HomeMy WebLinkAboutBuilding Review Board - Minutes - 10/26/1989amumm REVn1 BOARD
October 26, 1989
is rya•. ••ia.a •,. -
ID r'a•a
Ule minutes of the September 28, 1989 meeting were unanimously approved.
Class B license applicants, Rex lapehire and Robert William Mesenw for
Alley Oonstivction, were present at the meeting. Mr. ra pshire stated he was
the job superintendent on the Color Tile stare. On some of the other Oolor
Tile stores, he acted as assistant superintexlent, handling more than half of the
and the work dale to existing railroad tracks. Mr. Messner
explained he acts as the architect and the general contractor on all projects
listed. He was the superintendent c n most of them. In sore cases, as he
Proposes to do in Fort Oollins, he hires a superintendent to run the job. He
has hired Class B certificate holder, Paul McWilliams. Mr. Messner plans on
being the project manager and will be on the jab two to three times a week .
After answering quesstic s from several of the boardmmloers, both were unani-
mously approved for licenses.
Appeal #01-89 - Fire Board of Appeals
304 W. Prospect, Henry Glisan, Owner - Sections 10.306 and such other sections
as applicant may apprise the Board at hearing; UFC Standard 10-2.
Request - To have confirmed that an automatic fire alarm system need not be
installed, because the UPC does not (or should not be interpreted to) require
the ramie with regard to the subject property, or, alternatively, because suitable
alternatives exist. Mitigating Factors: Several of the subject apartment
buildings neither rise three stories in height nor contain more than 15
apartrments. The varying densities of the subject buildings make strict
application of the UFC irrational and arbitrary. Smoke detectors, different
types of alarm systems, and/or ladders and or other escape means provide a
suitable alternative. Applicant reserves the right to present further mitigating
factors at hearing.
0
Mr. Rick Zier, Attorney, represented H. C. Glisan
acccu anted by Mr. Nix, who tends the buildings a
Glisan was not at the meeting.
t
at the meeting. He was
Prospect Plaza. Mr.
Mr. Zier submitted as evidence Poucdre Fire Authority Fire Inspection Report
dated July 25, 1989; pictures from the location; and read frcam the attached
documents.
Summarizing the appeal, Mr. Zier felt PC udre Fire Authority has the burden to
prom that there is a "distinct" hazard by riot providing an automatic fire
alarm system, as stated in Section 1.103(b). In his opinion, they have not at
this time proved it.
The apartments were built in 1964 and were in Connformanoe at that time. Mr.
Glisan built the apartments and is still the owner. There has never been a
reported fire in any of the twelve buildings. Nine of the buildings have
sixteen units which subjects them to Pc udre Fire Authority law. Three of the
, 1 ings have twelve units and alarm requirements don't apply to them.
There are three levels; one garden level which does not constitute a "story" as
defined in the Uniform aalding CUcde; a middle story which is five feet above
grade; and an upper story standing fourteen feet above grade. The appellant's
claim is that none of the buildings are three stories in height, but are 2 - 1/2
stories. Mr. Zier's oorntentim is the Uniform Fire Code fails to provide
information such as distance to an exit (there should be a differenoe on an
interior hall if the door to an apartment was five feet frDDh an exit or forty
feet F an exit) , unit dimensions and n ater of occupants, which could vary
the degree of danger.
Mr. Zier stated all buildings are equipped with fire extinguishers and have low
pitch roofs. The overhead wires between the buildings that have made it
difficult for Poudre Fire Authority access have been installed underground.
The overhead cable for T.V. will be installed underground by June 1, 1990. A
new two inch water main has been installed for auxiliary water source. All
curtains have been reTaved and non-flammable blinds installed. No hot plates
are allowed nor spaoe heaters. No storage of flammable liquids is allowed.
All wiring is in metal conrhuit and all boxes are metal. Range hoods have
been removed. All units have new electric stoves. All units and stairways
have escape windows. Wide fire lanes are on both long ends of each building.
Mr. Zier maintains there is no need to discuss suitable alternatives; the
apartments themselves are alternatives.
Mike Gavin, Assistant Fire Marshal, presented a pacdmt of bacgrcnld informa-
tion to the Board and Mr. Zier at the meeting. Mr. Gavin said in 1983, the
1982 Uniform Fire Code and amentnents were adopted by the City of Fort
Collins and included the section regarding installation of auutanatic fire alarm
systems. In 1984, the chief, after examining national fire trends determined
that apartment buildings and hotels with interior corridors as the primary
means of emergency escape were a distinct hazard to life and as such must
comply with the new edition of the Ctxde.
0
Boazdmenber Johnson asked if there were any reported fires in similar build-
ings without alarm. Mr. Gavin names several including the Aspen leaf Apart-
ments, Cambridge AparbaNft, and Stadium Fast Apartments. He said alarms
saved peoples lives at the Aspen Taaf Apartment and the Stadium East Apart-
ment where the fires occurred in the night.
Boardmenber Cotterman asked if the building were to be built today, would it
require an alarm. Mr. Gavin said yes.
BoartInedber Bcnta asked if there were fourteen or fifteen apartments, and
Poud a Fuze Authority felt there was a hazard, could they require an alarm?
Mr. Gavin answered according to Section 1.103(b), yes they could. Mr. Bentz
brought up the earthquake in San Francisoo that had occurred just last week.
In this case when the road was designed, it met code, but because it wasn't
updated to prevent standards, there was a disaster and many people lost their
lives.
Boardmenber Cutteroan asked if the party walls between the units and the
hallways are fire rated. Mr. Zier didn't know. Director of Building Permits
and Dmpec'icns, Felix lee, said in 1964 there would not have been fire ratirq
requirements for the party walls, based on the 1961 Edition of the Uniform
B ildim Code, but the corridars and doors of the apartments would have been
required to be one hour fire rated.
Mr. Zier said he thinks the walls are ccstar-tern of 2 x 4's and 5/8" drywall.
Mr. Cotten= questioned whether this was assumed or fact since there are no
plans on the buildings. Mr. lee stated if Type X gypsum was used, it would
be one hour fire rated, but not having the plans, it would be hard to tell.
Mr. Zier said he hadn't thought to bring it up but there are smoke detectors in
plane, the small batter operated ones. Mr. Vincent asked if they are inspected
regularly and are records kept on the inspections. Mat are the locations of
the alarms? Mr. Zier said he had no facts on alarms.
Felix lee told the Board it was their job in this appeal to interpret whether
alternative means exist and are sufficient.
Boardnabber Baker said he agreed with Mr. Zier in the fact that government
shouldn't be allowed to put obstacles in the path of business for no apparent
reason. He does feel, however, that it is clear in Section 1.103(b) that if it is
a distinct hazard in the opinion of the chief, he has the right to require the
alarms. Therefore, he would vote to deny the appeal.
Boardmerber Bontz agreed with Boardnenber Baker and will vote to deny. He
pointed cut the law was not applied suddenly: evidence shows the owner has
fought the change for five years.
Boardamber Allison felt it would be outrageous if there was a fire and the
building didn't ccnply. He was involved in the Stadium Fast Apartment fires
and said it was a case of fire breaking cut uben everyone was asleep. The
smoke was so thick that people couldn't find the exits. There was an alarm
0
9 Nc- - =AV
system that worked well and probably saved lives. Mr. Allison felt the cost of
installing a system is not cut of line and said he would vote to deny the
variance.
•. - _. . MIM
Class A certificate applicant, Dale A. Fraser, was approved as a certificate
holder for PC L 03mtruction.
In reviewing Ray Spender's application for a Class C-02 license/certificate,
boob_ M bens didn't see any Class C-02 e>pPXien oe. He dial provide them with
Class D experience. Boardmember Johnson made a motion to approve Mr.
SPencer for a Class D lime/certificate, but deny the Class C-02 iuntil further
references were submitted. nie motion was seconded by Boardnember Guerrie.
Motion carried unanimously.
Uanas C. Lloyd, Lloyd Cwpany (ogstructors was approved for a Class D
lip/certificate.
Jim Buchanan, R. Burch Construction, was approved for a Class E license/
certificate with waiver of testing approved based on testing in Cheyerme,
Colorado Springs, and Aurora.
'Ihe next meeting will be held on November 30 at 9:15 a.m. in the Council
ncil
Chambers. Appeal #02-89 will be heard and Fbudre Fire Authority will pre-
sent amendments to the 1988 Uniform Fire Code. Me meeting was adjourned.
Respectfully submitted,
Felix Lee, f Liaison
0 !
HARDEN, SCHMIDT, HASS & ZIER, P.C.
ATTORNEYS AT LAW
NINTH FLOOR, FIRST TOWER BUILDING, P.O. BOX 1606, FORT COLLINS, COLORADO 80522
TELEPHONE (303) 482-7777 TELEFAX (303) 482-8084
Ralph B. Harden
H. Ted Schmidt, Jr.
George H. Hass
Richard F. Zier
d/b/a Pr ect tts
Appeal of H. C. Glisan f Prospect Plaza Apartments
S.
Jeannine a Haag
Marla R . HeHaag
Richard M. Stillwell
Before the Fort Collins Fire Board of Appeals
PP
Michael A. Abram:. u
John N. Lefler
October 26, 1989
Law
Section 10.306(a), UFC (1985 Ed.): "An approved automatic fire alarm system shall be
installed in the following occupancies: 1. Apartment houses three or more stories in
height or containing more than 15 apartments."
Section 1.103(b): "The provisions of this code shall apply to existing conditions as well as
to conditions arising after the adoption thereof, except that conditions legally in
existence at the adoption of this code and not in strict compliance therewith shall be
permitted to continue only if, in the opinion of the chief, they do not constitute a
distinct hazard to life or property."
Nonconforming conditions are permitted, unless the chief considers them a "distinct
hazard",
"Distinct" — "presenting a clear unmistakable impression"; "notable"; "readily
perceptible". [Webster's New Collegiate Dictionary]
The burden is on the fire authority to state and show a distinct hazard where there is a
nonconforming condition. This has not occurred here. (The fact that there are
apartment buildings at Prospect Plaza with 16 units does not mean they constitute a
distinct hazard — as non -conforming buildings, they would be legal even if they had 500
units as long as there was no distinct hazard. The number of units does not automatically
correlate to a hazard.)
The fire inspector simply considers any nonconformity with the UFC to be a violation.
This is patently incorrect. The fire inspector has a discretionary function: He can, and
should, determine whether something is or is not a distinct hazard. His failure to do so
here has resulted in damages to the owner in terms of application fee, professional
advice, and loss of time from work, among other things.
Prospect Plaza is placed in the awkward position of having to deny the existence of a
distinct hazard which has not been specified and about which it has no notice. This is, at
the least, a violation of the constitutional guarantee of due process, and it amounts to a
capricious enforcement of the Uniform Fire Code.
The charge of this Board is to determine the suitability of alternate materials and type
of construction and to provide for reasonable interpretations of the Fire Code. The
application form calls for the appellant to list "mitigating factors", but this is not
required by the Fire Code or the Code of the City of Fort Collins.
stes � ,rc Office m Assooahon wdn Hallberg & Brown. P.O. Box 3018. 201 1st National Bank Bldg., Estes Park, CO 80517 Telephone (303) 586A474
The proper focus of the Board should be on the interpretation of the Code concerning
height of the subject apartment buildings, and whether, under the facts and mitigating
circumstances, the 16-unit buildings could reasonably be considered a "distinct hazard".
"Story" -- (UBC) As defined, the garden level of each of these buildings is not to be
considered a story, because the floor level of the middle level in each building is not
more than six feet above grade (it is approximately five feet above grade).
"Height of Building" -- (UBC) This is measured from the highest adjoining sidewalk or
ground surface within five feet of exterior wall. The implication is clearly that height of
buildings is measured from the ground. Thus "three stories in height", as used in Section
10.306(a), must be interpreted as meaning three stories from (above) the ground.
"First Story" — A level will not be considered a first story if, for more than 50% of its
perimeter, its floor level is more than four feet below grade. This may well be the
situation at Prospect Plaza.
Facts and Mitigating Circumstances
The apartment buildings were in full conformance with all applicable fire and building
codes at the time of their construction in 1964. The apartments have never, to the
owner's knowledge (the current owner is the same person who built the complex), had a
reported fire.
Prospect Plaza features 12 separate apartment buildings. Three of the buildings contain
12 units, and nine of the buildings contain 16 units. Sixteen is the least possible number
of units which can subject an apartment building to the UFC requirement. (Increase in
simple risk from 15 units to 16 units is .066.)
Each building has three levels. The floor level of the bottom level is approximately four
feet below grade (in places more), and this level is called the garden level. The floor
level of the middle level is approximately five feet above grade, and the floor level of
the upper level is approximately 14 feet above grade.
The exterior perimeter dimensions and interior square footage of the 12-unit and the 16-
unit buildings are identical.
There are 180 units in the complex: 71 two -bedroom units, 37 one -bedroom units, and 72
buffet (efficiency) units. In a 12-unit building, there are six two -bedroom units (two on
each floor) and six one -bedroom units (two on each floor). In a 16-unit building, there are
six two -bedroom units, two one -bedroom units, and eight buffet units. On the first floor
of a 16-unit building, there are two two -bedroom units and two one -bedroom units
(identical to a 12-unit building). On the middle floor and the third floor of a 16-unit
building, there are two two -bedroom units and four buffet units each.
The difference between the 12-unit and 16-unit buildings is that in the latter the same
space which two one -bedroom units would occupy on each of the middle and upper floors
is instead occupied by four buffet units (the space for one one -bedroom unit is the same
as the space for two buffet units).
-2-
There is no automatic, or even apparent, correlation — without more — between
detection of fire and number of units. Similarly, there is no automatic, or even apparent,
correlation -- without more -- between the probability of adequately receiving warning
of fire and number of units. Any presumption in the UFC of the existence of such bald
correlations is unfounded, arbitrary and irrational. The UPC fails to provide necessary
indicia in order to be able to be rationally applied, e.g., specifying unit dimensions, or
fixing numbers of units in particular levels, or providing specific requirements for
particular building designs. By not so doing, irrationality, inconsistency and arbitrariness
are not only invited, but inevitable.
Each building is only 54 feet long (exterior dimension). The interior hallways are
straight, with no curves. There are staircases at either long end, and so the length of the
interior hallways is considerably less than the exterior length of the buildings, being less
than 40 feet.
In the 16-unit buildings, the doors to only two units on each of the middle and upper
floors are located near the middle of the hallway -- and those doors are less than 20 feet
from a stairway. The other doors on those floors are located adjacent to the stairways.
Average occupancy of Prospect Plaza is one person per bedroom. (For example, Prospect
Plaza is currently fully leased. Of the 71 two -bedroom units, there are two with one
resident, 65 with two residents, three with three residents, and one with four residents.
Thus, there are 145 persons occupying 142 bedrooms, or 1.0211 people per bedroom. Of
the 37 one -bedroom units, 31 have one resident, and six have two residents. Therefore,
there are 43 persons occupying 37 bedrooms, or 1.1621 people per bedroom. Of the 72
buffet units, 72 are occupied by one resident, and this is an average of 1.0000 people per
bedroom -- the owner does not permit more than one person in each buffet. The total
complex features 260 people in 251 bedrooms, or 1.0358 people per bedroom.)
The highest occupant density (people/bedroom) is in the one -bedroom units. The lowest
occupant density is in the buffet units.
Although each buffet unit does have a kitchen, a buffet unit is much safer than a one -
bedroom or a two -bedroom unit, because (1) the occupant will necessarily detect a fire
starting in the kitchen area more readily and more quickly than persons in the separate
bedrooms in one -bedroom or two -bedroom units, and (2) the occupant can exit from a
buffet to the hall more easily and quickly.
One -bedroom and two -bedroom units are not only less safe than buffet units in the event
of kitchen fire, but there are more people, both per unit and per bedroom, to evacuate
from such units as there are with buffet units.
None of the 12-unit buildings features buffet units. Those buildings could contain three
more units (and these could be one -bedroom or two -bedroom units) and still not trigger
the Fire Code requirement for alarm systems. The 16-unit buildings, however, have eight
buffet units, and each of them is safer than a one -bedroom or a two -bedroom unit. Thus,
the 16-unit unit buildings, because fully half of the units are buffets, are, as constructed,
much safer than a 151mit building which would feature one -bedroom and two -bedroom
apartments (and which would not require an automatic alarm system under the UFC).
-3-
All of the apartment buildings are brick/celotex (no plywood in walls). Celotex is 25/32"
All of the apartment buildings have fire extinguishers which are regularly tested, refilled
and certified.
There are wide fire lanes on both long ends of each building.
All roofs are low pitched, which means a slower rate of fire spread and permits easier
fire -fighting access to them.
All units (rooms) have escape windows. All stairways have escape windows.
The owner has recently installed a new 2" water main to the commercial building on the
property, which is available as an auxiliary water source in the event of fire.
As of one year ago, there are no longer any draperies in any of the buildings (entirely
replaced by nonflammable blinds).
No storage of flammable liquids is allowed. No hot plates are allowed. No space heaters
are allowed. Owner inspects at regular intervals for compliance (every unit).
All wiring in the building is in metal conduit. All boxes are metal.
All range hoods have been removed -no fans or grease filters.
All units have new (electric) stoves.
There is no combustible landscaping or any other combustible material around the
exterior of any of the buildings (entirely paved).
The small size of the buildings, the location of the doors near stairways, the easy, fast,
and close access to all the apartments, and the rapid response time of fire units
satisfactorily mitigate concerns having to do with occupants receiving warning of fire.
The owner of Prospect Plaza recently negotiated with the City of Fort Collins to have
the City remove its electric lines from the poles between the two rows of apartment
building. This was done in August, 1989, and the lines were placed underground. The
owner is now in negotiations concerning the remaining telephone and cable TV wires, and
they will be removed together with the poles by June 1, 1990.
Access to the complex is excellent (directly off of both Prospect Street, a major arterial,
and Lake Street, which goes through all the way from College Avenue, a major arterial,
on the east to Shields Street, a major arterial, on the west).
There are fire hydrants in close proximity to the property, both on Prospect Street (one
is on the property line, less than 35 feet from the first apartment building) and on Lake
Street.
The location is very near the Spring Creek Fire Station, and responding units need only go
west two blocks on Spring Creek Drive, north three blocks on College Avenue, and west
two blocks on Prospect Street.
-4-
Conclusion
None of the 12 buildings is three or more stories in height.
Three of the buildings contain only 12 apartments, and so they are entirely immune from
the UFC automatic alarm system requirement.
The remaining 9 buildings do not, in consideration of the many significant mitigating
factors, constitute a distinct hazard to life or property, and so the expressly permitted
nonconforming status of them under the UFC should continue.
-5-
Fire Prevention Bureau
�IorEMINGTON
/ L�O 102 COLLINS,
uc FORT COLLINS, COLO. 80524
s" 303-221-6570
T0: Fort Collins Fire Board of Appeals
FROM: Mike G. Gavin, Assistant Fire Marshal
RE: Fire Code Appeal for Prospect Plaza Apartments
DATE: October 23, 1989
ISSUE: Prospect Plaza Apartments of 304 West Prospect Street is
appealing an installation of an automatic fire alarm system
requirement pursuant to Section 10.306(a),(b),(c), (d) and (e)
of the 1985 Uniform Fire Code as adopted and amended by the
City of Fort Collins. The Appellant operates an apartment
complex at this location which comes under these requirements,
but is not in compliance of said Code. The owner of Prospect
Plaza Apartments, r1r. H.C. Glisan, has not complied with the
section of this Code nor has he submitted for approval plans
for such system, or submitted for approval suitable
alternatives as described in the Uniform Fire Code.
STAFF
RECOMMENDS: Staff recommends that the Board deny the appeal and require
that an automatic fire alarm system needs to be installed.
BACKGROUND: In 1983, the 1982 Uniform Fire Code and amendments was adopted
by the City of Fort Collins included the Section regarding
installation of automatic fire alarm systems. This was a new
requirement in the published Code developed by the Western
Fire Chiefs Association and the International Conference of
Building Officials. As applied to existing buildings, the UFC
does not have a "grandfather" clause but allows the chief to
continue the use of existing situations even though they are
not in compliance with the current code, if a distinct hazard
to life or property does not exist. In 1984, the Chief,
after examining national fire trends determined that apartment
buildings and hotels with interior corridors as the primary
means of emergency escape were a distinct hazard to life and
as such, must comply with the new edition of the Code.
Uniform Fire Code, Section 1.103(b)
The provisions of this code shall apply to
existing conditions as well as to conditions
arising after the adoption thereof, except that
conditions legally in existence at the adoption
of this code and not in strict compliance
therewith shall be permitted to continue only if,
in the opinion of the chief, they do not
constitute a distinct hazard to life or property.
PROTECTING LIVES & PROPERTY
Attachments
cc: John Mulligan
Felix Lee
John Duval
After the adoption of this Code, Poudre Fire Authority began
working with building owners who had buildings which fell into
this category to install proper alarm systems. As of this
time, there are nine buildings in this complex that are
required to comply with this section. These buildings have
16 units on three floors as garden level apartments.
In October 1984, we began working with the management and
owners attempting to have this property come into compliance
with the UFC. Due to many delays, refusals, and change of
ownership, this property is still not in compliance, nor have
any approved exceptions been presented, reviewed or accepted
by Poudre Fire Authority.
There are battery operated smoke detectors located in several
areas in these buildings, but their operation cannot be
guaranteed due to lack of a monitor system. These detectors
do not alert the entire floor or entire building of a possible
life threatening situation. Due to center hallway exiting,
there is only one approved exit per apartment and there is no
approved exit directly to the outside from floors other than
the lower garden level (window exits).
Since this Code was adopted, we have experienced fires in
apartments where approved automatic fire alarm systems have
been installed. These systems functioned correctly as
intended and we believe this has been a major contributing
factor in the prevention of fire loss including injuries and
deaths.
2
POUDRE FIRE AUTHORITY
INSPECTION POLICY 84-4
FIRE ALARMS IN APARTMENTS AND HOTELS
Section 10.307 (a) requires that apartment buildings and hotels meeting the following
criteria be equipped with an approved fire alarm system unless specifically
exempted. An approved system should include provisions for automatic detection
and manual operation in interior corridors and automatic detection in storage
rooms, laundry rooms, furnace rooms and similar common areas.
C:RITFRTA
Apartment buildings three (3) stories or more in height or containing 15 or more
apartments.
Hotels three (3) or more stories in height or containing more than 20 guest rooms.
EXCEPTIONS
1) Apartment buildings and hotels not over two stories in height with direct
exits from each dwelling unit to a yard or public way and one hour separation
between each dwelling unit from basement to roof.
2) Special PFA exception for all apartment buildings and hotels with direct
exits from each dwelling unit or guest room to a yard or public way.
RETROFIT POLICY
It will be the PFA policy to only require retrofit alarm systems in apartment
buildings or hotels with interior exit hallways if the building meets either one
of the first two criteria. This is because buildings with direct outdoor exits present
less hazard and the operational problems associated with alarming buildings with
no common areas.
DATE
s
Lo.R
-'m.
E^?•+�So
s Ez
S Q p .T m n= A u V m? �_—, D 7 o v 3- n C •O -O v n= O^
C�N_aOmes 79
=["=�°
0= O m ei is S R 6 n S d 3- m rtn 9 „K,. �1 C
^ d m N O m- if S O W
y ,°.,� y 3• H !? °: — n n N " W— O S m^ A O,
W o� C) u n O
o m n` o y d n c
O e n= n 0 O m G �. n o �' •m rt $. IOC 0 ,< o
0 O- •J N f O>> ' R m- a
K= .ei
c'N917
m O 3 O •p n O O
._,
o� = rn e d W c� ° is e � � � r"i •°. £ o° C m �`_^' `.c E -' a n
n
D
w y
n `< d'C 'm0 9 4
n w 4 RO
Z w m m G
rt 3 w = A = 3 >
o c 0_�
�.nmm
F.w too
=
7
n3
sm3o z
eo.m
Zm._
OAo
�^^nye3H <
Pi -m
m n
s
W
O
'i
n , e
7 ��
m .'p
z
�G
Cmb
c N
c
Mn
H N
°
3
n•r7 =Oo
t' E.
SKv
wp
NON^S�
-i0^y=69.GW
N
y
NR� 9S
dW 6�W m..l
6"j,OC
n n
°=^�I
1�
n•m0
x 0°
n A C
^ 6 �' N .Q
O
M
S n C. 6 A
n
m
4-
m
n n
m n O
= N=
a 7
^ ^ C N W S N
N 3
Z
^ 9 O O w n y
FrG n
^ �'
c
n
9k'nHR.F3�'
_
o' Nc
�N
3na^9,'^N
^Ns+-n'
� ��0
G
W
=
O
n 8 ==
3 3 ^
3 N
Y F
n
°' m
9 o e 3
'4
N n
F, n W
c o
=
p
ry N
n^ o
mso>m
'c3
m
�ce3a
w3HN
�W°Nj
^9=
`a
� �
C
^
muo
O
.nm.. a
�::t
3w'
3 �(��
Ov-' F m N
=< E.
'�
�o
n�R
<>ripc
<<, •a90
<c
O^
it -m=mn
^n
a-'.m.
oG
m
onNo'o.=°
n�
z^
O m«
°:
W 6g
N
n
nS=..Nn
._
o.N
n 3 n(�c
n n
n
na
.N
c„m^� no.
d
os°
o ^a
^ 3
ii Z
�_^
= o _c.9 °'
c.
e 3
n
o
_ o
F.o ,?
n
nO A
= O
S d O,
N O^
O' f^� rvm� n
y
C C'
m •^�
'-' -Oj •<
30•
w
O� �Fi
nn
C DN
C1
^9mD=NY
prt
�6
Cvne;^O
O
u
m D
90 n m
a v
E O
^
n•,� '
c c
�C
� >OO
n m
n
u
==
wF
0.�
H
a
m�
N
6� 9 3 y
^
i
<nOpS6=
!� � m O H O =
N
-O• � n
`t
3n�
b S 6 O
21
Fr
F, w
F l
v o
�—
•
POUDRE FIRE
AUTHORITY
•
FIRE
INSPECTION
DOCUMENT
FORM
w.ruo nr nneTXlrCC ADDRESS PERSON CONTACTED
DATE TIME COMMENTS
INSPECTOR
!"� r f St•� CEE Cam" NtT !!-<)-
t15 OO
/�
���
�:'� 14 �^ _�tiT WCT LtS
pwL
- A U �' L►Q-
_ � �
� 7
, ` .
�: �Lr t r ` 1 ��.� _ ♦^ �,.._,__ : �• • c Gam, �
G
k-5-er� v F
r.
7e c-- of wk-.
,
v- .n-i I.'..cwT �c c t -S 5 v c{J •- lttl� �..,�< I Gk t
1, hTA^< Oi 1E C-ii c��:I �
:4T
lev:,
1
� V\ 4� r c" t o-
KA-c,
L
I
-/
AMSWEk ALL QUESTIOMS: •
1. What did we see on arrival?
2. What did we do?
3. What were the results7
4. Were there any unusual factors involved?
I issued a summons to Michael Nix, manager of Prospect Plaza apts. This was
necessary for non-compliance of. sec. #10.301 of the Uniform Fire Code 1985 ed.
The buildings at 250-315 W. Prospect st. are required to have an approved fire
alarm system installed. We have been attempting to achieve compliance since
October of 1984. The owner,Mr. Ken Grady, lives in Littleton and has ignored
numerous deadlines and meetings to clear this violation from the books.
Log of contacts made:
- *October 16, 1984.
Letter sent to Mr. Grady stating one year to comply.
*September 4, 1985
Company inspection
*October 10,1985
Company Re -inspection
*September 8•, 1986
Company inspection
*October 4, 1986 .
Company re -inspection
*January 16, 1987
Letter to Mr. Grady stating 30 days to establish a timeline for
compliance:
*February 2, 1987
Reply from Mr. Grady setting up a meeting on 2/11/87 @ 1330.
*February 16, 1987
Letter from Mr. Grady stating he would call to set up a meeting
when he was in Ft. Collins. Also stating to contact Mike Nix for
business that needs immediate attention.
*April 21, 1987
Company inspection
*April 21, 1987
Mr. Grady and Mr. Nix met with Rob Weber of the Poudre Fire
Authority Fire Prevention Bureau. It was stated that Chadwick
Electric would start installation of the alarm system on
May 18, 1987.
*February 23, 1988
I talked to Mike Nix on the phone. He said Mr. Grady would be
in Ft. Collins on thursday 2/25/88.
*February 25, 1988
Cashier at desk said Mr. Grady had been in Ft. Collins on 2/24/88.
*February 26, 1988
Talked to Mr. Grady on the phone. Meeting set up for 3/3/88 @ 1330
*March 3, 1988
Mike Nix called to cancel appointment. Another meeting set for
3/10/88 @ 1330.
*March 3, 1988
I confirmed appointment with Mr. Grady by phone.
*March 4, 1988
Letter sent to Mr. Grady confirming appointment.
*March 10, 1988
Mike Nix called to say that Mt: Grady could not make appointment
because of bad weather.
*March 10, 1988
Mr. Grady called to say he could not make it but Mike Nix was his
representative.
*March 23, 1988
Letter sentse•tting deadline for a contractual agreement by 5/1/88.
*April 6, 1988
Reply stating a plan that Mr. Grady. had come up with that would
not comply.
*April 11, 1988
Letter stating specific requests for contracts and plans by 5/9/88
*April 25, 1988
Reply stating Chadwick Electric would be doing the work.
*May 12, 1988
Met with Mr. Chadwick. He submitted a bid to Mr. Nix on 5/5/88.
*May 12, 1988
Met with Mike Nix, he stated that no bid had been received.
*May 12, 1988 I issued a summons to Mr. Nix.
1311
/V?
6 8co
131 S
Z zs AJ,,q. of 78(-'(7YT
jz-z5 A).A. 4� 781-Y7Y7
To
/(A2e�iA1 se'f u� A.'ar (33a a-r
P/'csp2<T �o z a 301 W . �✓bspec-�.
3 ' 3 /n ; ke /J ix C,9,//ed fa Ca-n ce (
ca-ase ge.,
t as/eea( M(- Io re�,Ceol�le a_
ih„is_ 3-/6-88
3-fy
A
-f� aj)p ,,rf
A,are .
apP-- ¢ar
.Sa ri ear l l eo/ % f �Q r �o en Gera% �i �� ��• 7 y
/fi2e�i •r9 .
Lkc. Ni'c (l�l 4,0 SOS. �� � Ire Grady
Rd Ii6 ,!Lf" 2/e�k n) Z24--a vat of
lQd
A, Grady ca///mil A �j. Ae
here ie/r
POUDRE FIRE AUTHORITY FIRE INSPECTION REPORT
102 REMINGTON STREET
FT. COLLINS, COLORADO 80524 — PHONE: 221-6570
E OF BUSINESS _
F,8=C'r
ADDRESS.- j
BUSINESS HONFr,, •.
T i`- .FT`5
(_} t't T�r ..
-� 7
COORDIp5TE ,
MA�AGER' NAME
MANAGER'S HOME PHONE
.
FINAL NOTICE
Yo rar,had in excess of days,tg�correct the violations noted on the fire inspection conducted on
•r You have an additional ! n business days to take one of the following courses of action:
` (-TEN
(1) Correct the violation(s).
(2) Contact Inspector 11,1� G AA/ i r11 at 221-6570 or in writing at the above address and
request that a schedule for bringing all noted violations into compliance be established. All reasons for this re-
quest must be clearly stated and will be considered by the Fire Prevention Bureau representative.
(3) Appeal these violations in writing (pursuant to U.F.C. section 2-302) to the Fire Board of Appeals. An applica-
tion for appeal must be obtained from the Fire Marshal's office, Poudre Fire Authority, 102 Remington St., Fort
Collins, CO. 80524. The purpose of the appeals board is to "determine the suitability of alternate materials and
type of construction and to provide for reasonable interpretations of" the Uniform Fire Code.
If any one of these steps is not taken, a summons to appear in Municipal/County Court may be issued.
For any questions regarding this notice, please contact the inspector listed above at 221-6570.
I INlenooccrcn Vnnl eTtnnie
UFC SECTIONv
r v I
rl
X DATE DATE: i/--r' COMPANY/ ` PAGE OF
PROTECTING LIVES & PROPERTY
WHITE • Business Representative YELLOW: Fire Inspection Coordinator
r v I
rl
X DATE DATE: i/--r' COMPANY/ ` PAGE OF
PROTECTING LIVES & PROPERTY
WHITE • Business Representative YELLOW: Fire Inspection Coordinator
POUDRE FIREIRUTHORITY FIRE INSECTION REPORT
505 PETERSON STREET
FT. COLLINS, COLORADO 80524 - PHONE: 484-4220 Ext. 200
NAME OF BUSINESS
ADDRESS ^'
__.
BUSINESS PHONS. -
TYPE OF OCCUPANCY
BUILDINGOWNER— J
MANAGER'S NAME:
MANAGER'S HOME PHONE
OWNF,R'SADDRESS(CITY A STATED. -
A. FIRE PROTECTION
YES
o
(
Coordinate %- " ' !
Time
Point Value
1 SPRINKLER SYSTEM
VALVE LOCATION
FIRE DEPT. CONN. LOCATION
t STANDPIPES
LOCATION OF F.D. CONN.
S ALARMS
TYPE
A EXTINGUISHERS IN ORDER
S FIRE SYSTEM MAINTENANCE
6 FIRE DOORS ADEQUATE A IN ORDER
YES
MIA
1 ADDRESS VISIBLE
2 EXIT WAYS ADEQUATE A IN ORDER
S EXIT LIGHTS ADEQUATE A IN ORDER
a STAIRWAYS ADEQUATE 6 IN ORDER
5 DECORATIVE MATERIAL
6 PROPER STORAGE OF COMBUSTIBLES
7 PROPER STORAGE OF FLAMMABLEb
I OCCUPANT LOAD - POSTED
I• %
C. ELECTRICAL - HEATING
YEN
NO
NI
1 PROPER ELECTRICAL
/ ,
;
2 MAIN ELECTRICAL - DISCONNECT ACCESSIBLE
LOCATION
S MAIN GAS VALVE ACCESSIBLE O PROTECTED O
LOCATION
6 BOILER f_' GFA "' OTHER O
S PROPER VENTING
6 MOT WATER HEATER OAS 'I ELEC ❑
VIOLATIONS OF THE UNIFORM FIRE CODE AS ADOPTED:
UFC NUMBER
DATE
CLEARED
r
BY ORDER OF THE CHIEF:
You are hereby notified to immediately correct the conditions stated above, or show cause to the fire code Board of Appeals
why you should not be required to do so. A reinspection will be conducted after 141 days from the date of service of this
notice. If, at the time of reinspection, the same conditions exist, a summons to appear in court will be issued.
For any questions regarding this notice, please contact the Fire Prevention Bureau. 'I
INSPECTED
BY a
1. THE UNDERSIGNED, AM IN RECEIPT OF A COPY OF THIS INSPECTION � �. / 7
CAT / _COMPANY � ��` IMEOFINSP. � /
NOTICE AND AM AWARE OF THE HAZARDS AS INDICATED
REINSP EDmz
BY: - DATE DATE CORRECTED NOT COMECTED
WHITE 8169_ TOPSM YELLOW. Enalw OpmpanY PINK - FIN, PraY6HkM W-Millu GOLDENROD- FIN, PN,wnIHln Bwwu
0
Fire Prevention Bureau
FORT COLLINS, COLO. 80524
303-221-6570
September 12, 1989
Henry Glisan
Prospect Plaza Apartments
304 W. Prospect
Ft. Collins, CO 80521
Dear Mr. Glisan:
1 have enclosed an application for Request for Hearing by the Fire Board of
Appeals in the City of Fort Collins.
As explained on this form, the hearing is the last Thursday of each month
(September 28th) at 9:15 A.M. in the City Council Chambers at 300 Laporte Ave.
The application must be filed no later than September 21st at the City Building
Department, which is also located at 300 Laporte Ave. There is a $50.00 docket
fee which must also be filed at that time.
1 have also enclosed a copy of the Uniform Fire Code section that relates to
appeals. Keep in mind that the appeal must be for either alternate materials
or reasonable interpretation of the Code.
Pursuant to our conversation yesterday, if an appeal is not filed by September
21, 1989 for a September 28th hearing, I will be left with no other alternative
than to issue a summons to appear in Municipal Court for failure to comply with
the Code of the City of Fort Collins.
Thank you for your time and concern with this matter.
MGG:dede
Enclosures
Sincerely,
Mike G. Gavin
Assistant Fire Marshal
Inspection Services
PROTECTING LIVES & PROPERTY
• -A •
Fire Prevention Bureau
, h0 � R1 M1N UN
FOO RT COLLINS,I`'COLD. 80524
303-221-6570
July 25, 1989
Mr. Glissen
304 W. Prospect Street
Ft. Collins, CO 80521
Dear Mr. Glissen:
I am writing to confirm the fact that your property at 250-318 W. Prospect has
never been brought up to standards in the Uniform Fire Code. The section in
question regards the fire alarm requirements.
We have been attempting to work with you to resolve this issue for almost a year
(since you obtained the property from Mr. Grady), yet these buildings continue
to be in violation of the Uniform Fire Code, as adopted by the City of Fort
Collins. This is a situation that we will not allow to continue.
It is necessary for either you or your representative to contact me by September
8, 1989 to begin to resolve this issue, or a summons will be issued for you or
your business representative to appear in Municipal Court.
Sincerely,
Mike G. Gavin
Assistant Fire Marshal
Fire Inspection Division
MGG:dede
cc: R. Frasco
PROTECTING LIVES & PROPERTY
C:tv Attorn
Citv of Fort Collins
June 28, 1988
Mr. Michael Nix
250 West Prospect Road, #5
Fort Collins, CO 80526
Re: Municipal Court Case #43219
Dear Mr. Nix:
Please be advised that the above -mentioned case has been dis-
missed without prejudice at the request of the Poudre Fire
Authority. My understanding is that the ownership of the prop-
erty involved in that case has been transferred and that the
Poudre Fire Authority intends to work with the new owners in an
attempt to obtain compliance with the Code prior to making a
determination as to whether a new summons should be issued for
the violation.
As a result of this case being dismissed without prejudice,
please disregard any court dates which you had relating to the
same.
Sincerely,
t ri . ruin
Kathleen M. Allin
Assistant City Attorney
KMA:kkg
Enclosyres
cc: ,Art Echdahl, Poudre Fire Authority
George Hass, Attorney
300 LaPorte Avenue, P.O. Box 380, Fort Collins. CO 30522-0580 • (303) 221-6320
23 Brookside Dr.
Littleton, Colo. 80121
June 13, 1988
Mr. Steve Miller Ass't Chief
Poudre Fire Authority
505 Peterson Ref: Fire Safety Trial
Ft. Collins, Colo.-O0524 June 24, 1988
250-318 W. Prospect
Dear Mr. Miller:
Please be advised that in our approaching trial of
June 24, 1988, that I will not defend Prospect Plaza
against the Poudre Fire Department request for
additional fire protection systems, and therefore
allegations of operating unsafe buildings.
The property is being returned to the former owner,
H.C. Glisan, who has been informed of the fire
department request, and our differences of opinion
on fire safety at the property.
Mr. Glisan may be contacted at 14077 E. Arizona Ave,
Aurora, Colo. 80012, for your continuing fire safety
program.
Than you
Ken G. Gra
rc H.C. Glisan
Mike Nix
John Corbridge Attorney
Larimer County Court
23 Brookside Dr.
Littleton, Colo. 80121
April 25, 1988
Mr. Steve Miller
Assistant Fire Marshal
Poudre fire Authority
505 Peterson
Ft. Collins, Colo. 80524
Dear Mr. Miller I received your letter dated April 11, 1988
on April 22, 1988 concerning Prospect Plaza 250-318 Id.
Prdspect. In your recent inspection I assume you noticed
that we have installed independent smoke detectors in the
areas designated in my recent reply and first plan. This
alarm gyptem is in place in all apartment buildings. It is
installed and operational.
I have asked Mr. Nix to provide Chadwick Electric with a
copy of your letter of April 11, 1988, and come up with a
plan and proposal that is based on your letter and vour
meeting of Rob weber and Mr. Nix earlier in April. This
was requested last week and Mr. Chadwick should have something
for you to review shortly.
Thank you for vour letter and concern. We too are interested
in the best fire safety possible. For that reason we have
completed the redent outlined detector installation even
before you considered the plan outlined in my last letter.
I presume the installation of those detectors improves
the fire safety and reduces potential accidents. We hope to
have Chadwicks plan very soon.
Thank You
Ken Grady,
OEM,
w
T
Phone 303-22*70
Vlap1 •1. • `
'Iff
CERTIFIED, RETURN RECEIPT
Ken Grady
23 Brookside Drive
Littleton, CO 80121
Dear Mr. Grady:
April 11, 1988
RE: Prospect Plaza Apartments
250 - 318 W. Prospect St.
This letter is in reply to your correspondence to Art Eckdahl dated
April 6, 1988. In your letter you stated that you have not been given
clear direction about what is required and feel that the imposed deadline
is unrealistic. I have reviewed the file on your building and have
discussed this situation with those involved from our Department (Art
Eckdahl, Ralph Kettle, Glenn Levy, and Rob Weber).
The following comments are based on the above -stated research:
1) All indications are that you have been clearly informed as to what
you are required to do in regard to the fire alarm systems. On
4/21/87 you and Mike Nix met with Rob Weber of our Department in
regard to what was required. Rob outlined what was needed, and
you agreed to have Chadwick Electric start installation by
5/18/87.
2) In regard to May 1, 1988 being an unrealistic timeline, you have
repeatedly failed to meet promises to comply with this requirement
and/or attend meetings regarding this subject. This situation has
remained unresolved since 10/16/84 when Warren Jones informed Mr.
Nix of the problem. Three and a half years is much too long and
this deadline has been set to provide some movement on this
problem.
You must submit to me by May 2, 1988 the following:
1) A copy of the contract you have entered into to provide
installation of an approved fire alarm system in all the
apartments located at 250 - 318 W. Prospect St., Ft. Collins, CO.
The alarm installer must be licensed to work on alarms in the City
PROTECTING LIVES & PROPERTY
Ken Grady
April 11, 1988
Page 2
of Ft. Collins. The fire alarm shall be an automatic and manual
system, installed in accordance with National Fire Protection
Standard 72. This system shall provide smoke detectors in all
common areas (hallways); pull stations at each exit on each level;
and heat detectors in storage areas, furnace or boiler rooms,
laundries, and other similar areas. The system shall be designed
such that any device, when activated, will initiate an audible
alarm which can be heard in any part of the building.
2) The designated contractor must submit to me by May 9, 1988, two
sets of plans and other required documents for me to approve.
Have them contact me prior to the deadline if they have any
questions as to what is required of them.
3) Installation of the alarm systems must begin no later than May 16,
1988.
4) All alarm systems shall be installed and operational no later than
June 13, 1988.
Failure to comply with any of these requirements will result in the
issuance of a summons on this matter. '
If you have any questions please call.
Sincerely,
—4;�5 Aa
Steven S. Miller
Assistant Fire Marshal
ssm/sw
Phone 3030-6570
FORT COLLINS, COLO.80524
March 23, 1988
CERTIFIED.RETURN RECEI P
Mr. Ken Grady
23 Brookside Drive
Littleton, CO 80121
RE: Prospect Plaza Apartments
250 - 318 W. Prospect St.
Dear fir. Grady:
I'm sorry that the weather prevented you from attending the scheduled
meeting on March 10, 1988 regarding the fire alarm requirements at your
multi -unit apartment complex located at 250-318 West Prospect Street,
Fort Collins, Colorado. We did meet with your manager, Mr. Nix, at that
time and reviewed the history of this case with him.
As I explained to him, this situation has dragged on since 1984 and your
complex must conform to the fire alarm requirements of the Uniform Fire
Code as soon as possible. To the best of my knowledge, your apartment
complex is the only one in our jurisdiction that has not complied with
this Fire Code requirement. It is also one of the largest complexes of
this type in our jurisdiction.
Approximately one year ago you entered into an agreement with Rob Weber
of our Fire Prevention Bureau to complete a complying alarm system
"within one month". This agreement was never completed by you.
We must receive documentation (i.e. plans for review or a contractual
agreement) no later than April 15, 1988, showing that the alarm system
in your complex will be completed to full Fire Code compliance by flay 1,
1988 or a summons will be issued in this matter.
I'm enclosing a listing of fire
our jurisdiction. All of these
Code requirements. If you need
me.
Yours truly,
M1-7
J
rn
O J
Art D.
Eckdahl
"'
c
w
c
g�
Asst. Fire Marshal
m
{L
w
<o
_
Cc
cc
W
wa
z
ADE/sw
Ulu
oW
S
LL
Uz
M1
LL
a¢
D
a
F
W
i
W
2 O
�Z
Q
alarm installers approved to operate in
contractors are familiar with the Fire
additional information, please contact
m
y
M
M �
d
N
o
m
oo
s_
Q
v
o
"
cm
as
p
LL
3 0
L
S O
Y
G
•
Y9i"
'^
u)
O
0
1191OP-C"I'O'd'o'S'n • LBBL'god'DM w,oj sd f
Phone 303-2• 570
`' •FORT COLLINS,• •
March 4, 1988
Mr. Ken Grady
23 Brookside Drive
Littleton, CO 80121
Dear Mr. Grady,
I am writing to confirm our meeting scheduled for Thursday March 10, 1988
at 1:30 p.m. at 304 W. Prospect Street in Fort Collins, Colorado.
As we discussed by phone, this meeting is to clarify the fire alarm
requirements that apply to your buildings at 250-318 W. Prospect St. We
have been attempting to work with you to resolve this issue since October
of 1984, yet these buildings continue to be in violation of the Uniform
Fire Code, as adopted by the City of Fort Collins. This is a situation
that we cannot allow to continue.
It is necessary for
meeting or a summons
Municipal Court.
RK/cs
cc: Steve Miller
Art Eckdahl
either you or your representative to attend this
will be issued for you to appear in Fort Collins
Sincerely,
Ralph Kettle
Fire Inspection Coordinator
PROTECTING LTYES & PROPERTY
Phone 303-221-6570
• OW 1JPI1 L'iwVlI
FORT COLLINS, COLO. 80524
January 16. 1987
Mr. Ken Grady
23 Brookside Dr.
Littleton, CO 80121
Dear Mr. Grady:
Our records show you as the responsible party/owner of the Prospect
Plaza Apartments, 250-318 W. Prospect, Fort Collins, Colorado, 80521.
As required under the Uniform Fire Code, 1985 Edition, as adopted
by the City of Fort Collins, Section 10.306(a) and by Poudre Fire
Authority Inspection Policy #84-4, your buildings must have an approved
fire alarm system. This violation has been cited for the last three
years without compliance. It is imperative that you contact me within
30 days to discuss the violation and establish a timeline for
compliance.
Sincerely Glenn M. Levy
Fire Inspection Coordinator
GML/sw
cc: Uniform Fire Code requirements
Poudre Fire Authority Policy #84-4
Requirement letter of 3/5/84
PROTECTING LIVES & PROPERTY
FA
Fire Prevention Bureau - 221-6570
505 Peterson, Fort Collins. CO. 80524_
TATION INSPECTION COMPLAINT
/ h[ Master Building File Date 2� t_` Time
0 General File R/efe'r1reVo
LOCATION/ADDRESS`(
REQUESTING PERSON/CO./PHONE #
x
ACTION REQUESTED J
PREFERRED DATES & TIMES
NATURE OF CALL
)INGS:
�
I
aYmh � f4
r1PP
P
�
� t1 JI 0( f
�im�, J
trk L IQ
IU =\.CNI\i Date
i I
Phone 303-482-9020
SOS PETERSON - _ --
1
Hi•�
L FORT COLLINS, COI O. �05?4
X)
yt
I11� �Y
. • o _Ii r::17: M4'. :
Mr. Michael hick, 11anager
Prospect Plaza Apartments
304 W. Prospect
Fort Collins, CO 80521
Dear Mr. Nick:
Pursuant to our recent conversation concerning the boiler room in your Laun-
dromat, I agree with Company Officer Mark Sprenger, that sprinkler protection
is an acceptable alternative to retroactively installing a one -hour fire ra-
ting around the boiler room. Specifically, this one -hour rating is required
by the Building Code when the boiler or heating plant exceed 400,000 BTU's
per hour input.
It is my understanding from talking to Mark Sprenger, that there is a 2" water
service to this room. If this water service can supply the fire flow needed
for this small sprinkler system, it is permissible to use this rather than
providing a new water supply. Please remind who ever designs and installs
this system, to have their plans'reviewed and approved before installation
begins.
related -mate �+e-d-i
e'
1L�95UM =-Ahe:-datemf:i is--�etten �;" ere ire=several:;a_arm_con rac ors: "
famaa-iar with this-re`qu%cement i_n`the area ivho cM
be contacted to biif- this
worm= � QfP,C 1 UK lL4u
If you have any questions, please contact me at any time. Thank you for your
attention to these matters.
Sincerely,
Warren D. Jones,
Inspector
WDJ/cs
PROTECI-ING LIVES & PROPERTY