions ; of by fflofe
dueted aif distfibution heating and cooling systems shall be sized using eooling loads . All.
applieable- pfotoeols established by the building official and ifl. aeeofdanee- with the
ehanieal eode adopted by the City. "
Section 26 . That all subsections in Section 5 -31 of the Code of the City of Fort Collins
are hereby renumbered in sequential order as they appear in the IRC .
Section 27 . That the requirements of Sections 8 , 9 and 10 of this Ordinance will be
effective as to all applications for building permits filed on or after the effective date of this
Ordinance .
Section 28 . That the requirements of Sections 2 through 7 inclusive and I I through 25
inclusive of this Ordinance will be effective as to all applications for building permits filed on or
after January 1 , 2012 .
Introduced, considered favorably on first reading, and ordered published this 1st day of
March, A.D . 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
14
Passed and adopted on final reading on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
15
ORDINANCE NO , 0335 2011
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE IV OF THE CODE OF THE CITY OF FORT
COLLINS FOR THE PURPOSE OF AMENDING THE 2009 INTERNATIONAL
MECHANICAL CODE AS ADOPTED
WHEREAS, the City Council has determined that it is the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural
environment, reduced carbon emissions, reduced energy use and reduced water use, and;
WHEREAS , City staff has conducted a significant public outreach program, working
with three advisory committees comprised of representatives from the residential and
commercial construction industries, housing industry, real estate and appraisal industries,
construction recycling industry, specialized-trade contractors, and regional code officials ; and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of
the amendments ; and
WHEREAS , on February 9 , 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Economic Advisory Commission, and the Economic Advisory Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Natural Resources Advisory Board, and the Natural Resources Advisory Board
recommended approval of the amendments ; and
WHEREAS , on February 17 , 2011 , the substance of the amendments was presented to
the Water Board, and the Water Board considered water related elements and recommended
approval of those amendments ; and
1
WHEREAS , on February 24, 2011 , the substance of the amendments was presented to
the Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28, 2011 , the substance of the amendments was presented to
the Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS, based on the input obtained through this outreach process, together with
City Council and advisory board review and comment, staff has developed proposed
amendments to the 2009 International Mechanical Code ("IMC") as set forth in this Ordinance;
and
WHEREAS , the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that the IMC as adopted be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF
FORT COLLINS as follows :
Section 1 . That the opening paragraph of Section 5 - 107 of the Code of the City of
Fort Collins is hereby amended to read as follows :
Sec. 5-107 Amendments and deletions to code.
The 2009International Mechanical Code adopted heroin in § 5 - 106 is hereby amended in
the following respects :
Section 2 . That Section 5 - 107 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subsection (8) which reads in its entirety as follows :
(8) Section 202 GENERAL DEFINITIONS, is hereby amended to add the following
definitions in alphabetical sequence as follows :
"MULTIFAMILY. Any building housing group R- 1 , R-2 or R-4 occupancies .
Section 3 . That Section 5 - 107 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subsection (9) which reads in its entirety as follows :
(9) Section 407 is hereby added to read as follows :
"SECTION 407 WHOLE-DWELLING UNIT VENTILATION.
407. 1 Whole-dwelling unit ventilation compliance . A mechanical exhaust system,
supply system, or combination thereof shall be installed for each dwelling unit to provide
whole-dwelling unit ventilation. Such system shall comply with Sections 407 . 1 . 1 through
407 . 5 .
2
407. 1 . 1 Whole-dwelling unit ventilation rate. The mechanical ventilation system
shall provide outdoor air at no less than the rate specified in Table IRC
M1507 .4. 1 . 1 ,
TABLE 407. 1 . 1 . 1
DWELLING UNIT VENTILATION AIR REQUIREMENTS, CFMI
CONDITIONED NUMBER OF BEDROOMS
FLOOR AREA
(square feet) 0-1 2-3 4-5 6-7 > 7
< 11500 30 45 60 75 90
11501-31000 45 60 75 90 105
31001-41500 60 75 90 105 120
41501-61000 75 90 105 120 135
61001-7500 90 105 120 135 150
> 7, 500 105 120 135 150 165
1 . Equation M1507 . 4 . 1 can be used as an alternative to Table M1507 . 4 . 1 . 1
Equation M1507.4. 1 : Qfa„ = O. OlAfloor + 7 . 5 (Nbr + 1 )
Where :
Qfan = fan flow rate in cubic feet per minute (cfm) .
Afloor = conditioned floor area in square feet (ft) .
Nbr = number of bedrooms ; not to be less than one.
407.2 System design. The design of the required whole dwelling unit ventilation system shall
comply with the requirements of this Section. System design documents shall be submitted,
as required by the Building Official, at the time of application for a building permit.
407.2 . 1 System type. The system shall consist of one or more supply or exhaust
fans, or a combination thereof, and associated ducts and controls . Exhaust fans
shall be permitted to be part of a mechanical exhaust system. Outdoor air ducts
connected to the return duct of a forced air furnace shall be sized to provide
adequate mechanical ventilation in accordance with ASHRAE 62 .2 and shall meet
the manufacturer' s requirements for minimum return air temperature to the
furnace heat exchange .
407.2.2 Outdoor air intakes. Outdoor air intakes shall have automatic dampers
that close when the ventilation system is not operating.
407.2.3. Exhausts. Exhausts shall have gravity dampers that close when the
ventilation system is not operating.
407.2.4 Air Circulation fan motors. Motors for air circulation fans used in the
ventilation system, rated at one-quarter horsepower or greater, shall meet at least
one of the following criteria:
3
1 . Where the furnace serves as an air handler for the ventilation
system, the furnace shall be certified as an "electrically Efficient
Furnace" by the Air-conditioning, Heating and Refrigeration
Institute (AHRI) .
2 . The blower motor shall be specified as a `Brushless DC" (BL or
BLDC) motor by the manufacturer.
3 . The blower motor shall be specified as "Brushless Permanent
Magnet" (BPM) motor.
4. The blower motor shall be specified as "Electronically
Commutated Motor (ECM)" .
5 . The blower shall meet equivalent criteria acceptable to the
Building Official.
407.2.5 System controls. The mechanical ventilation system shall be provided
with readily accessible and labeled controls that enable occupant override.
407.2.6 Sound ratings for fans. Whole-building ventilation fans shall be rated
for sound at a maximum of 1 . 0 sones, in accordance with the procedures of the
Home Ventilating. Institute (HVI 915, Procedure for Loudness Rating of
Residential Fan Products) .
Exception : Heating, ventilating and air conditioning air handlers and
remote-mounted fans need not meet sound requirements . To be considered
for this exception, a remote-mounted fan must be mounted outside the
habitable spaces, bathrooms, toilets and hallways, and there must be at
least 4 ft ( 1 m) of ductwork between the fan and the intake grille.
407.3 System installation. The installation of the whole-dwelling unit ventilation system
and equipment shall be carried out in accordance with the manufacturers ' design
requirements and installation instructions .
407.4 Performance verification. Performance of installed mechanical ventilation
systems shall be verified in accordance with International Residential Code Section
M 1309 . "
407.5 Multifamily buildings. In multifamily buildings, all doors between dwelling units
and common hallways shall be gasketed or otherwise substantially airtight with weather
stripping, except when the ventilation system explicitly requires transfer air from
corridors into units . "
Section 4 . That Section 5 - 107 of the Code of the City of Fort Collins is hereby
amended by renumbering subsections 8 through 17 accordingly.
Section 5 . That the requirements will be effective as to all applications for building
permits filed on or after January 1 , 2012 .
4
Introduced, considered favorably on first reading, and ordered published this 1 st day of
March, A.D . 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
Passed and adopted on final reading on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
5
ORDINANCE NO , 0345 2011
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE IV OF THE CODE OF THE
CITY OF FORT COLLINS FOR THE PURPOSE OF AMENDING THE
2009 INTERNATIONAL FUEL GAS CODE AS ADOPTED
WHEREAS , the City Council has determined that it is the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural
environment, reduced carbon emissions, reduced energy use and reduced water use, and;
WHEREAS , City staff has conducted a significant public outreach program, working
with three advisory committees comprised of representatives from the residential and
commercial construction industries, housing industry, real estate and appraisal industries,
construction recycling industry, specialized-trade contractors, and regional code officials ; and
WHEREAS , based on the input obtained through this outreach process, together with
City Council and advisory board review and comment, staff has developed proposed
amendments to the 2009 International Fuel Gas Code ("IFGC") as set forth in this Ordinance;
and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of
the amendments ; and
WHEREAS , on February 9, 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Economic Advisory Commission, and the Economic Advisory Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Natural Resources Advisory Board, and the Natural Resources Advisory Board
recommended approval of the amendments ; and
WHEREAS , on February 17, 2011 , the substance of the amendments was presented to
the Water Board, and the Water Board considered water related elements and recommended
approval of those amendments ; and
1
WHEREAS , on February 24, 2011 , the substance of the amendments was presented to
the Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28, 2011 , the substance of the amendments was presented to
the Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS, the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that the IFGC as adopted be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF
FORT COLLINS as follows :
Section 1 . That the opening paragraph of Section 5 - 112 of the Code of the City of
Fort Collins is hereby amended to read as follows :
Sec. 5-112 Amendments and deletions to code.
The 2009 International Fuel Gas Code adopted min § 5 - 111 is hereby amended in
the following respects :
Section 2 . That subparagraph (7) contained in Section 5 - 112 of the Code of the City
of Fort Collins is hereby amended to read as follows :
(7) Piwhibikod EleletiHgENGeptiORS « » an
�—'. "303 .3 Prohibited locations. For new buildings and new appliances within
additions, natural draft appliances shall not be located within the building
thermal envelope or be located in a space where the only access to that space is
from sleeping rooms, bathrooms, toilet rooms, storage closets, or surgical rooms.
Exceptions .
1 . Where natural draft appliances are located in an enclosed mechanical
room and sealed to air flow from adjoining conditioned area and the
following conditions are met:
a. The access to the mechanical room is through a self-closing,
gasketed door.
b. No other exhaust appliances are located within the mechanical
room.
c . The mechanical room is provided with outside combustion air as
specified in this code .
d. The isolation of the mechanical room from adjoining conditioned
areas is verified with a differential-pressure test performed by an
approved agency.
e . Such natural draft appliances pass a combustion safety test under
worst-case depressurization conditions conducted by an approved
2
agency, in accordance with Building Performance Institute (BPI)
Technical Standards for the Heating Professional.
f. Documentation of satisfactory testing results are submitted to the
Building Official prior to receiving a Certificate of Occupancy.
2 . Natural draft fireplaces that pass a combustion safety test under worst-
case depressurization conditions conducted by an approved agency, in
accordance with the Building Performance Institute (BPI) Technical
Standards for the Heating Professional. , prior to receiving a Certificate of
Occupancy. "
Section 3 . That Section 5 - 112 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subsection ( 10) which reads in its entirety as follows and all
subsequent subsections renumbered accordingly:
(10) Section 305 . 1 General is hereby amended by adding the following paragraphs :
"Where natural draft appliances are replaced in existing buildings, such appliances shall
pass a combustion safety test under natural conditions, conducted by an approved agency
in accordance with the Building Performance Institute (BPI) Technical Standards for the
Heating Professional . .
Such appliances shall also be combustion safety tested under worst-case depressurization
conditions, by an approved agency in accordance with Building Performance Institute
(BPI) Technical Standards for the Heating Professional. . Should an appliance not pass
such test, a disclosure form reporting the test results shall be provided to the homeowner.
A copy of such disclosure form, signed by the homeowner, shall be submitted to the
Building Official prior to issuance of a Letter of Completion. "
Section 4 . That Section 5 - 112 of the Code of the City of Fort Collins is hereby
amended by the addition of a new subsection which reads in its entirety as follows :
Chapter 8 REFERENCED STANDARDS is hereby amended by adding the following
additional referenced standard in alphabetical sequence :
BPI - Building Performance Institute
107 Hermes Road, Suite 110
Malta, NY 12020
BPI 104 Envelope Professional Standard
Referenced in Amended 09 IFGC Section 303 .3 Prohibited locations and Section 305. 1
General
BPI Technical Standards for the Heating Professional
Referenced in Amended 09 IFGC Section 303 .3 Prohibited locations and Section 305. 1
General
3
Section 5 . That the requirements will be effective as to all applications for building
permits filed on or after January 1 , 2012 .
Introduced, considered favorably on first reading, and ordered published this 1 st day of
March, A.D. 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
Passed and adopted on final reading on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
4
ORDINANCE NO , 035 , 2011
OF THE COUNCIL OF THE CITY OF FORT COLLINS
AMENDING CHAPTER 5 , ARTICLE V OF THE CODE OF THE CITY OF FORT
COLLINS FOR THE PURPOSE OF REPEALING THE UNIFORM PLUMBING CODE
AND ADOPTING A LOCAL AMENDMENT TO THE COLORADO PLUMBING CODE
TO ESTABLISH WATER FLOW RATE RESTRICTIONS ON CERTAIN FIXTURES
WHEREAS , the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens to better align Fort Collins ' built environment with
community goals of improved indoor environmental quality, protection of the natural
environment, reduced carbon emissions, reduced energy use and reduced water use, and;
WHEREAS , City staff has conducted a significant public outreach program, working
with three advisory committees comprised of representatives from the residential and
commercial construction industries, housing industry, real estate and appraisal industries,
construction recycling industry, specialized-trade contractors, and regional code officials ; and
WHEREAS , on February 2 , 2011 , the substance of the amendments was presented to the
Electric Board, and the Electric Board recommended approval of the amendments ; and
WHEREAS , on February 3 , 2011 , the substance of the amendments was presented to the
Affordable Housing Board, and the Affordable Housing Board recommended against approval of
the amendments ; and
WHEREAS , on February 9 , 2011 , the substance of the amendments was presented to the
Landmark Preservation Commission, and the Landmark Preservation Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Economic Advisory Commission, and the Economic Advisory Commission recommended
approval of the amendments ; and
WHEREAS , on February 16, 2011 , the substance of the amendments was presented to
the Natural Resources Advisory Board, and the Natural Resources Advisory Board
recommended approval of the amendments ; and
WHEREAS , on February 17 , 2011 , the substance of the amendments was presented to
the Water Board, and the Water Board considered water related elements and recommended
approval of those amendments ; and
1
WHEREAS , on February 24, 2011 , the substance of the amendments was presented to
the Building Review Board, and the Building Review Board ; and
WHEREAS , on February 28, 2011 , the substance of the amendments was presented to
the Air Quality Advisory Board, and the Air Quality Advisory Board ; and
WHEREAS, based on the input obtained through this outreach process, together with
City Council and advisory board review and comment, staff has developed proposed
amendments to the 2009 International Plumbing Code as amended and adopted by the State of
Colorado pursuant to Title 12 , Article 58 , of the Colorado Revised Statutes (the "Colorado
Plumbing Code" or "CPC") to adopt local water flow rate restrictions on certain fixtures, as set
forth in this Ordinance; and
WHEREAS, the City Council has determined that it is in the best interests of the health,
safety and welfare of the City and its citizens that the CPC as adopted by the State of Colorado
be amended.
NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF
FORT COLLINS as follows :
Section 1 . That Section 5 - 125 of the Code of the City of Fort Collins is hereby
amended to read as follows :
Sec. 5- 125. Adoption of standards.
Pursuant to the authority conferred by Article 11, Section 7 of the Charter and Section 31 - 16-
2021 C .R. S . , there is hereby adopted by the City for the purpose of providing for the protection of
public health and safety and for the purpose of regulating the installation, alteration or repair of
plumbing and drainage systems in the City that certain code known as the Colorado Unifo
Plumbing Code, 3 Colorado Code of Regulations 720- 1 , 1 nn�tion, as published by saalv1ethe
appendices,
and except such portions as are hereafter deleted, modified or amended by § 5 - 126. The
plumbing code is adopted and incorporated as fully as if set forth at length herein and the
provisions shall be controlling within the City.
Section 2 . That Section 5 - 126 of the Code of the City of Fort Collins is hereby
deleted .
The Unifofm Plumbing Code adopted in § 5 125 is hereby amended to read as follows :
n Ceetiein 20. 2
is amended
by adding
pai4s (g) and (h) to vend as follows .:
11 1
Yl(yL t MpY.l 1 •lied .&OF of it 1n ffi.Ae d. at the pr-oyisiAmft; o •1h0 14n
4fAYN'.
2
Plumbing
(cede do not
apply or that the
trice intent and meaning of the rode has
anneal siieh deeision to the Colorado Examining Board of Dlufnbevs as pfovided
fof itt Section 12 58 104 . 5 , C .R. S .
11 (h) To Whom Permits May Be issued No permit shall be issued to any person to do �r
to eause t6 be, done plumbing of dr uge 3ATOfk Fegula4ed by the ! the
eity and the Code adopted hefeby except to a pefsovt 121 holding n valid masts
plumbefI
pt!ovided in this /
Sectio�€f 3itT€quit!ed by the Code of citymay be
� C1 Celled �!1 any pefs IN to Elo any plumbing
l m i It of Elfa nags wofl/ feg la4eE y thPC 1 ode, o
the eity in a single family dwelling used exclusively fot! 11 f1cluding
^g
et��that�. ]•��� the bona occupant of any sued
eity' s watef mains which senTe only fife pt!otection systems afe not 3A ratet! setvice.
lines of building
supplies as
Ele fi 'L the,
TN4form Plumbing
l mbi g I ode . Dp l l•1 •'�' s AOf
fife pfotection 3ATatef supply lines may be issued to a duly licensed specialty
supply is tapped fFom the fife litte, that portion of the piping fFom the pf!opet!ty line
II
"Any
1 AyFefson eorp eofation who shall violate any of the pvo%x 7101 ok" . f this Code.of the city II
e . r
11
traps ,
when sueh
systems . "
d . SeMOH 30. 4 (a), Schedule of-ftes, is amended by adopting the fee sehedule as set
7 Fees , of the Beilding Cede of the 7
the minimum fee f6f any peffnit fegulated hefein shall not be less than fifteen dollafs
(S15 . ) , and a pefmit f6r- a lawn iffigation system supplied ffom a siiigle dwelliiig unit
shall be fifteen dollars ($ l 5 1
(2) Can O ] 0
7 (n) is amended to read as follows :
11 1 / (� 11 �-y� L 1 1 1
'Y Zoning
g of
the eity and
is •lr(�he f a led fop f] esentatiy
( ) Ce6lj(9 708 (A) iS am e�� � �� +A read as Tll�llAWArS : ill 1 � 11/1 � �111 J .
11
sand, )
gfease of othef eontafflinafits shall be installed
in aeeordanee with the eify' s « Taber Utility speeifieatiens fof siieh devices '—"
( 4 ) Cep OH 711
is amended to rend as follows -
3
" Grease 1
for such
uc devices . "
11
11 '
(a) New const-fuetion inter4of
ng. All new water- consuming fixtufes in builitings
shall meet the
fol ASS in.9 roAlllrom o rAc+ •
11 j
7�) gallons per- flush
exeept that water- elesets and u6nals with t4tish Nzalves may be installed;
11
(2) Shower- heads shall contain flow contfol inserts, valves, devices or orifices t
YOP�Y1 / � TIASSI tA A MnNimllm AT Appr-ex mately three
13 \ gal A" o Hpr m1N11te •
11 Kitehen and !a-vator-y faueets shall have aerators or- laminaf flow deviees toge
with
TTAv Contfol ifisefts,
valves, ediees of
vrirr
ees at fes tfIC�t T
vw t6zc
maximum AT appFAvlmately two (2) gallons per- minute
11
(b) Existing buildings in existing buildings of! 1TATThich plumbing fixtufes af!e
eo'"nservation tkevIees .
Section 3 . That a new Section 5 - 126 is hereby added to Article V of Chapter 5 of the
Code of the City of Fort Collins, as follows :
Sec. 5426 Amendments and deletions to code.
The Colorado Plumbing Code as adopted is hereby amended in the following respects :
(1) Section 604 TABLE 604. 4 is hereby amended as follows :
"Section 604.4 Maximum flow and water consumption. The maximum water consumption
flow rates and quantities for all plumbing fixtures and fixture fittings shall be in accordance with
Table 604 .4 and such fixtures shall be Environmental Protection Agency (EPA) WaterSense®
labeled fixtures . "
"SECTION 604
TABLE 604.4
MAXIMUM FIXTURE AND FITTING FLOW RATES FOR REDUCED WATER
CONSUMPTION
PLUMBING FIXTURE PLUMBING FIXTURE
OR FIXTURE FITTING OR FIXTURE FITTING
Lavatory,private 1 .5 gpm at 60 psi
Lavatory, public (metering) 0.25 gallon per metering cycle
Shower head 2.0 gpm at 80 psi
4
Sink faucet 1 .8 gpm at 60 psi
Urinal 0.5 gallons per flush
Water closet 1 .28 gallons per flushing cycle, with minimum MaP threshold of 350 grams
Prerinse Spray Valves Must meet federal requirements
(food service industry)
Bar sinks 2.2 gpm at 60 psi
(food service industry)
For SI: 1 gallon per minute (gpm) = 3 .785 L/m.
1 pound per square inch (psi) = 6.895 kPa
a. A handheld shower spray is also a shower head
b. Consumption tolerances shall be determined from referenced standards.
Section 4 . That the requirements of this Ordinance will be effective as to all
applications for building permits filed on or after January 1 , 2012 .
Introduced, considered favorably on first reading, and ordered published this 1st day of
March, A.D. 2011 , and to be presented for final passage on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk
Passed and adopted on final reading on the 22nd day of March, A.D . 2011 .
Mayor
ATTEST :
City Clerk